0% found this document useful (0 votes)
773 views1 page

Single Line Diagram-Layout1

The document summarizes the specifications and wiring details of a new 480V panel located in an EE room. It has a 125A main breaker feeding six circuits, with the first two circuits supplying welding machine outlets at tracks 4 and 5 rated for 100A each, and the remaining circuits supplying screw jack outlets or marked as spares at 50A each. The panel has a NEMA 2 enclosure, is wall mounted, and has a minimum short circuit rating of 10kA.

Uploaded by

Lesther Sosa
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
773 views1 page

Single Line Diagram-Layout1

The document summarizes the specifications and wiring details of a new 480V panel located in an EE room. It has a 125A main breaker feeding six circuits, with the first two circuits supplying welding machine outlets at tracks 4 and 5 rated for 100A each, and the remaining circuits supplying screw jack outlets or marked as spares at 50A each. The panel has a NEMA 2 enclosure, is wall mounted, and has a minimum short circuit rating of 10kA.

Uploaded by

Lesther Sosa
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

PANEL : NEW PANEL VOLTAGE : 480V ENCLOSURE : NEMA 2

LOCATION : EE ROOM PHASE : 3 MIN.KAIC : 10


FEED : TOP WIRE : 3+G MOUNT : WALL MOUNTED

WIRES
CKT BREAKER CONNECTED LOAD CONDUIT (THHN/THWN)
LOAD DESCRIPTION VA
NO. P AF AT (RSC) LINE GROUND
1 3 100 100 WELDING MACHINE POWER OUTLET @TRACK 4 (2 NOS.) 5760 1920 1920 1920
2 3 100 100 WELDING MACHINE POWER OUTLET @TRACK 5 (2 NOS.) 5760 1920 1920 1920
3 3 50 30 SCREW JACK POWER OUTLET @ TRACK 4 (1 NO.) 2880 960 960 960
4 3 50 30 SCREW JACK POWER OUTLET @ TRACK 5 (1 NO.) 2880 960 960 960
5 3 50 30 SPARE 3000 1000 1000 1000 - - -
6 3 50 30 SPARE 3000 1000 1000 1000 - - -
TOTAL 23280 7760 7760 7760

FEEDER :

MAIN : 125AT, 125AF, 3P, 480V, 60Hz MCCB

TO GLSV
FEEDER NO. 34, 160 A RATING

NEW PANEL

@ EE ROOM
125 AT
125 AF

1 2 3 4 5 6

100 AT 100 AT 30 AT 30 AT 30 AT 30 AT
100 AF 100 AF 50 AF 50 AF 50 AF 50 AF
@ TRACK 4

@ TRACK 5

@ TRACK 4

@ TRACK 5
SCREW JACK POWER OUTLET

SCREW JACK POWER OUTLET

SPARE

SPARE
WELDING MACHINE POWER OUTLET

WELDING MACHINE POWER OUTLET

You might also like