Professional Documents
Culture Documents
0-1
October 2015
Sheet 36 001
Systems
Contents
Resistance Grounding Resistance Grounding Systems
High Resistance Grounding SystemMedium Voltage . . . . . . . . . . . . . . 36.1-1
22
23
High Resistance Grounding SystemLow Voltage . . . . . . . . . . . . . . . . . 36.2-1
Specifications 24
See Eatons Product Specification Guide, available on CD or on the Web.
CSI Format: . . . . . . . . . . . . . . . . . . . . . . . . . . . 1995 2010
High Resistance
25
Grounding SystemMV . . . . . . . . . . . . Section 16451A Section 26 05 26.11
High Resistance 26
Grounding SystemLV . . . . . . . . . . . . . Section 16451B Section 26 05 26.13
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
C-HRG Free-Standing
NEMA 1 Enclosure
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
51N
23
24
59
25
Utility
26
Delta HRG
59 27
Wye HRG Generator 28
59
29
Bus Bus
Duct Duct 51
51N 30
31
C-HRG Free-Standing NEMA 1 Unit
5 kV Switchgear
General Description 32
Where continuity of service is a high
priority, high resistance grounding can
add the safety of a grounded system 33
while minimizing the risk of service Conduit
interruptions due to grounds. The Cable
concept is a simple one: provide
Bus
Duct
34
a path for ground current via a
grounding transformer (with adjust-
able resistance across its secondary) To MCC To Power Circuit 35
that limits the current magnitude
and a monitor to determine when
an abnormal condition exists. Figure 36.1-1. HRGHigh Resistance Grounding System 36
The ground current path is provided Seismic Qualification
at the point where the service begins, 37
by placing a predominantly resistive
impedance in the connection from
system neutral to ground. Control 38
equipment continuously measures
ground current; a relay detects when the
current exceeds a predetermined level. Refer to Tab 1 for information on 39
An alarm alerts building personnel that seismic qualification for this and
a ground exists. The system has built-in other Eaton products.
fault tracing means to assist in finding 40
the source of the ground. A 120 Vac
supply (remote) is required for control
power for the system. 41
42
43
Application Issues Ground Current Detection When the fault is cleared, the current/
22 This member of Eatons medium voltage Any time a system is energized, voltage relay will reset. If the reset
a small ground current called the control is set on auto, the lights will
metal-clad switchgear family has return to normal on, ground fault
capacitive charging current will
23 actually been around for many years.
However, it is now offered as a stand- be observed. For medium voltage off, and the ground alarm contacts will
(4200 V and below) systems, this re-transfer. If the reset control is set on
alone unit that can be added to exist- manual, the lights and relay contacts
naturally occurring current is typically
24 ing installations. The C-HRG is used
3 A or less. will remain latched until the operator
to protect an electrical distribution turns the reset control to reset. The
system from damaging transient over- When one phase becomes grounded, lights and ground alarm contacts will
25 voltages caused by ground faults. additional current above the charging then return to normal. The system
It also provides a means to locate the level will flow. As all ground current can be reset only if the fault has
ground fault, therefore extending the must flow through the grounding been cleared.
26 life of the distribution system. resistor/grounding transformer
assembly, an ammeter in this circuit During a fault, the optional alarm
Ratings and Configurations horn can be silenced at any time by
will read the total amount of ground
27 The C-HRG MV is offered at the current. By placing a current-sensing using the alarm silence pushbutton.
5 kV class rating. It can be applied relay in series with the ammeter, the It will not re-sound until either the
to delta or wye ungrounded three- current relay can be adjusted to pick- system is reset, or the re-alarm timer
28 wire distribution systems. Standard up at a level in excess of the capacitive expires. The re-alarm timer is activated
dimensions are 36.00-inch (914.4 mm) charging current, thus indicating the by the alarm silence control. If the
W x 40.00-inch (1016.0 mm) D x abnormal condition. horn has been silenced but the fault
29 92.00-inch (2336.8 mm) H. has not been cleared, the timer will
Alternatively, an optional voltmeter- run. It has a range of 248 hours.
4200 V (Maximum) Delta Systems relay can be connected across the When the timer times out, the horn
30 To add high resistance grounding to an grounding resistors. The voltage will re-sound, alerting maintenance
ungrounded delta-connected system, across the resistors is proportional personnel that the fault has not
a neutral point must be created. Three to the amount of ground current. The been cleared.
31 single-phase transformers can be voltmeter-relays pickup adjustment
interconnected in a wye-broken delta is set above the capacitive charging Test Circuit
configuration to provide such a neutral current, to the desired detection level. A test circuit is provided to allow the
32 point. The transformers and grounding
resistors are chosen to limit the ground In both current and voltage detection
user to quickly determine that the
system is working properly. The test
current to a maximum value of 6 A. methods, the ground current ammeter circuit will operate only under normal
provides a direct reading of the total
33 Application Note: The neutral point may actual ground current present in the
conditionsit will not allow testing if
not be used to serve phase-to-neutral loads. the system is sensing a fault. The test
system at that time. It will be helpful operation does not simulate an actual
Also, this technique may be applied on wye-
to periodically note the ammeters
34 connected sources when the neutral point
reading: a trend toward higher values
system ground fault. It does, however,
is not conveniently accessible from the test the complete controls of the fault
service entrance location. One delta high may indicate the need for equipment indication and pulsing circuitry. The
35 resistance grounding would ground the maintenance, and hence reduce the system then reacts as it would under
5 kV system. occurrence of unplanned shutdowns. actual system ground conditions
Indication and Alarm Circuits lights transfer, alarm contacts transfer
36 4200 V (Maximum) Wye Systems and the (optional) horn sounds.
To add high resistance grounding to When a fault is detected, an adjustable
a wye-connected system, resistors time delay is provided to override Pulser Circuit
transients. When the time delay has
37 are placed across the secondary
been exceeded, the green normal
The pulser circuit offers a convenient
of a grounding transformer whose means to locate the faulted feeder and
primary is placed in series with the light will turn off, the red ground trace the fault to its origin. The pulser
fault light will turn on, and the
38 neutral-to-ground connection of the
ground alarm contacts will transfer.
is available any time a fault has been
power source. The resistors are detected. The pulse intervals are con-
chosen to limit the current to a If equipped with the optional alarm trolled by an adjustable recycle timer.
horn, it will sound.
39 maximum value of 6 A. The pulse light flashes on and off,
The grounding transformer secondary corresponding to the on-off cycles
Application Note: Per 1999 NEC 250.36(4),
line-to-neutral loads may not be connected breaker must be closed for the system of the pulser contactor. The pulser
40 to a system that the neutral is resistance- to be operational. Should this breaker contactor switches a bank of resistors
grounded. Also, if the system has two be opened at any time, the system will on and off, thus allowing a momentary
switchable sources not permanently signal a ground fault condition as a increase in the ground current
41 connected to the bus, two wye-type fail-safe feature. The breaker must be (approximately a 4 A current pulse
grounding systems are required as closed to clear the alarm signal. above the ground current).
shown in Figure 36.1-1.
42
43
24 Ungrounded To Ungrounded
To
Wye Distribution Delta Distribution
Circuits Circuits
25 X0
26 5 kV - CLE
Fuses 5 kV - CLE
Fuses
27 [1]
Mechanical
Control
Mechanical
Interlock
Interlock
Power
28 Transformer
3-Auxiliary
Control
Power
29 Transformers
Secondary Secondary
Circuit Circuit
B Breaker B Short Circuit B B Short Circuit
Breaker
30 T.B. T.B.
CT 10/10 A
Option Option
CT 10/10 A
2 4A AM 4A
2 AM
Pulsing Resistor
Pulsing Resistor
5A 5A
Pulsing Contactor
3 3
33
Pulsing Contactor
4 6A 6A
4
5IN
34 5IN
Ground Ground
35 Current Current
Adjustment Adjustment
Optional
Detector
Optional
Detector
Voltage
Voltage
T.B. T.B.
36 Current Current
Detector Detector
37 20 A 20 A
To To
Remote Control 120 V Remote Control 120 V
Fuses Fuses
38 Alarm Circuit 60 Hz Alarm Circuit 60 Hz
Supply Supply
20 A 20 A
39 Optional Optional
40 G R W G R W
43
24
25
Vent
26
40.00
(1016)
27
28
Primary Conduit
3.50
Entrance
(88.9)
29
2.00 (50.8) Diameter
8.50 Knockout
(215.9) for Secondary
Conduit Entrance
3.62 30
(91.9)
1.50 3.25
(38.1) (82.6) 31
3.76
(95.6) Plan View
32
92.00
(2336.8)
33
0.81 0.81
(20.6) (20.6)
0.562 (14.3) Diameter (4) 2.75 34
(69.9)
2.50 3.00 35
2.75 (63.5) (76.2)
(69.9)
3.00
Ground
Provision
36
(76.2)
Entrance
2.50
(63.5) 37
3.75
(95.3)
38
7.12
Primary Conduit
(180.9) Entrance
39
3.75
(95.3)
36.00 40
(914.4)
3.50
(88.9) 9.38 2.75
Front View 3.75 (238.3) (69.9) 41
(95.3)
2.75
(69.9)
3.00
(76.2)
Secondary Conduit
Entrance
42
1.75
(44.5)
Approximate Weight = 2000 lb (1800 kg) Floor Plan 43
Figure 36.1-4. NEMA 1 Free-Standing
1 Minimum required clearances are: front 36.00 inches (914.4 mm), rear 30.00 inches (762.0 mm), left or right sides6.00 inches (152.4 mm).
Product Selection
33 Eatons C-HRG High Resistance Grounding Assembly can be completely described by an 8-digit
catalog number: MVRG-_ _ _ _ _ _ _ _
34 Table 36.1-2. High Resistance Pulsing Grounding Systems Catalog Numbering System
35 MVRG F W W C L L T S
2 8
Ammeter will indicate current pulses at a
rate matched by white pulse lamp. 10. Phase and neutral terminals
B. Test each feeder conduit with clamp-on
ammeter to locate conduit that causes the accept #12 AWG to #8 AWG.
clamp-on ammeter to pulse. Fault is in that
conduit or in connected load. See instruction
manual for information on fault locating.
11. Ground terminal accepts wire sizes
0 Ac
Amperes
10 C. Once fault has been located:
1. Open feeder
2. If reset control is in manual, reset system
3. Clear fault
from #8 AWG to 500 kcmil. Ground 34
4. Close feeder
5. Return system control switch to normal bus is 1/4-inch x 2 inches copper.
To Test Ground Fault System
Pulse
Group Current
Note: Test circuit will not operate if system is presently
detecting a ground fault. 12. The paint is applied using an 35
Ammeter A. Turn and hold system control selector switch in test
position. After time delay expires, lights will transfer
to indicate a fault, and pulser will begin operating.
electro-deposition coating system.
W B. Return system control switch to normal. Reset Metal surfaces are prepared by
36
system. Turn reset control to auto or manual.
spray and dip cleaning, and
System Control
Normal
Reset Control
Manual
Ground Normal
phosphatizing. The standard
Pulse Test Auto Reset Fault color is ANSI 61, light gray.
R G 13. Line side fuses are rated for use up 37
to 200 kA fault current systems. All
other fuses are rated to protect
Ground Voltage
Meter Relay
each circuit as required. 38
Device 59N
Voltage
14. The resistors are wire wound on
Meter Relay a steel tube, insulated by Micarta. 39
S V Resistors are mounted on a steel
Alarm
Horn
rack with ceramic insulators.
40
Meter Relay Setpoint Adjustment
1.
Instruction
Press S & up-arrow keys
Display
PAS 15. No. 8 AWG wire is used for internal
2. Press S key SP1, then setpoint
3. Adjust setpoint 1 using setpoint connections from the neutral point
up/down arrow keys
to ground. Control connections
4.
5.
6.
Press S key
Adjust setpoint 2 using
up/down arrow keys
Press S key
SP2, then setpoint
setpoint
END,RUN,
are a minimum of #14 gauge. All 41
meter reading
See meter relay manual for complete Ground Alarm control wires insulation is type SIS.
programming instructions.
23 F 4 W N C R N S F 4 6
24 Enclosure Type System Frequency
F = Free-standing, Type 1 Distribution Wire Harness 5 = 50 Hz
System Voltage Length for N
25 S = Free-standing, Type 1
with screened vents 6 = 600 V
(No Enclosure)
6 = 60 Hz
Audible Alarm
34 N = No audible alarm
R = Alarm horn with re-alarm timer
35 1 Low pass filter attenuates high frequency ground current signals, as typically produced by variable speed drives, allowing the ground relay to see only
power frequency ground current.
36
37
38
39
40
41
42
43
Technical Data
22
HV 600/347 V (Max) Wye, Ungrounded HV 600 V (Max) Delta, Ungrounded
23
To To
Distribution Distribution
Equipment Equipment
24
N A B C G R W A B C G R W
CLF
CLF
Control
Zig-Zag
Grounding
CLF
CLF
Control
25
Circuit Transformers Circuit
CLF CLF
AM 51N AM
26
28
G G
29
Figure 36.2-3. Four-Wire SourceFault Detection via Current Relay Figure 36.2-6. Three-Wire SourceFault Detection via Voltmeter Relay
39
A B C W A B C G R W
G R
Zig-Zag
Grounding
CLF
CLF
Control
CLF
CLF
Control 40
Circuit Circuit
Transformers CLF
CLF
AM 51N Wye -
Broken Delta
41
Pulser Grounding 59N
Grounding Resistor Resistor
Transformers
Pulser
Resistor
Grounding
Resistor
Test Test
Resistor
42
Resistor AM
G G
43
Figure 36.2-5. Three-Wire SourceFault Detection via Current Relay Figure 36.2-8. Three-Wire SourceFault Detection via Voltmeter Relay
22 2.00 0.56 (14.2) Dia. (4) 2.36 0.63 (16.0) Dia. (6)
(50.8) (59.9)
5.00 x 5.00 (127.0 x 127.0)
Conduit Entry Area 5.00 x 5.00 (127.0 x 127.0)
23 0.75
(19.1)
(Top and Bottom)
3.41
(86.6)
Conduit Entry Area
(Top and Bottom)
24.00 3.00 37.00
(609.6) 3.47 (76.2) (939.8) 5.00
(88.1) 2.36
24 (59.9)
(127.0)
16.00 5.00
3.13 Front 5.00
25 (79.5) (127.0)
(406.4) (127.0)
Plan View
Front 1.44
0.94
Plan View (36.6)
26 4.00 (101.6) Vent Neutral and (23.9)
Phase Terminals
#12 to #8 AWG Neutral and Phase Terminals
#12 to #8 AWG
27 Ground
Current
Ammeter Instruction
Nameplate Ground
Current
Ammeter
28 Instruction
Nameplate
29
92.00 93.00
30 (2336.8) (2362.2)
Voltmeter Alarm
Relay
31 Horn
Voltmeter
Relay Alarm
Horn
32
Resistors Resistors
Ground Terminals Ground Terminals
33 #8 to 500 kcmil #8 to 500 kcmil
Grnd Bus
Grnd Bus
34 21.00
(533.4)
26.00
(660.4)
Front View Approx. 650 Lb (295 kg) Front View Approx. 950 Lb (431 kg)
35
Figure 36.2-9. NEMA 1 Free Standing Figure 36.2-10. NEMA 3R Outdoor
36
37 12.00
(304.8)
2.00 4.00 (101.6)
5.00 x 5.00 (127.0 x 127.0)
(50.8)
Conduit Entry Area
Top View
38 1.75
0.375 (9.5) Dia. (4)
(44.5)
Ground
Current
Ammeter Instruction
1.13
0.438 (11.1) Dia. (4)
39 Nameplate (28.7)
0.50 (12.7)
13.00
(330.2) 1.13 (28.7) KOs
(3)
40 50.00 52.00
Neutral and 12.50
(317.5)
13.50
(342.9)
Phase Terminals
(1270.0) (1320.8) #12 to #8 AWG
Ground Terminals
41 #8 to 500 kcmil
17.13
(435.1)
16.38
(416.1)
Voltmeter Alarm
Front View Side View
42 Relay Horn
Figure 36.2-11. NEMA 1 Wall Mounted Dimensions for estimating purposes only.