You are on page 1of 6

TRAFO :

Rumus Menghitung Arus Gangguan 3 Phase :I


3phase
I 2 Phase E phase - phase
Note : Z1 eq = Z2 eq Z1 Eq + Z2 Eq

I 1 Phase E pha - netral


Z1equi + Z2 Equiva + Zo Equiv
MVA HS di BUS 150 kV 350 MVA

Kapasitas 20 MVA
Tegangan Primer 150 kV
Tegangan Skunder 20 kV
Connection YY∆
Kapasitas ∆ 1/3 dari Kapsitas 6.6 MVA
Impedasi HS 10 %
Penghantar A3C 150 mm²
Z1 = Z2 0.22 + j
Zo 0.36 + j

Xt Impedansi Trafo X1=x2 2 Ω


Impedansi Xo Trafo 6.06 Ω

Panjang L1 30 KM
Panjang L2 20 KM

Z1 Saluran 1 RL 1 6.6 Ω XL 1
Zo Saluran 1 10.8 Ω

Z1 Saluran 2 RL 2 4.4 Ω XL2


Zo Saluran 2 7.2 Ω

Xs (Impedasi Sumber) 64.3 Ω Disisi 150 kV


Xs (Impedasi Sumber) Xs1 1.14 Ω Disisi 20 kV
Pentanahan Sistem Rn 40 Ω

Menghitung arus gangguan

I 3phase 100 % 20 kV/√3


Z1 equv

E phase - netral
jXs1 + jXt1 + RL1 + jXL1 + RL2 + jXL2

E phase
(RL1 + RL2) + j (Xs1 + Xt1 + XL1 + XL2)

Ephase 11547 VOLT


√ (RL1+RL2)² + (Xs1 + Xt1 + XL1 + XL2)² 22.5 OHM
E phase - phase
Z1 Eq + Z2 Eq

20000 V 20000
2X(√ (RL1+RL2)² + (Xs1 + Xt1 + XL1 + XL2)²) 45.03

20000 444.6848
45.0262961717

444.18

3. 20kV√3
2(√ (RL1+RL2)² + (Xs1 + Xt1 + XL1 + XL2)²) + ( Xot + RoL1 + XoL1 + RoL2) + 3 Rn

34641 131.77155597
262.89
RUMUS Xs Sumber kV²/MVA sisi 150 kV
RUMUS Xs Sumber (kV²*Xs)/150^²

Penyulang : Krakatau
Penghantar : A3C 150 mm²

0.33 Ω/km
1.62 Ω/km

9.9 Ω
48.6 Ω

6.6 Ω
32.4 Ω

Catatan :
Penyelesaian a + jb = √a² + b²

513
513

513 Amper