DRAWING NO.

FP-1
Sprinkler Design Data
Project Name: System:

Project Street Address: Sys. Sq. Ft.:


Suite: Floor#: Ceiling Height:

Designed By: Phone: Total Bldg. Hgt.:

Occupancy: Hazard:

DATE:
Design Summary
System # System # System # System # System #
Design Method

Design Area #

5-1-06
LL
Location

Type of System

W Warren
REVISIONS:
Hazard Class

Criteria From

Design Area

Sprinkler Spacing

Density
K-factor

Hose Allowance

# Design Sprinklers

Special Application Spk.

Requirement @

SPRINKLER DESIGN DATA


G.P.M. Req'd
P.S.I. Req'd
Safety Factor @

Safety Factor (PSI)

Dry Sys. Volume (gal)

Water Supply Information


Tested by Date/Time Pressure Hydrant

Hydrant Elevation Flow Hydrant # 1 Flow Hydrant #2

Static (PSI) Residiual (PSI) Flow (gpm)

DESCRIPTION:
Copy of Water Test Data Included with Calculation is required

Fire Pump Data


Rated G.P.M. Rated Pressure Horsepower

Diesel/Electric Churn Pressure Style of pump

Combined Discharge 150% Flow (suction) 150% Flow (gpm)


CITY OF RALEIGH FIRE DEPARTMENT

Certified pump curve required 310 WEST MARTIN ST. RALEIGH, NC 27602

If Storage is Greater than 12 Feet Complete Commodity Storage Design Information


FIRE PROTECTION DIVISION

Comodity Description Storage Type (Rack,Bin,Pile)


Comodity Class Storage Height Clearance

Stable/Unstable Open/Close Wet/Dry


Array System
Curve
Figure Density
# # Height Clear Array Dry Design Minimum Final

Factor Factor Factor Penalty Design Design


Area

Initial

Secon

-dary
Is system compliant with Chapter 23 (FPC) Is storage area layout, rack, and pile plan included?
ELEVATOR

4'

4'

4'
MACHINE
4'

STORAGE
ROOM 002

9'

9'
10' 5'-8"
2'-3
4'
001

3'8

2'

9'-2"
5'-10"

5'
12'-0"

9'-10"
MECHANICAL 004 OFFICE
003

9'-2"
10'-0"
6'-2" 13' 6'-2"
5'

4'
SPRINKLER REFLECTIVE CEILING PLAN
SCALE: NTS

CITY OF RALEIGH FIRE DEPARTMENT DESCRIPTION: REVISIONS: DATE: DRAWING NO.

FIRE PROTECTION DIVISION


310 WEST MARTIN ST. RALEIGH, NC 27602
SPRINKLER REFLECTIVE CEILING 5-1-06 FP-2
W Warren LL
SPRINKLER UNDER STAIR STAIRS UP

1"
ELEVATOR
1" 1" 1" 1" 1" 1" CONCRETE BEAMS

MACHINE (TYPICAL)
ROOM 1" 1"

400
6 3
1" 1" 1" 1" 1"

2"
2" 103
4" 4" 4"
SPRINKLER SUPPLY UP
TO SECOND FLOOR
6" DI
4"
2" 2"
1" 1" 2
400 5
1" 1"

102
MECHANICAL OFFICE
399 1"

1" 1" 1"


4 1 DESIGN AREA 1B
1" 1"

101

SPRINKLER PIPING PLAN


SCALE: NTS

CITY OF RALEIGH FIRE DEPARTMENT DESCRIPTION: REVISIONS: DATE: DRAWING NO.

FIRE PROTECTION DIVISION


310 WEST MARTIN ST. RALEIGH, NC 27602
SPRINKLER PIPING PLAN 5-1-06 FP-3
W Warren LL
SHOW OVERALL DIMENSIONS
FOR DEVICES AND CLEARANCE.

___' ___"

SPRINKLER VALVE TRIM AREA


___' ___"

RISER PIPE

CLEAR
12"
CLEAR
18"
12"
CLEAR

12" 12" 12"

CLEAR CLEAR CLEAR


CLEAR
18"

36"
36"
36" 36"

NOTE:
APPROACH CLEARANCE
WHEN RISER IS LOCATED IN A

OPEN SPACE (ie. WAREHOUSE, ETC.)


MECHANICAL PROTECTION IS

REQUIRED.(BOLLARDS, ETC.)

RISER CLEARANCE
NOT TO SCALE

CITY OF RALEIGH FIRE DEPARTMENT DESCRIPTION: REVISIONS: DATE: DRAWING NO.

FIRE PROTECTION DIVISION


310 WEST MARTIN ST. RALEIGH, NC 27602
RISER CLEARANCE DETAIL 5-1-06 FP-5
W Warren LL
RESIDUAL PRESSURE * RESIDUAL PRESSURE *
CHURN PRESSURE ** CHURN PRESSURE **
500 74' ELEV.
gpm HOSE STREAM 250
250 GPM gpm HOSE STREAM
* *
500 GPM
** **
ROOF 62' ELEV.

psi gpm SPKLR DEMAND

* 80.4 *
** **
5TH FLOOR 50' ELEV.

SPKLR DEMAND psi gpm

* *
** **
4TH FLOOR 38' ELEV.

psi gpm SPKLR DEMAND

* *
** **
3RD FLOOR 26' ELEV.

SPKLR DEMAND psi gpm

* *
** **
2ND FLOOR 14' ELEV.

psi gpm SPKLR DEMAND *

**
RPZ
*
**
GROUND FLOOR 2' ELEV.

psi gpm SPKLR DEMAND 750 GPM

* *
**
BASEMENT -8' ELEV. **

VALVE WFS FIRE PUMP


85 PSI @ 750 GPM
GAGE FLOW TEST
RELIEF
S = 60
R = 40
TEST & DRAIN DEVICE
F = 750
FLOOR CONTROL ASSEMBLY DETAIL

CITY OF RALEIGH FIRE DEPARTMENT DESCRIPTION: REVISIONS: DATE: DRAWING NO.

FIRE PROTECTION DIVISION


310 WEST MARTIN ST. RALEIGH, NC 27602
STANDPIPE PRESSURE SUMMARY 5-1-06 FP-6
W Warren LL
IN
MA NUMBER OF VALVES
T Y TO SYSTEM
CI PER NFPA 20.

RPZ IN HOT BOX. TEST


BACKFLOW PREVENTER HEADER
WITH BYPASS METER.
(REQUIRED)

RODDING & BLOCKING


CK. VALVE
ALL-U/G & STUP-UPS W/ BALLDRIP
)
ED
PER NFPA 13 & PUBLIC
UTILITIES HANDBOOK UIR METER
EQ
(R CONTROL FIRE DEPT.
SS VALVE
CONNECTION W/
PROTECT PIPING
PA ER
THRU WALLS BY M
ET 1
RALEIGH THRDS.

AND FLOORS. W TE
O O
FL N

4 I EF
TE EL E
O R LV
N VA
TE
5 O
N
TE 2
FIRE
O
N PUMP
Ductile Iorn underground
D/I or Galvanized pipe CONTROLLER

to fire pump flange JOCKEY


THROTTLING
and bypass check valve PUMP
CONTROL
FIRE
VALVE
PUMP

Presure Relief
Valve

Pressure
JOCKEY
SUPPLY Gauge
TEST GAUGE ADJACENT PUMP NOTES:
TEST
TO TEST CONNECTION CONTROLLER
VALVE HYDROSTATIC TEST ALL PIPING PER NFPA 13.
(BUT NOT OFF 2" PIPE)
PUMP TEST HEADER IS REQUIRED.
FLOW METER IS OPTIONAL.
MINIMUM 2" PIPE NOTES 1,2,4&5 SEE NFPA
TO OUTSIDE BLDG. 20, A 2-14

Control Valve

Check Valve FIRE PUMP ISOMETRIC


N.T.S.

CITY OF RALEIGH FIRE DEPARTMENT DESCRIPTION: REVISIONS: DATE: DRAWING NO.

FIRE PROTECTION DIVISION


310 WEST MARTIN ST. RALEIGH, NC 27602
FIRE PUMP ISOMETRIC 5-1-06 FP-7
W Warren LL
36" 208/240VOLTS
42" 440 VOLTS

CONTRL
CLEARANCE

24"
24" 24"

FDC

24" MIN.
CLEARANCE

24"

MINIMUN
JOCKEY
PUMP CLEARANCE
TOP VIEW

FULL
SERVICE
CONTRLR

FIRE
PUMP
CONTRL

JOCKEY
FIRE PUMP
PUMP

SIDE VIEW END VIEW

CITY OF RALEIGH FIRE DEPARTMENT DESCRIPTION: REVISIONS: DATE: DRAWING NO.

FIRE PROTECTION DIVISION


310 WEST MARTIN ST. RALEIGH, NC 27602
FIRE PUMP ELEVATIONS 5-1-06 FP-8
W Warren LL
SPRINKLER LEGEND

EXISTING SPRINKLER 1/2" / 155 / SSP / 5.6K / TOTAL 250 /

R EXISTING SPRINKLER TO BE REMOVED & PLUGGED / / / / TOTAL 10 /

EXISTING SPRINKLER TO BE RELOCATED / / / / TOTAL 30 /

NEW CHROME PENDENT SPRINKLER 1/2" / 155 / SSP / 5.6K / TOTAL 16 /


VIKING FAST-RESPONSE MODEL M WITH
MODEL F1 CHROME ESCUTCHEON

NEW BRASS UPRIGHT SPRINKLER 3/4"/ 165 / SSU / 8.0K / TOTAL 20 /


CENTRAL MODEL A

NEW CHROME HORIZONTAL SIDEWALL SPRINKLER 1/2" / 165 / QR / 5.5K / TOTAL 6 /

New Extended Coverage Pendent Semi Recessed 3/4" / 155 / SSP /11.4K/ TOTAL 28 /

New Chrome Pendent Sprinkler Quick Response 1/2" / 155 / QR / 5.5K / TOTAL 10 /
QR

ES New ESFR Upright Sprinkler 1" / 155 /ESFR / 25.2K/ TOTAL 30 /

EXISTING PIPE

EXISTING PIPE TO BE REMOVED

NEW PIPE

2 2 2 2-HOUR RATED FIRE WALL

1 1 1 1-HOUR RATED FIRE WALL

CITY OF RALEIGH FIRE DEPARTMENT DESCRIPTION: REVISIONS: DATE: DRAWING NO.

FIRE PROTECTION DIVISION


310 WEST MARTIN ST. RALEIGH, NC 27602
SPRINKLER LEGEND TYPICAL 5-1-06 FP-9
W Warren LL
EQUIPMENT SCHEDULE

A ELECTRIC FIRE PUMP 30HP 480V 3PH - 1000 GPM AT 40 PSI

B FIRE PUMP CONTROLLER WITH LOW FUEL ALARM


AND LOW ROOM TEMPERATURE ALARM

C JOCKEY PUMP 3/4HP 480V 3PH - 2 GPM AT 40 PSI

D JOCKEY PUMP CONTROLLER

E FLOW METER UL/FM APPROVED

F CONCENTRIC REDUCER

G ECCENTRIC INCREASER

H CASING RELIEF VALVE

I ORIFICE UNION

"A TYPICAL EQUIPMENT SCHEDULE"

CITY OF RALEIGH FIRE DEPARTMENT DESCRIPTION: REVISIONS: DATE: DRAWING NO.

FIRE PROTECTION DIVISION


310 WEST MARTIN ST. RALEIGH, NC 27602
EQUIPMENT SCHEDULE 5-1-06 FP-10
W Warren LL
System No. F-C-1009 SystemNo. F-C-1009
F Rating.1 and2 Hr(Sealtern1) F Rating .1 and 2 Hr (See Item 1)
T Rating.1 Hrand2 Hr(SeeItem1) T Rating .1 Hr and 2 Hr (See Item 1)
.
L RatingAt Ambient LessThan1 CFMlsqIt L Rating AtAmblent. Less Than 1 CFMlsq It
L RatingAt 400F .4 CFMlsqIt .
L RatingAt400F 4 CFM/sqIt

O. Sleel Plale- WhenlumberplalOOeredlaoontlnuous,nom 1.1/210..wideNo. 20 gauge(or heavlar)g... staalplatasshal beInstalledto


oonnecteachdisoontinuouslumbarplale tnI to provfdea formfor th. fillmal.dal. SleeIplatessizedto I~ 2 In.onIoea::hdsoontinuous
lumberpial. andsecuredto lumberplal.s withstealr;aewsor nails.
E. GypsumBoard' . Thlokness,typ.. numberof layars andfast.""", shallbe es speoIfledIn 1ncIvfciJai WallandPIItitIonDesIgn
2. ChaseWall. The throughpene~"'1 ~Iam3) shallbe rouled througha 1 or 2 hr flre-ratedslngl.. doubl. or staggered 'MJOdstudIgypsum board
chasawall havinga fire ratingoonsIst.nlwith thatof th. floor-cellingassembly.D.pth of chasawall tobe mln 110.grnatarihanthedlametarIi
the throughpenetrant.The chasewall shallbeoons~cted of thematOllaisandIn the mannerspecI1Ied u:m SBIIasWalland
In thei1<fvIduaI
PartitionO.aIgn.ln the UL Flra R.slstoooeDirectorytnI shallindude thefollowingocnstJuctIon faaturee
A. Studs. Nom2 by 410...2 by610..ordoubl. nom2 by 410..lumbarstuds.Nom2 by 4 In. studslIS allowedfor th~~..,1s ~Iarn3)
nolexoeedlngnom210..dam.
3. ThroughPene~anls- One melalilcpipe,oonduIlor tubingto be Inslalledwithinthe firaslop syslam.Pipe.concI.ilortubingto berigidlySt.I'IJOI\ed
on both sidesof floor assambly.Th. annul...specewithin th. flmstopsystemshallbe mln 0 In. (pointoonIect)tomax 1 n.. Thefrjlowlngtypes
and sizesof metallicpipesor oorodullo maybeused:
A. SleeIPipe. Nom410..dlam(or emslar) ScheOOIe 10(or heavIar)atealpipe.
B. Iron Pipe - Nom410..dlam(or smallar)oesIor 00ci1eIronpipe.
C. Conduit- Nom410..dlam(or amaller)steelelectrioalmelairlctWlngorstealoondlil.
O. CopparTubing- Nom41n.dlam (or smaller)TypeL (orheavlar)ooppartubing.
E. CopparPipe - Nom410..diem(or smallar)ReglI... (orheavIar)oopparpipe.
4. Fill, Void or Cavil}'Matellal'. Sealant- Mln 3/4In. thlct<noss
offill malellal appliedwithinthe ardus, IkJohwlththetopQlfeoe Ii theflooror the
sole pI.I.. A genarousbeadof fil matarlalalso<wiled within theMOOlueof thelop pial.. flushwithbottomlIIIfeoeIi "-' toppima.
HIL TI CONSTRUCTION CHEMICALS, OIV OF HIL TIINC -CP601S, CP606 or F8-0ne SaalIri. (Note: L Ratings apply or;y when FS-ONE

SEcnooA-A S..I..,lIo used.)


'S.aring the ULClassificationMilk

1. FIoor-C.lllng Assembly.Th.1 or 2 hr flre-<aledsolid or trussedlumberJoistfloor-ceilingassamblylMl be ocnstnJctedof thematOllalstnlln


the mannerspecI1IedIn the individualL500Saltas Floor-CallingDesignsIn theUL Flra R.slst Directory.The FRatingIi theflrestopsystam
Is equal to theratingof thefloor-ceilingtnI wall _I... The _aI oonstructlonfeaturesof the1Ioor-celling
~ lIS smmartzad
below:
A. FlooringSystam- Lumberor plywood"""floor with flnlshfloorof lumber.plywoodor FloorToppngMlxIura'as6p9Ci1Ied n theIOOIvIduaI
Floor-Callng O.slgn. Olamof opanlngto be max 110..largerthandlamof pipe.As an allamate,theopeningmaybe squa:&<Utwitha max
dlm.nslon 1 In. greatarthanthedam of thepipe.
B. WoodJoists' . Nom 10In. deep(or deapar)Itrnbar. sleel or oomblnallonlumbar andsteeljoists,InJssesor StnJoIurai WoodMsmbers'with
bridgingasrequiredandwith endsflrastq:Jped.
C. FarrlngChannels. (Nol Shown)-(As required) R.slilant galvanizedsleelluning InstalledInaocadanoewiththemannarspecffiedIn the
IndividualL500SOII.s O.slgns In the FlmResist Directory.
O. GypsumBoefd"- ThlcI<n lype."""ber oflaye'" andfoolenarsshallbe as speoIfledn the1nclvfdual Floor-CailingDesIgnOiamIi
opening10be max1 In. large<thandiamIi pipe. Note: CPVC Pipe Compatibility
B. Sol. Plale- Nom2 by 410..,2 by 610..or parallel2 by 410..lumbarplales,IIghllybutted.Olamof opeo1ng Istobe mex11n.lorgarthandlam
of pipe.As an allamata.theopeningmaybe squara-outwith a maxdimenston110.gmatarthanthedam of thepipe.Platasmaybe
dlaoonllnuousoveropeoIng,lermlnallngat two opposingedgesof opening.Maxlangthof dlSOOC1IIooIIy to be 1In.geatar thandlamof
throughpenetranI.
C. Top Plate - The doubl. top pial. shalloonsIstof two nom2 by4 In., 2 by 610..or twosalsoff)'rallel2by 4 In.lurt>arplates,tirl>lIybutted.
Olamof openingIsto be max 1 In. largerth.., dlamof pipe.As an allamat., theopeningmaybe squa-a-outwitha maxdimension1In.
g",al.r thanthe dlamof the pipe.Plalesmay be dlaoontinuotJS overopening,terminatingaltwo opposingedgesof opering.MaxIangthof
dlaoonllnullyto be 110..grealarthandlamof throughpene~1ri.

C=80CSS?08
FIRESTOP SYSTEMS
Reproducedby HILTI, lno. C<UIesyIi
UnderwIIlarsLaboralorles,lno.
Oecermer10.2004
C=:80bS?08
FIRESTOP SYSTEMS
Reproduoadby HILn. lno.CWtesy Ii
UndarwrIlarsLaboratories.lno.
Deoambar10.2004
Page:
1of2 Page:
2of2

(IT1Of- RAl[I(H FIR[ Di:F-APIM,NT DESCRIPTION: REVISIONS: DRAWINGNO.


FIRE PROTECTIONDIVISION
310 WEST MARTIN ST. RALEIGH, NC 27602
FIRE STOP DETAIL 5-1-06 FP-11
WWorren IL
9 1/2" MIN.

24" MIN.
2"
2 1/2"
8" MIN.

9 1/2" MIN.
8" MIN.
45
°

3 1/2"
48"

12" MIN.

24" MIN.

3.340 x 6 SHARP "V" FORM THREAD


FINISH FLOOR CITY OF RALEIGH THREAD

CITY OF RALEIGH FIRE DEPARTMENT DESCRIPTION: REVISIONS: DATE: DRAWING NO.

FIRE PROTECTION DIVISION


310 WEST MARTIN ST. RALEIGH, NC 27602
FIRE DEPT. HOSE VALVE CABINET 5-1-06 FP-12A
W Warren LL
Wall

2"
4" 2 1/2"

45
°

48"

3.340 x 6 SHARP "V" FORM THREAD


CITY OF RALEIGH THREAD FINISH FLOOR

CITY OF RALEIGH FIRE DEPARTMENT DESCRIPTION: REVISIONS: DATE: DRAWING NO.

FIRE PROTECTION DIVISION


310 WEST MARTIN ST. RALEIGH, NC 27602
FIRE DEPT. HOSE VALVE 5-1-06 FP-12B
W Warren LL
Top Beam C-Clamp
Steel I-Beam or Model 300 Michigan
Bar Joist Top Beam C-Clamp
or Equal
W/Lock Nut

Rounded to All
Nearest Inch Thread

"A"
and Noted Rod
on Plan.

"D"
Top of Beam or Bar
Joist to Center

Line of Pipe

Pipe
"C"

Swivel Ring Swivel Ring


Take-Out

Note on Plan: Hanger Number and "A" Dimension

CITY OF RALEIGH FIRE DEPARTMENT DESCRIPTION: REVISIONS: DATE: DRAWING NO.

FIRE PROTECTION DIVISION


310 WEST MARTIN ST. RALEIGH, NC 27602
TYPICAL PIPE HANGER DETAIL 5-1-06 FP-13
W Warren LL
TO SYSTEM
NAME
SIZE

END3
FITTING2

NAME NAME
MATERIAL
FITTING

MATERIAL
SIZE
SIZE
FITTING2

FITTING2
FITTING
MATERIAL
SIZE NAME MATERIAL
FITTING

FITTING2
FITTING NAME
SIZE

MATERIAL

4 LINEAR PIPE FEET MIN.


END1
FITTING2

MATERIAL
FITTING

NAME
SIZE

36" TO 42"
ABOVE
FINISHED 5" STORZ CONNECTION
GRADE
30 DEGREE FIXED (NON-SWIVEL)
W/ CAP SECURED W/ CHAIN
4"
GUARDIAN MODEL 6625 RAL (4")
MAX. MODEL 6628 RAL (6") OR EQUAL
QUARTER TURN
BALL VALVE 12"
BALL DRIP
MAX.

END1
NAME

MATERIAL
SIZE

FITTING2
FITTING

END3
NAME

MATERIAL
SIZE

FITTING2
FITTING

BALL DRIP

36" TO 42"
&

FINISHED
FINISHED GRADE Shown for clarity.

ABOVE

GRADE
QUARTER TURN
Run parallel to wall.
BALL VALVE

FINISHED GRADE

TYPICAL NOTES:

1)-ALL EXPOSED PIPING AND FITTINGS TO BE GALVANIZED


WITH EXCEPTION OF STORZ CONNECTION

2)-40' MAX. FROM FDC TO APPARATUS ACCESS LOCATION


3)-FOR NFPA 13R SYSTEMS (2 1/2" RISER AND SMALLER) SINGLE.
FDC W/ RALEIGH THREADS (3.340 X 6 SHARPE V FORM)
4)-WHEN BUILDING HT. IS GREATER THAN 200' USE RAL. SIAMESE

CITY OF RALEIGH FIRE DEPARTMENT DESCRIPTION: REVISIONS: DATE: DRAWING NO.

FIRE PROTECTION DIVISION


310 WEST MARTIN ST. RALEIGH, NC 27602
FLUSH FDC DETAIL REQUIRMENTS 5-1-06 FP-14
W Warren LL S B
BUILDING SLAB BREEZEWAY SLAB

GALVN. SCH. 40 STEEL

FOUNDATION WALL
FOUNDATION WALL
OR D.I. SLEEVE

24" MIN. COVER TO TOP OF PIPE 24" MIN. COVER

2"
6" EXTEND RUBATEX INSULATION 2" PAST

LISTED FIRE SLEEVE AND 6" INSIDE OF SLEEVE


PROTECTION PIPING

LISTED FIRE
PROTECTION PIPING
2"
EXTEND SLEEVE 2"
PAST FOOTING

SLEEVE SIZE
FOOTING
2" TO TOP OF PIPE
NOTE:
2" TO BOTTOM OF PIPE
IF PIPE IS RUN UNDER FOOTING WITH NO PROTECTION
+ PIPE SIZE
MINIMUM CLEARANCE TO TOP OF PIPE IS 3'
= SLEEVE SIZE

PIPE ON TOP OF FOOTING


NOT TO SCALE

CITY OF RALEIGH FIRE DEPARTMENT DESCRIPTION: REVISIONS: DATE: DRAWING NO.

FIRE PROTECTION DIVISION


310 WEST MARTIN ST. RALEIGH, NC 27602 Underground fire protection 6-1-06
W. Warren LL
FP-21
18"

12"

PO
NE
C
OL
ES
36"

RISER #3 - PREACTION SYSTEM

PO
RISER #2 - IN-RACK SYSTEM

NE
C
OL
ES
HOSE VALVES (RACK AREA)
RISER #4 - DRY SYSTEM
RISER #1 - SYSTEM #4

SPRINKLER
ROOM
FIRE DEPT. CONN.

[" 3-WAY VALVE,


GUAGE & PLUG

2" ANGLE VALVE

12"
FOR MAIN DRAIN

6" OS&Y VALVE


W/TAMPER SWITCH
EF EF
CB
O

O
2" GALVANIZED 45
12" Minimum

RISER ELEVATIONS
nts

CITY OF RALEIGH FIRE DEPARTMENT DESCRIPTION: REVISIONS: DATE: DRAWING NO.

FIRE PROTECTION DIVISION


310 WEST MARTIN ST. RALEIGH, NC 27602
RISER DETAIL MULTIPLE RISER 6-1-06 FP-22
W WARREN L.L.
R-19 Batt Insulation

Secured in place

R-19 Insulation R-19 Insulation

Blown In Type Blown In Type

1/2" OSB Plywood

5/8" GWB

R-19 Batt Insulation

Secured in place

R-19 Insulation
R-19 Insulation
Blown In Type
Blown In Type

1/2" OSB Plywood

1/2" OSB Plywood 5/8" GWB

CITY OF RALEIGH FIRE DEPARTMENT DESCRIPTION: REVISIONS: DATE: DRAWING NO.

FIRE PROTECTION DIVISION


310 WEST MARTIN ST. RALEIGH, NC 27602
Insulation Detail 6-1-06 FP-23
W. Warren L.L.
SLC

Elevator
Shunt Relay Module
Breaker

SLC

N/O

N/C

Power Relay Monitor Module

SLC

EOL N/O

N/C

CITY OF RALEIGH FIRE DEPARTMENT DESCRIPTION: REVISIONS: DATE: DRAWING NO.

FIRE PROTECTION DIVISION


310 WEST MARTIN ST. RALEIGH, NC 27602 Shunt trip supervisory detail 6-1-06
W. Warren L.L.
FP-24
Dry Sprinkler
System
Elevator
Shaft

Blow off
Drain

Elev. Pit Drain plug

CITY OF RALEIGH FIRE DEPARTMENT DESCRIPTION: REVISIONS: DATE: DRAWING NO.

FIRE PROTECTION DIVISION


310 WEST MARTIN ST. RALEIGH, NC 27602 Elevator Shaft Dry System Detail 6-1-06
W. Warren L.L
FP-25
NFPA 72 AND ADA DEVICE

INSTALLATION REQUIREMENTS

CONDUIT

INSTALL PER
NATIONAL ELECTRIC CODE

MOUNT AUDIBLE
MOUNT ON A
& VISUAL DEVICES
APPROVED
ON APPROVED
BOX
BOXES.
AIR SUPPLY DIFFUSER OR
RETURN AIR OPENING
SMOKE/ HEAT
DETECTOR

0'-6" MINIMUM 0'-4" MINIMUM,


0'-4" MINIMUM 3'-0" MINIMUM
1'-0" MAXIMUM
HORN/ STROBE
EXIT

GRAPHIC
HORN SMOKE/ HEAT
ANNUNCIATOR DETECTOR
CONTROL
PANEL
STROBE

96" MAXIMUM
TOP OF DEVICE

MANUAL PULL STATION


80" MINIMUM
BOTTOM OF DEVICE

HINGED SIDE 5'-0" MAXIMUM


5'-6"

3'-8"
(3'-6" MINIMUM,
4'-0" MAXIMUM)

FINISHED
FLOOR

CITY OF RALEIGH FIRE DEPARTMENT DESCRIPTION: REVISIONS: DATE: DRAWING NO.

FIRE PROTECTION DIVISION


310 WEST MARTIN ST. RALEIGH, NC 27602
FIRE ALARM DEVICE MOUNTING 7-1-06 FP-26
W. WARREN LL
4"-12" Under Unobstructed 1
Construction (Typical) 1
HANGER INSTALLATION REQUIREMENTS
T

O
MAXIMUM DISTANCE BETWEEN HANGERS
T
S
NOMINAL PIPE SIZE 3/4" 1" 1-1/4" 1-1/2" 2" 2-1/2" 3" 4" 6"

BLAZEMASTER CPVC 5' 6" 6' 0" 6' 6" 7' 0" 8' 0" 9' 0" 10' 0" N/A N/A

THREADABLE LIGHTWALL N/A 12' 0" 12' 0" 12' 0" 12' 0" 12' 0" 12' 0" N/A N/A

STEEL PIPE (10/ 40) N/A 12' 0" 12' 0" 15' 0" 15' 0" 15' 0" 15' 0" 15' 0" 15' 0"
1"-22" Under Obstructed
Construction (Typical)
100 PSI STATIC PRESSURE ON SYSTEM REQUIRES UP-LIFT RESTRAINT WITHIN
12 INCHES HORIZONTALLY OF HEAD FOR ARM-OVERS AND END OF BRANCH LINE
1"Under Obstructed
Construction (Typical)
THE UNSUPPORTED LENGTH BETWEEN THE END SPRINKLER AND THE LAST HANGER

ON THE LINE SHALL NOT EXCEED 36" FOR 1" PIPE, 48" FOR 1 1/4" PIPE AND 60" FOR 1 1/2" PIPE OR LARGER
THE CUMULATIVE HORIZONTAL LENGTH OF AN UNSUPPORTED ARMOVER TO A SPRINKLER,
SPRINKLER DROP, OR SPRIG-UP SHALL NOT EXCEED 24"

TRAPEZE INSTALLATION REQUIREMENTS

NOMINAL PIPE SIZE SUPPORTED


SPAN OF TRAPEZE

(Schedule 10) 1" 1-1/4" 1-1/2" 2" 2-1/2" 3" 4" 6"

1 FT. 6 IN. 1" 1" 1" 1" 1" 1" 1-1/4" 1-1/4"

2 FT. 0 IN. 1" 1" 1" 1-1/4" 1-1/4" 1-1/4" 1-1/4" 1-1/2"

2 FT. 6 IN. 1-1/4" 1-1/4" 1-1/4" 1-1/4" 1-1/4" 1-1/4" 1-1/2" 2"

3 FT. 0 IN. 1-1/4" 1-1/4" 1-1/4" 1-1/4" 1-1/2" 1-1/2" 1-1/2" 2"

4 FT. 0 IN. 1-1/2" 1-1/2" 1-1/2" 1-1/2" 2" 2" 2" 2-1/2"

5 FT. 0 IN. 2" 2" 2" 2" 2" 2" 2-1/2" 2-1/2"

6 FT. 0 IN. 2" 2" 2" 2" 2" 2-1/2" 2-1/2" 3"

Correct details as required 7 FT. 0 IN. 2" 2" 2" 2-1/2" 2-1/2" 2-1/2" 2-1/2" 3"

for each installation 8 FT. 0 IN. 2-1/2" 2-1/2" 2-1/2" 2-1/2" 2-1/2" 2-1/2" 2-1/2" 3"

9 FT. O IN. 2-1/2" 2-1/2" 2-1/2" 2-1/2" 2-1/2" 2-1/2" 3" 4"

10 FT. 0 IN. 2-1/2" 2-1/2" 2-1/2" 2-1/2" 2-1/2" 3" 3" 4"

CITY OF RALEIGH FIRE DEPARTMENT DESCRIPTION: REVISIONS: DATE: DRAWING NO.

FIRE PROTECTION DIVISION 9-14-06


310 WEST MARTIN ST. RALEIGH, NC 27602
SPRINKLER DETAILS FP-28
L.L.
TYPICAL NOTES:

1)-ALL PIPING AND FITTINGS TO BE DUCTILE IORN, GALVANIZED


BRASS, STAINLESS STEEL, OR ALUMINIUM
2)-40' MAX. FROM FDC TO APPARATUS ACCESS LOCATION
3)-FDC TO FACE FIRE APPARATUS ACCESS LOCATION (DRIVEWAY)
4)-DO NOT BLOCK APPARATUS ACCESS TO BUILDING WITH HOSE
LAY FROM HYDRANT TO FDC

5)-MINIMUM DISTANCE 3 FEET BEHIND CURB, PROTECT FROM VEHICLES


6)-PROVIDE HEAT AND ALARM SUPERVISION TO HOT BOX (2 CONDUITS)
7)-COMPLY WITH PUBLIC UTILITIES HANDBOOK REQUIREMENTS

12" Minimum

To
FDC

CITY OF RALEIGH FIRE DEPARTMENT DESCRIPTION: REVISIONS: DATE: DRAWING NO.

FIRE PROTECTION DIVISION


310 WEST MARTIN ST. RALEIGH, NC 27602
HOTBOX DETAIL REQUIREMENTS 5-1-06 4-1-06 FP-27
W Warren LL L L