AVIDA TOWER MAKATI WEST CONDO

(Tower 1 & 2)

Preventive Maintenance of electrical equipments


2018

Test Results
Thermal Scan Test Results

I. Tower 1 Panels include;

a. LVSG1
b. MTS/ATS
c. LVSG2
d. ELVSG1
Remarks:

1. LVSG1, LVSG2, ELVSG1, ATS/MTS at Tower 1 Panels have successfully passed


the thermal scan test conducted last May 8 of 2018 considering that there
were no hot spot found within the breaker and the bus bar section.

2. The Temperature scanned resulted between minimum of 35.3 degree Celsius


to 38.4 degree Celsius maximum which is still allowable temperature for
equipment.
Thermal Scan Test Results

II. Tower 2 Panels include;

a. LVSG3
b. MTS
c. LVSG4
d. ELVSG3
Remarks:
1. LVSG3, LVSG3, ELVSG3, MTS at Tower 2 Panels have successfully passed the
thermal scan test conducted last May 8 of 2018 considering that there were
no hot spot found within the breaker and the bus bar section.

2. The Temperature scanned resulted between minimum of 35.4 degree Celsius


to 38.2 degree Celsius maximum which is still allowable temperature for
equipment.

Prepared by:

Engr. Jeffrey S. Rogero


COSINE SERVICE DEPT.HEAD

Noted by:

Engr. Rodrigo M. Sigua


COSINE SPECIAL PROJECT HEAD