Professional Documents
Culture Documents
Hi-Pot Test For Cable 1
Hi-Pot Test For Cable 1
3. General Inspection : OK
4. Continuity Checks : OK
Measured Values
Reference Applied Voltage (V) Duration (min)
(TΩ)
R-E 5000 1 >1
Y-E 5000 1 >1
B-E 5000 1 >1
R-Y 5000 1 >1
Y-B 5000 1 >1
B-R 5000 1 >1
6. Hi-Pot Test:
Applied Voltage
Reference Duration(min) Measured Leakage Current (mA)
(KV)
R-(Y+B+E) 57.0 3 0.9
Y-(R+B+E) 57.0 3 0.9
B-(R+Y+E) 57.0 3 0.9
Measured Values
Reference Applied Voltage (V) Duration (min)
(TΩ)
R-E 5000 1 3.98
Y-E 5000 1 2.21
B-E 5000 1 2.38
R-Y 5000 1 3.21
Y-B 5000 1 3.88
B-R 5000 1 4.72