Carga Lateral del Suelo

Datos

γs = 1.75 [tf/m³] → γs = 17.16 [KN/m³]


c = 3.50 [tf/m²] → c = 34.32 [KPa]

β = 0.00° → β = 0.00 [rad]


Φ = 30.00° → Φ = 0.52 [rad]
α = 56.00° → α = 0.98 [rad]
δ = 15.00° → δ = 0.26 [rad]

45 + Φ/2 = 60.00° → Angulo del plano de falla

Coulomb

+𝜙) 〗 /(sin^2⁡𝛼⁡⁡sin⁡〖 (𝛼−𝛿) 〗⁡ [1+√((sin⁡〖 (𝜙+𝛿) 〗⁡⁡ sin⁡〖 (𝜙−𝛽) 〗 )/(sin⁡〖 (𝛼−𝛿) 〗⁡⁡ sin⁡〖 (𝛼+𝛽) 〗⁡ ))]^2⁡)

�_(𝑎⁡𝐻𝑂𝑅𝑍)=cos⁡𝛿⁡�_𝑎

β → Angle of backfill slope


Φ → Angle of internal friction of the soil
α → Wall slope angle from horizontal (90° for vertical face)
δ → Angle of friction between soil and wall (Usually asumed to be 2/3Φ to 1/2Φ)

Ka = 0.676
Ka.HORZ = 0.653 → Kp.HORZ = 1.530
Ka.VERT = 0.175

Rankine
�_𝑎=(cos⁡𝛽−√(cos^2⁡𝛽−cos^2⁡𝜙⁡))/(cos⁡𝛽+√(cos^2⁡𝛽−cos^2⁡𝜙⁡))

�_(𝑎⁡𝐻𝑂𝑅𝑍)=cos⁡𝛽⁡�_𝑎

Ka = 0.333
Ka.HORZ = 0.333 → Kp.HORZ = 3.000
Ka.VERT = 0.000
Altura Critica para Suelos Cohesivos

𝐻_𝑐=2𝑐/(𝛾√(�_𝑎⁡))

Hc = 4.86 [m] → Coulomb


Hc = 6.93 [m] → Rankine

F.S. = 2.00

Hc = 2.43 [m] → Coulomb


Hc = 3.46 [m] → Rankine