Liang Chi
Liang Chi series LC cooling towers have been designed Thermal Performance certified
for cross flow type with Low Noise Motor and Fan. by the Cooling Tower Institute
The compact design is suitable for Equipment Cooling, se, orescence
Industrial Process Cooling and Air Conditioning. po CTI STD-201
LANG CHI INDUSTRY. CO.,LTD.Characteristics
Design of Integrated System
Liang chi low noise cross flow rectangular type of series LC cooling towers have been designed
according to the international standards. The light weight structure and standardized components of
LC tower feature easy transport, lifting and site installation.
Low Noise & Easy Maintenance
Series LC cooling tower use high tension V-belt recucers, which are corresponding to the low noise
axial flow fans featuring silent operation and easy maintenance.
Light Weight, Less Space and Multi-Cell Installation
Comparing with other types of cooling tower, LC features lighter operational weight and less
installation space. Also the combinative multi-cell structure is suitable for large cooling requirement
and future expansion.
Unique Distribution System & Efficient Heat Exchange
Gravitational distribution systems features low pressure and slow water flow which can prolong
cooling duration and ensure cooling efficiency.
Efficient Performance
Unique dasign of vacuum-formed & round-chorded filling with ripple surface facilitate aven spread &
long duration of water drop and free of deposits & scales.
Low Electrical Power Consumption
The high efficient hydrodynamic "venturi-tube" fan stack with high efficient low-resistance filing
facilitates good ventilation and reduction of fan motor power to save electrical power.
Durableness & Low Maintenance Cost
LC tower components are made of weather-proof and anti-corrosive materials. Casing is in
anti-ultraviolet P.V.C. which features sound -proof and non-decayed merits with fine steam-lined
outlook. Fan stack, basin and access-door are made by F.R.P. Filling & inlet louvers are by P.V.C
Supporting rack is by light weight steel. All the steel parts are hot-dip-galvanized so as to enable the
durableness and low cost.
Easy Piping Work & Low Installation Cost
All the piping connections ate gathered on basin except inlet pipe connection which lies over the
distribution basin for easy piping.
Structure and Standard Materials
Mor
Fen Sk (FRP) ———— Fan Glad (Hol Dp Ga St)
Leder (Hot Dip al Stel) eT
an
Hot tr It Por (FRP)
Dishnuon Basin (FP)
Casing (PVC)
‘Access Door (FRP)
Basin Fae (Hot Dp Gal Sted)
Loves (PVC) - Cot ier Out fe (Dp Ga Si)
Filing (PVC) - - —— grag 4B Waste Bis
Cekvatr Bash (FRP) / . Ovefow Pice
Sump (FRP) ——_—_— Dan PrpeSeri
EXAMPLE :
Design condition :
Circulating water flow rate : 2450GPM
Hot water temperature : 100°F
Cold water temperature : 90°F
Wet-bulb temperature : 81"
Range :
Hot Water Temp, - Cold Water Temp.
R= 100-90 = 10°F
1.Trace up the hot water temperature
‘of 100°F vertically to find the |
intersecting point @) with the 81°F
entering wet-bulb temperature curve.
2.Shift the point to the right to find
the intersecting point @ with the 10°F
range curve.
3.Then trace up again from the point
to find the intersecting point
withthe 2450 GPM circulating water
flow rate.
4.1f point @ falls on the curve of a
model, select this model. If point 3)
falls between two curves, select the
larger model.
5.Because point @ falls between the
curves of 800 & 900, the selection
is model 900.
114
110
Hot water temperature °F
106 102 98 94 90 86
LC Cooling Towers Selection Chart
4000
3500
3000
2500
2000
1500
1000
900
800
700
600
500
400
350
300
250
200
150
Range °F