You are on page 1of 1

HVAC System Pipe

No Item Material Type of testing


Refrigerant Pipe (ACCU) Cooper Gas type: Nitrogen
Reference Doc: EURO5-EPC-EXE-HEC-00- Pressure : 1.5 x Operating Pressure
1 HVA-DES-0002 Hold for 24 Hours
Section : 5.11 PTS 12.24.03 (Section 4.2.2.2)

Chiller water pipe Carbon Steel Gas type: Water


Reference Doc: EURO5-EPC-EXE-HEC-00- Pressure : 1.5 x Operating Pressure
2 HVA-DES-0002 Hold for 24 Hours
Section : 5.11 PTS 12.24.03 (Section 4.2.2.2)

Drain Pipe (AHU) UPVC or PVC As Specified by OWNER


Reference Doc: EURO5-EPC-EXE-HEC-00- PTS 12.24.03 (Section 4.2.2.2)
3 HVA-DES-0002
Section : 5.11

Sanitary water pipe PVC As Specified by OWNER


Reference Doc: EURO5-EPC-EXE-HEC-00- PTS 12.24.03 (Section 4.2.2.2)
4 CVS-SPN-0006
Section : 11.2