TEST REPORT FOR

CIRCUIT BREAKER INDURE PVT LTD

STAR ELECTRICALS
2X800 MW STPP NTPC DATE: Page NO:
GADARWARA STAGE-1

CLIENT M/S NTPC GADARWARA


CONTRACTOR M/S INDURE PVT LTD
PROJECT 2X800 MW STPP NTPC GADARWARA M.P.
GENERAL DATA: Location:AET MCC ROOM

MAKE UNILEC
RATED VOLTAGE 415 V
RATED FREQUENCY 50 HZ
PHASE 3

Instrument Name Make Model No. Serial NO.


LT Megger Rishabh RISH INSU 10 E0033741
Multimeter Rishabh RISH Multi 14S 007305
Micro Ohm Meter Sakova CRM100 1001
Breaker Timing Kit Scope Se TIC103 1555

CIRCUIT BREAKER TEST : PANEL NO. – 8F1/01 BA OVER FLOW -1


1. Name plate details

Sr. No. 129034


Type AHA-6N-CS
Make C&S ELECTRIC

2. Insulation Resistance Test-


Insulation Resistance
Description Test Voltage
R Y B
Phase to Earth 500V >1 GΩ >1 GΩ >1 GΩ
3. Contact Resistance Test-
Resistance R Y B
21.3 µΩ 20.5 µΩ 21.5 µΩ

4. CB Coil Resistance-

Coil Rasistance
CC Coil 97.5 Ω
TC Coil 91.1 Ω
5. CB Time Test

Operation R Y B
Close Time 42 ms 43 ms 43 ms
Trip Time 26 ms 26 ms 27 ms

TESTED BY WITNESSED BY WITNESSED BY WITNESSED BY


Company STAR INDURE PVT LTD N.T.P.C. (Erection) N.T.P.C.(commissioning)
ELECTRICALS
Signature
Name &
Designation