Professional Documents
Culture Documents
Institution of Structural Engineers-Recommendations For The Permissible Stress Design of Reinforced Concrete Building Structures PDF
Institution of Structural Engineers-Recommendations For The Permissible Stress Design of Reinforced Concrete Building Structures PDF
February 1991
Thanks are due to F. N. Pannell, BSc, MScTech, PhD, CEng, MIStructE, who
prepared the column design charts given in Appendix B.
This amendment has been prepared in order to keep the document up to date, so that it may be used as an
alternative to BS 8110 or Eurocode 2. This amendment covers changes made in Amendments 1-4 to BS 8110-
1:1997, the introduction of BS EN 206-1, BS 8500-1 and BS 8500-2 and also changes in the Building Regulations.
Because some of the latest changes in these documents affect items which were previously altered in Amendment
Slip No. 1, for ease of use Amendment No. 2 is presented in consolidated form. It therefore supersedes Amendment
No. 1.
Background
BS 8110-1: 1997 reduced the materials safety factor on steel reinforcement compared with previous editions.
However the latest amendment to BS 8110 restores this partial safety factor to its previous value and the
characteristic stress of high tensile reinforcement is also increased from 460N/mm² to 500N/mm². In addition, the BS
8110 recommendations for specifying cover and concrete mixes for durability have been replaced by
recommendations in BS EN206-1 and BS 8500-1.
Recommendations for the permissible stress design of reinforced concrete building structures – Amendment No.2, August 2009
The Institution of Structural Engineers Page 1 of 6
(iii) PAV1 and PAV2 for external hardstandings and concrete subjected to freezing when wet.
(iv) FND2, FND2Z, FND3, FND3Z, FND4, FND4Z and FND4M for foundation concrete subject to attack by
chemicals including sulphates.
2.5.2 Designed concrete
As an alternative to standard designated concrete mixes, designed concrete may be used. A designed concrete mix
is specified by its strength class (e.g. C25/30) plus any other specific design requirements such as minimum cement
content, maximum water/cement ratio, etc.
2.5.3 Prescribed concrete
For prescribed concrete, the specifier prescribes the composition and constituents of the concrete mix.
2.5.4 Standardised prescribed concrete
BS 8500-2 specifies a range of standardised prescribed concrete mixes for use on small sites where the concrete
will be site-batched, or obtained from a supplier without third-party accreditation.
2.5.5 Proprietary concrete
Proprietary concrete is designed and produced by a supplier to meet specified performance requirements. The
supplier must produce evidence to the third-party certifier or the specifier to show that the mix meets the specified
requirements.
Table 2 For high tensile steel, amend heading to ‘high yield steel to BS4449 and BS4483’ and increase pst to
275N/mm² and psc to 235N/mm².
3A.5 Loadings Delete ‘and CP3: Chapter V’.
3A.6.1 Table 1 delete ‘grade of concrete’, insert ‘concrete strength class’, in column 1 replace ‘15 ... 60’ with
‘C12/15, C16/20, C20/25, C25/30, C28/35, C32/40, C35/45, C40/50, C45/55, C50/60’.
3A.6.4 Shear Stress
Delete sentence: ‘Where d exceeds 400mm, the term 4√(400/d) should be taken as unity.’.
3A.8 Delete existing text and insert:
Increases of permissible stresses for wind forces or earth pressures
The permissible stresses in concrete and in the reinforcement may exceed those given in subsections 3A.6 and
3A.7, respectively, by not more than 25% in the following situations:
(i) where the increased stress is caused by wind loading, or
(ii) where the increased stress is caused by earth pressure calculated in accordance with BS8002 and water
pressure calculated on the basis of a maximum credible water level. (NB if water and earth pressures are
calculated in accordance with CP2, no increase in stress is permitted.)
3A.11 In beams, where fst = 275N/mm², the clear distance between bars in tension should not exceed 170mm.
Table 5 – Anchorage bond and lap lengths as multiples of bar size for fully stressed bars
Recommendations for the permissible stress design of reinforced concrete building structures – Amendment No.2, August 2009
The Institution of Structural Engineers Page 2 of 6
Table 6 Basic span/effective depth ratios
cantilever 9 6.9
continuous 32 25.5
5 30 41 12 34 47 38 42
10 26 35 11 30 42 33 37
20 23 31 9 26 37 29 32
Delete existing Note 1, insert:
‘Note 1: For pst = 140N/mm², ratios may be increased by 20%. Intermediate stresses may be interpolated.’
Recommendations for the permissible stress design of reinforced concrete building structures – Amendment No.2, August 2009
The Institution of Structural Engineers Page 3 of 6
3C.6.3 Shear reinforcement
Amend first and second paragraphs to read:
If the effective shear stress exceeds the permissible value pv, shear reinforcement should be provided. This may
take the form of links, bent-up bars or fabricated components. However the effective shear stress on the critical
perimeter should not exceed 2pv The design of bent-up bars or other components should be justified by established
theory and/or test data.
Links in flat slabs should be designed in a similar manner to those in beams, with Av taken as the total area provided
on one perimeter of links (see Clause 3B.10.2). Spacing of link legs along the perimeter should not exceed 1.5d.
Where the effective shear stress on the critical perimeter exceeds 1.75pv, the permissible stress pst in equation (19)
should be reduced: where the effective shear stress is 2.0pv, pst should be taken as 0.75 times the normal value;
intermediate values for stresses between 1.75pv and 2.0pv may be interpolated.’
3J.1.6 Air Entrainment
Delete ‘When concrete lower than grade 50 is used ... aggregate’ and insert
‘When concrete with strength class lower than C40/50 is used, the minimum air content by volume of fresh concrete
at the time of placing shall be: 5.5% for 10mm max. aggregate, 4.5% for 14mm max. aggregate, 3.5% for 20mm
max. aggregate, 3.0% for 40mm max. aggregate’.
Add paragraph at end:
“When air-entrained concrete is specified with a strength class of C32/40 or over, or with a cement content greater
than about 350kg/m3, problems may be encountered in achieving the required strength, compaction and surface
finish. The inclusion of air in concrete reduces the compressive strength and the concrete producer may increase
the cement content to achieve the specified compressive strength."
Conditions of exposure Nominal cover to all reinforcement (mm) and designated concrete mixes
(BS 8500-1 exposure class) cover concrete cover concrete cover concrete
Internal except poorly ventilated rooms 25 RC20/25
with high humidity (XC1)
Recommendations for the permissible stress design of reinforced concrete building structures – Amendment No.2, August 2009
The Institution of Structural Engineers Page 4 of 6
Table 23 40mm aggregate: delete ‘-30’, insert ‘-20’.
3J.1.8 Reactive aggregates - alkali-silica reaction
At end: delete Concrete Society Report 30, add BRE IP 1/02, BS8500-1 and BS 8500-2.
3J.2 Resistance to chemical attack
Delete ‘Table 24 indicates the requirements for concrete exposed to sulphate attack’. Insert new para.:
‘Table 24 gives recommendations in accordance with BS8500 for 20mm aggregate concrete at least 140mm thick
exposed to sulphate attack in (i) natural ground with mobile water and pH > 5.5 or static water with pH > 3.5 or (ii)
brownfield site with mobile water and pH > 6.5 or static water with pH > 5.5. For concrete over 450mm thick, the
requirements of classes 2, 3 and 4 may be reduced by one class. A ‘brownfield’ site is one which might contain
chemical residues from previous industrial use or imported waste. For more detailed recommendations covering
other conditions and concrete mixes, refer to BS8500-1 and BS8500-2 and BRE Concrete in Aggressive Ground,
Special Digest 1.
Delete existing Table 24 (p. 81) and replace with the following:
Table 24 Recommendations for concrete exposed to sulphate attack
3K.1 General
Add at end:
‘Table 25 is based on the recommendations in BS8110-2. Alternatively, the cover recommendations in BS8110-1
may be used.’
3L.1.5 Delete
3L.2 Ties
(iii) Add at end: ‘Horizontal ties should be connected directly and robustly to the vertical structure. For columns, this
can generally be achieved by ensuring that a minimum of two bottom bars in each direction pass through the
column. Where top bars are used as ties, they should be restrained by links.’
Recommendations for the permissible stress design of reinforced concrete building structures – Amendment No.2, August 2009
The Institution of Structural Engineers Page 5 of 6
(iv) Delete and insert:
Vertical ties Each column and wall carrying vertical load should be continuously tied from the lowest to the
highest level. The tie should be capable of resisting a tensile force equal to the maximum load received by the
column or wall from any one storey, calculated in accordance with 3L.4. Where a column or wall is supported at
its lowest level by an element other than a foundation, the structural layout should be carefully checked to
ensure that there is no inherent weakness and that adequate means exist to transmit the dead, imposed and
wind loads safely from the highest supported level to the foundations.
Insert:
‘(v) Bars should be lapped, welded, or mechanically jointed together in accordance with 3A.12.11-16. A tie may be
considered anchored to another tie at right angles if the bars of the former tie extend either 12 diameters or
equivalent anchorage beyond all the bars of the other tie, or an effective anchorage length (based on the force
in the bars) beyond the centre-line of the bars of the other tie. At re-entrant corners or at substantial changes in
construction, care should be taken to ensure that the ties are adequately anchored or otherwise made
effective.’
3L.3 Acceptable limits of damage
For buildings in Class 2B of Building Regulations Approved Document A which do not comply with the requirements
of subsection 3L.2, the structure should be designed such that if any element of structure were to fail or be forcibly
removed, due to misuse or accident, the structural failure consequent on such removal would be localized within an
area not exceeding 70m² or 15% of the area of the storey, whichever is less. Furthermore, the failure would be
localized within the storey in which the element occurs, the storey next above (if any) and the next storey below (if
any).
Where the removal of such an element would result in an extent of damage exceeding the above limit, then the
element should be designed as a ‘key element’ in accordance with 3L.5.
3L.5 Key elements and Bridging elements (where required in buildings of Building Regulations Approved
Document A Class 2B or Class 3)
Where a structural member is deemed to be a ‘key element’, the member and its supports should be capable of resisting a
load of 34kN/m² acting in any direction on the whole surface of that member plus any building components attached to it,
with reactions from the latter limited to the maximum that might reasonably transmitted taking into account the strength of
the attached components and their connections. If a vertical key element relies on a horizontal member for stability, the
relevant horizontal member (or part of the horizontal member) should also be considered as a key element.
Bridging elements should be designed by considering, at each storey in turn, the loss of each vertical loadbearing
element in turn (other than key elements). If catenary action is assumed, allowance should be made for the
horizontal reactions necessary for equilibrium. In this analysis, the length of loadbearing wall considered as a single
element should be either the length between adjacent lateral supports or between a lateral support and a free edge,
subject to a maximum of 2.25 times the storey height. For the purposes of this analysis, a lateral support to a
loadbearing wall is either (a) a stiffened section of the wall (maximum 1m length) capable of resisting a horizontal
force of 1.5Ft kN/m, or (b) a partition (mass at least 100kg/m²) at right angles to the wall, connected with ties capable
of resisting 0.5Ft kN/m, where Ft = 20+4no < 60 (no = number of storeys).
5.1.1, 5.1.2 Delete ‘BS 5328’, insert ‘BS 8500’
5.2.2 Delete ‘BS4466’, insert ‘BS8666’.
6.1Methods of testing concrete
After ‘BS1881’ insert ‘and in BS EN 12350, BS EN 12390 and BS EN 12504’; after ‘BS 812’ insert ‘BS EN 933, BS
EN 1097, BS EN 1367 and BS EN 1744’. Delete last sentence.
Appendix A replace references to ‘BS 882’ with ‘BS EN 12620’.
TECHNICAL NOTES (p. 122)
Delete note on Clause 3C.6.3.
Recommendations for the permissible stress design of reinforced concrete building structures – Amendment No.2, August 2009
The Institution of Structural Engineers Page 6 of 6
. .. . .._,
.... . .. ._-._ . -. . . .. -- -, -
, . ,..
. -..i
.- .
.. . .: .
r
. ..
Foreword 11
1 General 13
1 . 1 scope 13
1.2 Definitions 13
1.3 Symbols 14
2 Materials 17
2. ICements, ground granulated blastfurnace slags and pulverized-fuel ashes 17
2.2 Aggregates 17
2.3 Reinforcement 17
2.4 Admixtures 17
2.4. I General 17
2.4.2 Types 18
2.4.3 Specification 18
2.5 Concrete 18
2.5.1 Designed mix 18
2.5.2 Special prescribed mix 19
2.5.3 Ordinary prescribed mix 19
2.6 Nominal mixes 19
3 Design considerations 20
3A General 20
3A. 1 Basis of design 20
3A. 1.1 Method of design 20
3A.1.2 Momcntsof inertia 20
3A.2 General stability 20
3A.3 Complete structures and analysis of structural frames 21
3A.3.1 General 21
3A.3.2 Frames supporting vertical loads only 21
3A.3.3 Frames supporting vertical and lateral loads 21
3A.3.4 Stress reversal 21
3A.4 Overturningstability 21
3A.5 Loadings 22
3A.6 Permissible stresses i n concrete 22
3A.6.1 Compressive and bond stresses and elastic modulus 22
3A.6.2 Compressive stress 22
3A.6.3 Modular ratio method 22
3A.6.4 Shear stress 23
3A.6.5 Bond stress 24
3A.7 Permissible stresses in reinforcement 24
3A.7.1 General 24
3A.7.2 Tensile stress 24
3A.7.3 Compressive stress 24
3A.7.4 Tensile stress due to shear 24
3A.8 Increases in permissible stresses due solely to wind forces 24
r. I.-- . 7 -
~ ~ ~
r - ”.
- -
3B.9 Slabs: ribbed and hollow-block construction 15
3B.9.1 General 45
3B.9.2 Blocks and forms 45
3B.9.3 Topping 46
3B.9.4 Calculation of resistance moment 46
3B.9.5 Resistance toshear 46
3B.9.6 Thickness of topping 46
3B.9.7 Size and spacingof ribs 46
3B.9.8 Reinforcement in ribs 46
3B.9.9 Supports parallel to ribs 47
3B.10 Resistance toshear 47
3B. 10.1 General 47
3B.10.2 Shear reinforcement 49
3B. 11 Loads near supports of beams: shear enhancement 49
3B. 12 Deep beams 50
3B. 13 Torsional resistance of beams 50
3B.13.1 General 50
3B. 13.2 Calculation of torsional rigidity 50
3B.13.3 Torsional shear stress 51
3B.13.4 Limit toshear stress 52
3B. 13.5 Reinforcement for torsion 52
3B.13.6 Torsion reinforcement 52
3B.13.7 Arrangement of links in T-, L- or
I-sections 53
- . ---_
3D Stairs 64
3D. 1 Distribution of loading on stairs 64
3D.2 Effective span of stairs 64
3E Columns 66
3E. 1 Reinforcement in columns 66
3E. 1.1 Longitudinalreinforcement 66
3E.1.2 Transverse reinforcement 66
3E.2 Permissible loads on columns 67
3E.2.1 Axially loaded columns 67
3E.2.2 Columnssubject to both direct load and bending 67
3E.2.3 Elastic theory 69
3E.2.4 Overturning 69
3E.2.5 Reduction coefficients for columns 70
3E.2.6 Bending moments in columns 71
3K Resistance to fire 80
3K.1 General 80
3K.2 Robustness 80
3K.3 Elementsexposcd to fire 80
3K.4 Aggregates 80
3K.5 Average cover to main bars 82
3K.6 Cover to secondary bars 82
3K.7 Contribution tocover of additional protection 82
3K.8 Floor thickness 82
3K.9 Beam width 82
3K. 10 Beams and ribs 82
3K. 11 Continuity 85
3K. 12 Use of tabular data (Table 25) 85
5 Workmanship 100
5.1 General LOO
5.1.1 Concrete quality 100
5.1.2 Transportation 100
5.1.3 Placing 100
5.1.4 Curing 100
5.1.5 Concreting in cold weather 101
5. I .6 Concreting in hot weather and drying winds 101
5.2 Reinforcement 10 I
5.2.1 Specification 101
5.2.2 Cuttingand bending 10I
5.2.3 Fixing 101
5.2.4 Surface condition 102
5.2.5 Welding 102
5.2.6 Mechanical splices 102
DAVID DORAN
Chairman of Task Group
1.2 Definitions
Bedded bearing A bearing with contact surfaces having an inter-
mediate padding of cementitious material
Bearing length The length of support, supported member or inter-
mediate padding material (whichever is least) mea-
sured along the line of support
Bearing width The overlap of support and supported member
measured at right-angles to the line of support
Braced structure Structure where resistance to lateral forces is pro-
vided by cross-bracing, shear walls or other such
elements
Bundle of bars A group of not more than four bars in contact
Characteristic strength The characteristic cube strength of concrete is
defined in BS 5328
The characteristic strength of reinforcement is
defined in BS 4449
Column head An enlargement of the top of a column supporting
a flat slab so designed and constructed as to act
monolithically with both the column and the flat slab
Core of helically reinforced The portion of the concrete enclosed within the
column centre-line of the helical reinforcement
Drop The portion of a flat slab above and immediately
surrounding the column head and of greater thick-
ness than the remainder of the flat slab panel
1.3 Svmbols
equivalent area of helical reinforcement (volume of helix per unit length I
Ab
of column)
gross cross-sectional area of concrete, excluding any finishing material
gross cross-sectional area of concrete core
area of longitudinal reinforcement
cross-sectional area of bent-up bars
cross-sectional area of steel in compression
cross-sectional area of steel in tension
cross-sectional area of link
distance from nearest support to the section under consideration
distance from face of support to nearest edge of principal load
breadth of a rectangular beam or breadth of flange of a T- or L-beam
effective moment transfer strip from a flat slab to an edge column
breadth of the rib of a T- or L-beam
torsional constant
column width
diameter generally
effective depth to the tensile reinforcement in a beam
depth to the compressive reinforcement in a beam
depth of concrete in compression in a beam
depth to neutral axis
depth of slab forming the flange of a T- or L-beam
modulus of elasticity
2.2 Aggregates
Aggregates should comply with BS 882 for coarse and fine aggregates from natural
sources or with BS 877, BS 1047 or BS 3797 as appropriate for lightweight
aggregates.
2.3 Reinforcement
Reinforcement should be designated by its type and effective diameter. Characteris-
tic or yield strengths are given in BS 4449 and 4483 as 250 N/mm’ for mild steel and
460 N/mm’ for high-tensile steel.
2.4 Admixtures
2.4.1 General
Admixtures may be added to concrete mixes to improve the properties of the
concrete. While improving certain properties, an admixture can significantly affect
others, and it is therefore important to know all the effects of any admixture and to
use the material in strict accordance with the manufacturer’s instructions. Two or
more admixtures may not be compatible, and they should be combined only if tests
or other suitable investigations prove satisfactory. The behaviour of admixtures with
composite or supersulphated cements should be carefully investigated before use.
The suitability and effectiveness of any admixture should be verified by trial mixes
with the cements, aggregates and other materials to be used in the works.
2.4.2 Types
The main types of admixture are:
(i) water reducing, often referred to as ‘plasticizers’ which may be used to
increase workability or, by reducing the water content of the mix, to increase
its strength
(ii) accelerating, .which increase the rate of gain of early strength
(iii) retarding, which slow the setting time and thus extend the workability phase
(iv) air-entraining, which introduce very small air bubbles into the concrete,
improving workability and resistance to frost action
(v) superplasticizing, which have highly efficient water-reducing effects
(vi) waterproofing, which reduce the permeability of concrete to water and
dampness
(vii) pigments, which change the colour of concrete.
2.4.3 Specification
Admixtures should comply with the following British Standards, where applicable:
BS 1014: Pigments for Portland cement and Portland cement products
BS 5015: Concrete admixtures
Part 1 : Accelerating admixtures, retarding admixtures and water reduc-
ing udmixtures
Part 2 : Air entraining admixtures.
2.5 Concrete
Concrete should be designated by a grade number (with a prefix C) for which
appropriate design stresses are given in these recommendations. All concrete
designed and prescribed mixes should be specified in accordance with BS 5328 by
reference to the grade of concrete and type of mix. Guidance on specifications and
forms for specifying different types of concrete are given in BS 5328.
One of three types of mix should be selected:
2.5.1 Designed mix
Designed mixes are intended for general use and arc designated by a grade number
with the suffix D. The recommendations of this document apply to the following
designed mixes containing normal-weight aggregates:
C20D, C25D, C30D, C35D, C40D, C45D, C50D, C55D and C60D.
For lightweight aggregate concrete an additional grade, C15D, may be used.
The supplier may choose from the various types of cement and aggregates listed
in BS 5328 unless the specifier wishes to restrict the choice. The specifier should also
state:
(i) the nominal maximum size of aggregate
(ii) the minimum cement content
(iii) the rate of sampling.
~
3A.3 Complete structures and analysis of structural frames
3A.3.1 General
The analysis of a structure should be carried out to determine a set of internal forces
and bending moments in equilibrium with the design loads applied to the structure.
The method of analysis should be based on as accurate a representation of the
behaviour of the structure as is reasonably in accordance with the recommendations
of section 3A. Alternatively, the methods below may be adopted if appropriate.
3A.5 Loadings
The loadings should be in accordance with BS 6399 and CP 3: Chapter V, as
appropriate. For the purpose of calculating dead loading, the weights of materials
should, unless otherwise agreed, be taken to be as in BS 648: Schedule of weights
of building materials.
For ordinary construction the density of reinforced concrete may be taken as 2400
kg/m3, but where the amount of steel exceeds 2%, some greater weight may be more
appropriate. Where lightweight aggregates are used a smaller appropriate weight
may be taken.
Guidance on the distribution of concentrated loads on slabs and on the distribution
of loads on stairs is given in subsections 3B.7 and 3D.1, respectively.
For modifications of permissible stresse.s due to wind forces see subsection 3A.8.
The derivations of the basic permissible concrete stresses in Table 1 are given in
the clauses 3A.6.2 to 3A.6.5.
Equation 2 may be used for values of fCu between 20 and 40 N/mm'. For normal
weight aggregate concrete,fCushould not be taken as greater than 40 N/mm'. Where
d exceeds 400mm, the term .\1/(400/d) should be taken as unity. Subsection 3B.10
I gives values of p,. for various concrete strengths, effective depths and reinforcement
proportions (see subsection 3H.2 for lightweight aggregate concrete).
3A.7.1 General
The tensile and compressive stresses in steel reinforcement should not exceed those
shown as appropriate for the.type of reinforcement and its characteristic strength, f,.
Stress
land-df
2 Stress diagram
* At a failure of beam or slab, the maximum compressive strain in the concrete has been shown by tests to
be such that a reinforcing bar at the surface of the beam would develop a stress of 700 Nlmm’ with the steel
of the requisite yield or proof stress. With a load factor of 1.8, the limiting stress to he used in design is
thus 385 Nlrnrn’ at the compressive surface. Since tests show that the strain is roughly linear across the
section, the limiting cornpressive stress at the depth d‘ is therefore 385(1 - d’/d.). With an allowance for
displaced concrete this becomes 375(1 - d’ld.).
0.95
0.90
L
0
c
s
U-
! 0.85
0
L
w
0
2
0 80
0.77 '
0 1 2 3 4
'/bd2, Nlmm2
3 Lever-arm factors
* For intermediate values of b,lb and d,ld the value of y can be calculated from the
following formula
y = O . 3 5 -br+ - br
1 (I---)(:) (2-+)
b 2
Where it is necessary for the resistance moment to exceed ypccbd2,compressive
reinforcement should be provided so that
Mr = Ypccbd’ + Asgsc(d - d ’ ) (12)
:.: _ *.' I .
. ..
3A.12.5 Hooks and other anchorages
'
Hooks and othcr anchorages of reinforcement should be of such form, dimensions
and arrangement as will ensure their adequacy without overstressing the concrete
or other anchorage material.
D
-I
I --------A
I t 24D
(b) L-Hook
4 Standard hooks f o r high yield bars
Table 5 Anchorage bond and lap lengths as multiples of bar size for fully stressed bars
23
concrete grade 20 25 30 35 40 45 50
not further apart, centre to centre, than 12 x the diameter of the anchored bar or
300mrn, whichever is less. Links used for this purpose should pass round, or be
hooked over, both the compression and tension reinforcement.
The amount of steel in compression should preferably not exceed 4%, but if it
does, only 4% should be allowed for in the calculation of the resistance moment of
the beam. This percentage should be calculated as follows:
(i) in rectangular beams, on the total cross-sectional area
(ii) in T- and L-beams, on an area equal to the total depth X the width of the rib.
Where compression reinforcement is needed, the area should not be less than
0.2%, except in the case of webs to T- and L-beams, where it should not be less
than 0.4%.
3B.1.5 T-beams
In T-beams, the breadth of the flange assumed as taking compression should not
exceed the least of the following:
(i) Vj of the effective span of the T-beam
(ii) the distance between the centres of the ribs of the T-beams
. (iii) the breadth of the rib plus 12 x the thickness of the slab.
3B.1.6 L-beams
In L-beams, the breadth of the flange assumed as taking compression should not
exceed the least of the following:
(i) '/h of the effective span of the L-beams
(ii) the breadth of the rib plus V'z of the clear distance between ribs
(iii) the breadth of the rib plus 4 x the thickness of the slab.
When a part of a slab is considered as the flange of a T- or L-beam, the
reinforcement in the slab transverse to the beam should cross the full breadth of the
flange. The quantity of such reinforcement should be related to the shear stress in
the slab produced by its acting as the compression member of the T- or L-beam, but
should not be less than 0.15% of the slab area and placed near thc top surface.
3B.2.1 General
Reinforced concrete members should possess adequate stiffness to prevent such
deflection or deformation as might impair the strength or efficiency of the structure
or produce unacceptably large cracks in finishes or in partitions.
Deflections may be calculated and compared with the serviceability requirements
appropriate to each particular case, which may include consideration of such
beneficial factors as secondary support, high-performance materials, reduction in
early deformations, chartacteristics of loading and redundancy. However, in all
normal cases the deflection of beams and slabs should not be excessive if the ratio
Table 6 Basic spadeffective depth ratios for T-beams and ribbed slabs
L
0
L
0 1 2 3 i
5 Modification factors for spanleffective depth ratios M/bd2 ,Nlrnrn2
beams -0.08 WI
slabs +0.063 WI -0.063WI
- ,
.* . r
- r _- . _,. ..
where M , and M y are the bending moments at midspan on strips of unit
width and spans I, and ly, respectively
w is the total load per unit area
I , is the length of the shorter side
1, is the length of the longer side
a, and ayare the coefficients from Table 8.
At least 50% of t h e tension reinforcement provided at midspan should extend to the
supports. The remaining 50% should extend to within 0.1 of the span from the
support.
Table 8 Bending moment coefficients for two-way slabs simply supported
on four sides
1.0 1.1 1.2 1.3 1.4 1.5 1.75 2.0 2.5 3.0
0.062 0.074 0.084 0.093 0.099 0.104 0.113 0.118 0.122 0.124
0.062 0.061 0.059 0.055 0.051 0.046 0.037 0.029 0.020 0.014
the surrounding floor is not impaired by the opening. Due regard should be paid to
the possibility of diagonal cracks developing at the corners of openings.
'Y
k CI
Load included
--
in this shaded area
to be carried
I
B
Load included in this
shaded area to be
carried by beam B
Load width
- V
A
I
V
A
3B.9.1 General
This type of construction consists of a series of reinforced concrete ribs cast in situ
between blocks that remain part of the completed floor or on forms that may be
removed after the concrete has set.
0.7--
-
ul
E 0.6--
L
8 -
c
ul
-n
w
'j, o,s--
.-ul
E -
c
0.4 --
0.3-
0.2--
0 1
9 Permissible shear stress
a, < 0.6d, horizontal links should normally be provided, and special attention
should be paid to the anchorage of the main reinforcement. Fig. 10 shows
possible methods of anchoring the main tension reinforcement in corbels.
(C 1
Outside edge of bearing
to be kept clear of bend
in main reinforcement
(minimum ckarance
D 1 bar diameter) Detailing rules
(1) hy 4. 0 5 h
(2) 04S100Astlbd < 1.3
(3) 0.6S 100(Ast+A~v)lbdS2.0
(4)Other details as per diagrams
l 1 1.5 2 3 5 >5
kr I 0.14 0.20 0.23 0.26 0.29 0.33
(
hlnli,, h,,;,, - A)
3
where T is the torsional moment acting on the member.
(ii) T-, L- or I-sections
T-, L- or I-sections are divided into their component rectangles; these are
chosen in such a way as to maximize h3nlinhnlzlx
in the following expression:
The torsional shear stress, v,, carried by each of these component rectangles
may be calculated by treating them as rectangular sections subjected to a
torsional moment of:
h3niinhm:ix
( t(h3minhm;ix) )
(iii) Hollow sections
Box and other hollow sections in which wall thicknesses exceed one-quarter
of the overall thickness of the member in the direction of measurement may
be treated as solid rectangular sections.
(iv) Other sections
For other sections, specialist literature should be consulted.
25 I 0.21 2.50
30 I 0.23 2.14
40 or above 0.26 3.12
I
52 IStructE RC pcrmissiblc stress rccommcndations
I
where A, is the area of longitudinal reinforcement
A, is the area of two legs of closed links at a section
s is the spacing of the links
xI is the smaller centre-to-centre dimension of a rectangular link
is the permissible reinforcement stress given in clause 3A.7.4
yl is the larger centre-to-centre dimension of a rectangular link
(ii) I n a section with multiple links only the legs lying closest to the outside of
the section should be used as torsion reinforcement.
(iii) The longitudinal spacing of the links, s, should not exceed the least of x,, y,/2
or 200 mm.
(iv) The links should be of the closed type complying with shape code 74 of BS
4466.
(v) Longitudinal torsion reinforcement should be distributed evenly round the
inside perimeter of the links. Thc clear distance between these bars should
not exceed 300 mm, and at least four bars, one in each corner of the links,
should be used. Additional longitudinal reinforcement required at the level
of the tension or compression reinforcement may be provided by using larger
bars than those required for bending alone. The torsion reinforcement should
extend a distance at least equal to the largest dimension of the section beyond
where it theoretically ceases to be required.
(vi) Consideration should be given to the congestion that may arise in providing
the required amount of reinforcement for torsion. This may result in the need
for larger member sizes than would result from other considerations.
Any concrete in
this orea is to
be neglected
in the calculations
l+-r
I I
I I
Perimeter a
i
3C.6.4 Openings
When openings are less than 6 X the effective depth of the slab from the edge of a
column then that part of the perimeter that is enclosed by radial projections from the
centroid of the column to the openings should be considered ineffective as shown in
Fig. 15.
-1
I
1
I
I
(i) the angle of greatest slope of the head should not exceed 45" from the vertical
(ii) the diameter of the column head, D, should be taken as its diameter
measured at a distance of 40 mm below the underside of the slab or the
underside of the drop where provided, as shown in Fig. 11
a
Edge of
slab
b
b
b
4
ba=b+d
I L b
be= b + y
+Column strip
j
3C.ll.l General
Flat slabs may be designed as continuous frames on the assumptions given in clauses
3C.11.2 to 3C.11.7.
Subsections 3B.3 and 3C.3 to 3C.10 are also applicable to this method of design.
wL2
8
(.,?) 2
where w is the total load per unit area on the panel and D is the diameter of the
column heads supporting the slab concerned (see subsection 3C.10). Where the
diameters of the column heads supporting the slab are not equal, D should be
assumed to be the average of the two diameters.
The bending moments for which provision is made should be divided between the
column and the middle strips in the proportion given in Table 14.
negative moments 75 25
positive moments 55 45
3C.12.1 General
This empirical method is described in subsections 3C. 13 to 3C. 17. Subsections 3C.3
to 3C. 10 are also applicable.
3D STAIRS
3D.1 Distribution of loading on stairs
In the case of stairs with open wells, where spans partly crossing at right-angles
occur, the load on areas common to any two such spans may be taken as one-half
in each direction as shown in Fig. 17. Where flights or landings are built into walls
a distance of not less than 100 mm and are designed to span in the direction of the
flight, a 150 mm strip may be deducted from the loaded area and the effective
breadth of the section increased by 75 mm (see Fig. 18).
- UP
I
I
I
E
I
SI W Loading
I
-Down
I
I
I
I
I.
-4 L w 1 2
Loading
L--+--
Max 1M Max 1M
Effective span
19 Effective span for stairs sirpportcd at cwch cwcl by lanrlings spanning purallrl with
the risers
3E COLUMNS
3E.1 Reinforcement in columns
+ 375 (T)
d, - d
or + pbc(compression)
-
+ 375 (T) + plc (compression)
d, d'
f,r =
385 (T)
d' - d,
or - + p5, (tension)
Vbl + fd)
(iv) P, = 0.9pC,bd, + 2
A,
+ *{
(y) h - 0.9d A h h
( v ) M, = 0.9p,,bdn (T- f,, d ) +f,? ( T - d.,>,,7)
where d, is the depth to neutral axis from the compression face
d is depth to the reinforcement farthest from the compression face
d' is depth to the reinforcement nearest the cornpression face
A, is the area of longitudinal reinforcement
f,l is the stress in steel layer farthest from the comprcssion face
f,* is the stress in steel layer nearest the compression face
f, is the permissible direct load
M, is the permissible moment.
Note that in equations (26) and (27) 0.9pc,bd, # pobh and in equation (27) the
first term should not be taken as less than zero.
(S,”
(2,” +
M , and M y are the applied moments and M,, and M y , the corresponding moment
capacities for uniaxial bending. O( may be taken as I where PIP, 0.2 and 2 where
PIP, 2 0.8, with intermediate values obtained by interpolation. PO is the capacity
of the column section in pure compression ( P O = pccAc+ pbcAbc). See clause 3E.2.5
for values of k .
For convenience, equation (28) is shown graphically in Fig. 20.
20
3E
Alternatively, column design may be based on elastic theory with a modular ratio
of 15 and the permissible stresses given in subsections 3A.6, 3A.7 and 3A.8. The
direct load on an eccentrically loaded column should not exceed that permissible for
an axially loaded column.
33.2.4 Overturning
Where appropriate, the factor of safety against overturning should be checked in
accordance with subsection 3A.4.
0 0 1.oo 1 .oo
17 5 0.95 0.95 0.95
34 10 0.89 0.85
52 15 0.81 0.71
69 20 0.69 0.56
86 25 0.56 0.43
104 30 0.45 0.32
121 35 0.34 0.23
138 40 0.26 0.18
172 50 0.13 0.09
207 60 0 0
Internal columns
Moment at foot of upper column
t m
Plan
Section X - X Section V - V
(i) The walls surrounding the pockets should be sufficiently thick and adequately
reinforced to avoid bcing damaged by wedges driven in between the precast
column and the wall to secure the column.
(ii) Dimension t should be a minimum of 75 mm to allow efficient grouting with
a concrete composed of cement, sand and small aggregate.
(iii) The wedge should be bevelled at such an angle as to carry in vertical
compression the load from the column. If this cannot be achieved then the
concrete in the base below the column must be checked for punching shear.
(iv) The whole base should be reinforced as though it was monolithic to accept
the critical bending moments and shears described in clauses 3G.l.l and
3G. 1.3.
60. I 5 0.09 0.22 0.21 0.21 0.20 0.19 0.19 0.18 0.17
0.25 0.10 0.26 0.25 0.25 0.24 0.23 0.22 0.21 0.20
0.50 0.11 0.33 0.32 0.31 0.30 0.29 0.28 0.27 0.25
0.75 0.12 0.38 0.37 0.35 0.34 0.33 0.33 0.31 0.29
1 .oo 0.13 0.42 0.40 0.39 0.38 0.37 0.36 0.34 0.32
1S O 0.14 0.49 0.46 0.45 0.43 0.41 0.41 0.39 0.36
2.00 0.15 0.53 0.51 0.49 0.47 0.46 0.45 0.43 0.40
33.00 0.17 0.61 0.58 0.57 0.54 0.53 0.51 ,0.49 0.45
3H.7 Cover
Cover should be 10 mm greater than that specified in subsection 35.1.
3J.1 Durability
35. I. 1 General
In a rcinforced concrete design one of the most important aims is the production of
a durable structure. To produce it requires the integration of all aspects of design,
materials and construction.
Much of the damage to reinforced concrete structures arises from water
penctration to the reinforcement causing rusting and subsequent cracking and
spalling of the concrete cover, but the effects of other potentially deleterious
substances need also to be considered. To prevent such damage, it is necessary that
the cover specified is adcquatc for the conditions applying, that the concrete is of a
suitable quality and that it is correctly placed to give a dense impermeable whole.
35.1.2 Drainage
Care should bc taken that surfaces exposed to water are laid to adequate falls or
other appropriate measures taken to avoid ponding.
35.1.5 Admixtures
Where admixtures are used their effect on the durability of the concrete and the risk
of corrosion of the reinforcement should be considered. The chloride-ion content of
admixtures must not exceed 2% by mass of the admixture or 0.03% by mass of the
cement.
Mild
(Internal concrete) 25 20 20* 20%
Moderate
(Sheltered from severe rain and against
freezing while saturated with water) - 35 30 25
Severe
(Exposed to driving rain, alternate
wetting and drying, occasional freezing
or severe condensation) - - 40 30
Very severe
(Exposed to seawater spray, de-icing
salts, corrosive fumes and severe freezing
while wet) - - 50 40
10 +40
14 +20
20 0
40 -30
The above requirements have been found to be adequate for many common
structures and circumstances. However where particular conditions might be
relevant or an unusual design life is required, consideration may be given to such
factors as concrete mix design, admixtures, cement replacements and enhancers,
special surface treatment of steel, stainless steel and surface treatment or protection
of the concrete surface. The influence of wear on the concrete surface should also
be considered where relevant.
3K RESISTANCE TO FIRE
3K.1 General
The following text gives simple tabular methods for checking that a structure has ade-
quate resistance to fire for the required pcriods. Other methods of assessment may be
used, such as the direct application of the rcsults of fire-resistancc tests, or calculations
I
based on the reduced strength of steel and concrete at elevated temperatures.
3K.2 Robustness
In the consideration of fire resistance, such factors as robustness, continuity and
availability of alternative paths of support are important.
3K.4 Aggregates
Concretes made with lightweight aggregates have better fire resistance than normal-
weight aggregate concretes, and rarely exhibit spalling. Calcareous (limestone)
F
m
C
c -
-e
t
C
a
a
2
U
=
b-,
L
c w
3
L P 6
E
EL c
x
e,
v.
e,
E
m
.c
c 'c:
-a r,
L
0
e
E
d
0
J
C
e Y
3 3
N
L
e,
5
I
'/2 l h '/2 4h
-
Reinforced concrete
(simply supported)
( a ) Normal-weight thickness 70 90 105 1 I5 135 150
concrete width 75 90 110 125 150 I75
cover 15 25 35 45 55 65
(6) Lightweight concrete thickness 70 85 95 100 1 I5 130
width 60 75 85 100 125 150
cover 15 25 30 35 45 55
Reinforced concrete
(continuous)
(a) Normal-weight thickness 70 90 I05 1 I5 135 150
concrete width 75 80 90 110 125 150
cover 15 20 25 35 45 55
(b) Lightweight concrete thickness 70 85 95 100 115 130 II
3L.1.5 Exceptions
Generally, it is not considered necessary to make special design provisions (other
than the normal attention 10 the matters outlined in clauses 3L.1.2 and 3L.1.3) for
buildings up to four storeys in height including the basement storey (if any).
3L.2 Ties
Floors and roofs of all buildings should be capable of resisting the following tic
forces, assuming no other forces arc acting:
(i) fnternal ties. These should be located at each floor and roof level in two
directions approximately at right-angles. They should be effectively con-
tinuous throughout their length and should be anchored to the peripheral tics
at each end. The total tie force may be spread over the width of the floor or
grouped at uniform intervals in the top or bottom of the floor, or in the beams
or walls (within 0.5m of the top or bottom of the floor slab). Spacing of ties
should in no case be greater than ISL;,, where L a , is the greater distance (in
metres) in the direction of the tie between the centres of columns, frames or
walls supporting any two adjacent floor spans.
In each direction, ties should be capable of resisting a tensile force (in k N
per metre width) equal to the greater of:
(a) +
F, = the lesser of (20 4N) or 60, where N is the number of storeys in
the structure, or
( 6 ) ((dead + imposed floor loading)/7.5) X (L,/5) X ( F J , where L, is as
defined above.
the failure would be localized within the storey in which the element occurs, the
storey next above (if any) and the next storey below (if any).
For the application of this clause ‘public buildings’ may be defined as theatres,
halls or other place of public resort, schools, churches, chapels or other places of
public worship. I t need not apply to restaurants, shops, stores, warehouses or private
houses to which members of the public are admitted.
3L.4 Loads
In considering the ability of the structure to withstand removal of a supporting
member as described in subsection 3L.3, the dead load of the structure above the
level of collapse should be considered, together with one-third of the tabulated
imposed loading. However, loads due to plant, machinery or other equipment
should not be reduced. For buildings such as warehouses, storage buildings, factories
and workshops where the imposed loading is likely fo be of a permanent nature, the
full imposed loading should be considered. Wind loads should be taken as one-third
of the normal design loading.
3L.6 Stresses
For all strength calculations arising from the emergency loading conditions described
in section 3L, the permissible stresses may be taken as 1.75 X the values given in
subsection 3A.7 for steel and subsection 3A.6 for concrete.
4.2 Detailing
4.2.2 Connections
Connections are of vital importance in precast construction and should be carefully
checked to ensure adequate strength, practicability, compatability with other
associated construction and durability.
4.3 Stability
Thc rcconimendations regarding stability and disproportionate collapse given in
scction 3L apply also to precast and composite construction. In particular, the
following points should be noted concerning ties:
(i) All ties should be arranged so as to minimize eccentricity.
(ii) Ties should be effectively continuous and may be provided wholly or partly
within in situ toppings, in situ concrete or precast members.
(iii) A tie may be considered effectively continuous if one of the following
conditions is satisfied:
( a ) A bar in a precast member is lapped with a bar in in situ concrete
bounded on two opposite sides by rough faces of the same precast
mcmber (see Fig. 22)
(h) A bar in a precast member is lapped with a bar in in situ topping or other
concrcte anchored to the precast member by enclosing links (see Fig. 23).
The tensile capacity of the links should not be less than that of the tie
(c) Bars projecting from the ends of precast members are lapped or
interconnected in accordance with clauses 3A. 12.11, 3A.12.12, 3A. 12.13
and 3A. 12.14.
(d) Bars are lapped within it1 situ topping or connection concrete and
projecting links are provided from the precast concrete members to
anchor the in situ concrete (see Fig. 24).
\-Tie
22 Continuity of ties: bars in precast member tapped with bar in in situ concrete
Tie Tie
. . . . . . .:..
. . .... .. . . . . . . I .
4.5.3 Concentrated loads on slabs with reinforced topping
For concentrated loads on slabs with reinforced topping, the provisions of clause
4.5.2 apply in all respects except that, instead of three, the width of four precast
units and joints may be allowed to contribute.
4.6.1 General
In the design of bearings it is important to make allowance for proper overlap of
reinforcement in the supported member and the support, as well as for any loss of
bearing through movement or rotation. A net bearing width is first calculated, and
this is increased to cover these other effects. Fig. 25 is a schematic arrangement of
the allowance to be made for bearing.
\
-L -----
I A'\, Ineffective bearing
Allowance for **Allowance for Net bearing
inaccuracies inaccuracies width
* Nominal bearing width
m
I
Maximum bearing width
*
I
I
I
Bearing
length I Plan
a b
Bearing width
Notes: I Where unusual spalling characteristics are known to apply when particular constituent nliiterials
are heing used. adjustment should he made to the distances recommended.
'7 Chamfers occurring within areas suhject to spalling may he discounted. If steel packs are used for
erection. they should he kept clear of areas suhject to spalling.
4.14.1 Loops
Where continuity of reinforcement is achicved by overlapping loops of reinforce-
ment, the bearing stresses inside the loops should be checked (see subsection 3A. 12).
4.14.2 Sleeves
Sleeves should be provided with cover not less than that specified for normal
I reinforcement. The detailing should be such that the ends of the two connccted bars
can be accurately aligned in the sleeve.
4.14.4 Welding
Welded connections should conform with the appropriate Code or Standard.
4.17.1 General
Where in situ concrete is used in conjunction with precast units to provide a
composite structure, provision for horizontal shear transfer should be made at the
interface.
The design should take into account construction methods, including the effects
of propping on the stresses and dcflection in the structure.
The relative stiffness of the composite materials should be based on the concrete
gross or transformed section, making due allowance for differences of more than
10N/mm' concrete strength in the precast and in situ components.
Where therc is an appreciable difference between the age and quality of concrete
in the precast and in situ components, differential shrinkage effects should be
considered, and in particular, the occurrence of tensile stresses, which may be
significant.
The minimum re'commended thickness of structural topping to precast units is
40 m m with a local minimum of 25 mm. The topping should be well vibrated on to
a surfacc that has been dampened but is without standing water.
5 Workmanship
5.1 Concrete
5.1.2 Transportation
Concrete should be handled from the place of mixing to the place of final deposit
as rapidly as practicable by methods that will prevent the segregation or loss of
ingredients. I t should be deposited as nearly as practicable in its final position to
avoid rehandling.
Ready-mixed concrete should be transported and delivered in accordance with the
requirements of BS 5328.
5.1.3 Placing
(i) Generul. The concrete should be placed before setting has commenced and
should not be subsequently disturbed unless specifically permitted by the
engineer.
(ii) Construction joints. Concreting should be carried out continuously up to
construction joints, the position and arrangement of which should be
approved by the engineer.
When work has to be resumed on a surface that has hardcned it should be
scabbled, swept clcan and wetted, and it may be covercd with a layer of
mortar composed of cement and sand in the same ratio as the cement and
sand in the concrete mixture. This mixture should be freshly mixed and
placed immediately before the placing of the concretc.
Construction joints should be at right-angles to the general direction of the
member and provided with joggles where appropriate.
(iii) Compacting. Concrete should he thoroughly compacted by vibration or other
means, worked around the reinforcement and embedded fixtures, taking care
not to displace them, and i n t o the corners of the formwork to form a solid
void-free mass having the required surface finish.
Over vibration causing segregation should be avoided.
5.1.4 Curing
After placing, appropriate curing procedures should start as soon as the concrete
has lost its free surface water. The method adopted should prevent loss of moisture
from the concrete surface and maintain a satisfactory temperaturc of the concrete
during the curing process.
Faces of concrete should be kept moist by approved means for 4 days after placing
(Portland cement concrete) or six days after placing (concrete containing pfa or
ggbfs). In cold dry weather these periods should be extended to 6 and 10 days,
respectively. I n freezing conditions, special arrangements should be made to protect
the concrete from frost.
.. .
5.2 Reinforcement
I 5.2.1 Specification
Reinforcement should comply with current British Standards.
5.2.3 Fixing
All reinforcement should be placed and maintained in the position shown on the
drawing. Unlcss otherwise specified, the actual concrete cover should be not less
than the specified cover minus 5 mm. Spaeers, chairs or other supports should be
used to maintain the reinforcement in its correct position. Spacers should be of such
materials or designs as will be durable, not lead to corrosion of the reinforcement
or cause spalling of the concrete cover. Spacer blocks made from cement, sand and
small aggregatc should match the mix proportions of the surrounding concrete as
far as is practicable.
5.2.5 Welding
Welding on site should be avoided if possible, but where suitable safeguards and
techniques are employed, and provided that the types of steel have the required
welding properties, it may be undertaken. All welding should be carried out in
accordance with the relevant British Standards and the recommendations of the
reinforcement manufacturers, and only with the engineer’s prior approval.
5.3 Formwork
5.3.5 Tolerances
Tolerances should be in accordance with BS 5606, unless otherwise specified.
100
Soffit formwork to slabs 4 days 6 days -days
f+lO
Soffit formwork to beams 250
and 10 days 15 days -days
t + 10
Props to slabs
360
Props to beams 14 days 21 days -days
t+ 10
6.3 Inspection
Immediately after stripping the formwork the concrete should be completely
inspected. Any defects should be made good as soon as practicable.
6.4.1
Load testing of completed structures or components may be required by the
specification or may be demanded if there is reasonable doubt a s to the adequacy
of the strength of the structure or component. Such testing should not generally be
carried o u t until the concrete may reasonably be expected to have obtained its design
strength, and the objective should be to obtain sufficient information to enable an
assessment of the adequacy of the structure to be made without affecting its long-
term strength or durability.
6.4.2
During testing, struts or other supports should be provided sufficient to take the
whole load in the event of collapse. Such supports should be designed so as not to
inhibit the deflection of the structure or place undue constraints on the recording or
reading of the test results.
6.4.3
The test load should in the first application be equal to and in latcr applications
equal to 1% X the spccified imposed load used for the design, making due allowance
for any finishes etc. that may not be in position at the time of test. However the
total test load plus the dead load in place should not be less than 1 % X the total
combined dead and imposed load used in the design.
Test loads should be applied and removed incrementally, while observing all
proper safety precautions. The test loading should be applied at least twice, with a
minimum of 1 h between tests, and allowing 5 min after a load increment is applied
before recording deformation measurements. A third application of load should be
made that is left in position for 24 h.
., -. . - . . . .. ~ . e
7.2 Protection
Protection of a concrcte surfacc is somctimcs ncccssary particularly whcrc aggrcssivc
chemicals are in contact with i t . Many protcctivc coatings arc available, and cxpcrt
advice should bc sought from the nianufacturcr to dctcrminc thc corrcct coating for
thc conditions which apply.
Any coating used should be durablc and ablc to adjust itsclf to clastic and thcrmnl
movement of thc structures and should bc rnaintaincd in good condition by rcncwcd
applications during the lifc of thc building. Any concrctc paint iiscd should bc
suitable for the alkaline charactcr of concrctc.
7.3 Maintenance
The effect of unforcseen happcnings on a striicturc can bc minimizcd if thc problem
is discovcrcd at an early stage. Periodic inspections should therefore bc carried out
to detect early signs of cracking or spalling of the concrctc or dctcrioration of the
surface. Remcdial action should be taken immcdiatcly damagc is discovered.
7.4 Repair
The repair of reinforced concrete structurcs is a specialist mattcr end rcquircs a high
level of skill and cxpericncc in determining thc cause of thc problem and the
specification of the repair tcchniqucs to be adopted.
The most common causc of damage to concrete structures is corrosion of the
reinforcement causing staining of the surface or spalling or loosening of the concrete
cover. I n such cases the whole of thc loose concrcte should be cut away back to
sound concrete, the reinforcement complctcly exposed and thoroughly cleaned to
remove rust or replaced if ncccssary and frcsh concrctc or mortar placed. The prccisc
method adopted will depend o n the location and thc cxtcnt of thc repair required,
and information should be sought from available technical literature.*
Repairing concrete structures i s a skilled job, and unless the work i s done correctly
and effectively by contractors experienced in the field furthcr repair work may
become necessary i n a short time.
* See Allen. R. T. L.: The rcpuir of concww .witctiircs, 4th ed.. C & C A . Wexham Springs 19x5.
A.1.3 Workability
Thc workability should bc controllcd by dircct mcasurcmcnt of watcr content. making
allowancc for any watcr in thc finc and coarsc aggrcgatcs. Thc slump tcst or thc compacting
factor tcst dcscribcd in BS 1881: Meih0d.y ofiesiing C ~ ~ C I ’ C I Cmay
. bc uscd as a guidc. The lattcr
tcst is primarily dcsigncd for laboratory conditions and is particularly uscful for concrctc mixcs
of vcry low workability.
Table A1 Proportions and strength requirements for nominal concrete mixes with Portland
cement or Portland-blastfurnace cement and with aggregates complying with BS 882
(1) (2) (3) (4)
Cubic metres Cubc strcngth Altcrnativc cubc
aggrcgatc per within 28 days strcngth within
Mix 50 k g of ccmcnt aftcr mixing 7 days aftcr mixing
proportions Nlmm’ Nlmm?
Prcliminary Works Prcliminary Works
Finc Coarsc tCSt tCSt tcst tcst
so that for high-tensile steel and 30Nlmm’ concrete (P,~= 215, pur = 8.25). the required
reinforcement may be read off directly. Reinforcement for other values of pcc and psc may be
determined pro rata.
0.70
0.65
075 080 0.85 090 095
dlh
9 2 0
0
, .
- -. . . . I ....
II
L
T
i
7
4
/
7
4
/
//A
I16 IStructE RC pcrmissiblc strcss rccommcndations
. .. , '
.. .
. . . -- .~_.., - .
.-
. :... . . -. ,. '.,.
. ,
. ... ..
cf
0
rn
0
i
IStructE RC pcrmissiblc strcss rccommcndations 119
. \. .
I2
120 IStructE RC permissible stress recommendations
..- ._ --.
40 kN
Check cohrrm slrufi
Effective length I = (say) 0.85L = 5 . l m I/b = 17
Maximum moment at %L from end = 80 - 30 = 50 kNm
Table 17 gives k = 0.724. Design section for
p = 450/0.724 = 622 kN M = 50/0.724 = 69.1 kNm
p = 622 X 10’ = 0.837 = 69.1 X 106 = 0.31
pobh 8.25 x 300’ p&i’ 8.25 x 300’
d = O.8h : r = 3.4%
= o.85/l : = 3,0yo d = 0.808L : r = 3.3% = 2970mm’
use 4T32 = 3220mm’
Technical notes
These notes do not form part of the Recommendations for the pert~zissiblestress design of
reinforced concrete bidding structures. The notes are meant to show where the Recorntnenda-
tions differ technically from the requirements of BS 8110 (other than those due to the
permissible stress format) and to explain the differences.
General
Overall safety factors are generally conservative or similar to BS 8110. Principal values are as
follows, with BS 8110 average values (Y = 1.5) in parentheses:
steel tension, compression - 1.8 (1.72):
concrete compression - 2.4 (2.25):
concrete shear - 1.98 (1.88): bond - 2.08 (2.1).