2. Frequency: 50Hz
4. LCD Display with display language in English for current, voltage and time display
5. Timer feature with range 0 to 999.999 sec or more, with 1ms resolution or better
8. Current outputs AC: range 0-100A with no load voltage (min) of 10V, output voltage (min) 7.7V
(100A) load or better.
i). Range 0-250V with output voltage min 220V (2.7A) or better,
ii). Range 110V AC (fixed) output voltage min 110V (0.3 A) or better,
iii). Range 0-350V DC, output voltage min 280V (2A) or better,
iv). Range 20-220V DC (Stab.) with output voltage min. 200V (0.25A)
11. Built-in capacitor provided for phase-shift when testing directional protection and set of resistor to
divide voltage.
14. Test lead set with stackable safety plugs and spade tongue connectors along with a rugged transport
case.
15. Supplier shall provide detailed technical catalogue along with the offer.
16. Supplier shall provide calibration certificate along with the supply.