XCLK
DB-B
Fed from: SMSB
Location: GROUND FLOOR ELECTRICAL ROOM
/ RCD Size
mm2
R 15 4 4
1 Y 15 4 4
B 15 4 4
R 15 4 4
2 Y 15 4 4
B 15 4 4
R 20 4 4
3 Y 15
B 15 4 4
40 A, 3PH RCD 100 mA
R 20 4 4
40A TP&N ISOLATOR
4 Y 20 4 4
B 10 2.5 2.5
R 10 4 1.5
5 Y 20 4 2.5
B 10 2.5 1.5
R 10 2.5 2.5
6 Y 10
B 10
R 15 4 4
7 Y 15
B 15
R 15
8 Y 15
B 10
Incoming Cable Size/Type: 4c 10mm² XLPE/SWA/PVC + 1c 10mm² ECC
Main Breaker Type & Rating: 40A ISOLATOR+ 100mA RCD 40A 3ph
800
1000
1000
150
300
3250.00
9.8
SMSB
4c x 95mm² XLPE/SWA/PVC +1c x50mm² ECC
4 WAY TP MCCB WITH 250ATP MCCB MAIN BREAKER
Location: ELECTRICAL ROOM
Fed From:
MCCB
C.C.T.NO DESCRIPTION RATING
A mp.
1 R.Y.B- 1 DB-B 40
2 R.Y.B- 2 SF FOR EXHAUST HOOD-1 20
3 R.Y.B- 3 SF FOR EXHAUST HOOD-2 20
4 R.Y.B- 4 SF FOR FRYERS-1 40
5 R.Y.B- 5 SF FOR FRYERS-2 40
6 R.Y.B- 6 SF FOR FRYERS-3 40
7 R.Y.B- 7 SF FOR FRYERS-4 40
8 R.Y.B- 8 SF FOR FRYERS-5 40
9 R.Y.B- 9 SF FOR FRYERS-6 40
10 R.Y.B- 10 SF ADDITIONAL 40
11 R.Y.B- 11 SF FOR CHILLER 20
12 R.Y.B- 12 SPARE 40
TOTAL CONNECTED LOAD 102.80
ECC
N BREAKER
WIRE TOTAL
LOAD IN KW
SIZE LOAD
m.m2. K.W R Y B
4c 10mm² XLPE/SWA/PVC + 1c 10mm² ECC 9.80 3.27 3.27 3.27
4c 6mm² XLPE/SWA/PVC + 1c 6mm² ECC 3.00 1.00 1.00 1.00
4c 6mm² XLPE/SWA/PVC + 1c 6mm² ECC 3.00 1.00 1.00 1.00
4c 10mm² XLPE/SWA/PVC + 1c 10mm² ECC 12.00 4.00 4.00 4.00
4c 10mm² XLPE/SWA/PVC + 1c 10mm² ECC 12.00 4.00 4.00 4.00
4c 10mm² XLPE/SWA/PVC + 1c 10mm² ECC 12.00 4.00 4.00 4.00
4c 10mm² XLPE/SWA/PVC + 1c 10mm² ECC 12.00 4.00 4.00 4.00
4c 10mm² XLPE/SWA/PVC + 1c 10mm² ECC 12.00 4.00 4.00 4.00
4c 10mm² XLPE/SWA/PVC + 1c 10mm² ECC 12.00 4.00 4.00 4.00
4c 10mm² XLPE/SWA/PVC + 1c 10mm² ECC 12.00 4.00 4.00 4.00
4c 6mm² XLPE/SWA/PVC + 1c 6mm² ECC 3.00 1.00 1.00 1.00