2.

Name Plate Details:

Size 185 Sq.mm


Run 1 x 3C
Rating 33 KV

3. General Inspection : OK

4. Continuity Checks : OK

5. Insulation Resistance Test (Before Hi-Pot):

Measured Values
Reference Applied Voltage (V) Duration (min)
(TΩ)
R-E 5000 1 >1
Y-E 5000 1 >1
B-E 5000 1 >1
R-Y 5000 1 >1
Y-B 5000 1 >1
B-R 5000 1 >1

6. Hi-Pot Test:

Applied Voltage
Reference Duration(min) Measured Leakage Current (mA)
(KV)
R-(Y+B+E) 57.0 3 0.9
Y-(R+B+E) 57.0 3 0.9
B-(R+Y+E) 57.0 3 0.9

7. Insulation Resistance Test (After Hi-Pot):

Measured Values
Reference Applied Voltage (V) Duration (min)
(TΩ)
R-E 5000 1 3.98
Y-E 5000 1 2.21
B-E 5000 1 2.38
R-Y 5000 1 3.21
Y-B 5000 1 3.88
B-R 5000 1 4.72

8. Remarks: Test results are found Satisfactory.