CENTRAL PUBLIC WORKS DEPARTMENT
No.CD0/S8E(D) /G(2)/77/ Cir. No.11/77 Dated:27.5.77
MEMORANDUM
Sub: Masonry spread footings.
Provisions regarding masonry spread footings in IS code
1080-1962 (Para 4.3.2) and the National Building Code (Para
7.1.2) are as under:
"The angle of the spread of the load from the wall base
to the outer edge of the ground bearing shall not exceed
the following values.In brick masonry and stone masonry
1/2 horizontal to 1 vertical."
However, the practice adopted in CPWD differs. Some follow
the rule given above while others follow the traditional practice
of 2-1/4" (quarter brick) offset in every course of 3" thicknéss.
The matter has been examined and it has been decided that
in future uniform practice may be followed in CPWD and an offset
of 2-1/4"(quarter brick) may be provided in every course of 3"
thickness.
In order to reduce the quantity of masonry in footings,
offsets (as many as required) should be provided in the lower
part of the footing. Enclosed sketch shows what is being done by
some of the S.Ws and what should be done to economise cost.
The above instructions may be communicated to all
concerned for implementation with immediate effect. These should
be implemented even in building under construction.
Encl: One Sketch -sa-
(V.R.VAISH)
r-in-Chief
c.P.W.D.,New Delhi.
Copy to:
All CEs/SSWs/SEs with spare copies for their EEs.tb)
A.
laso,
PUNTH A_Lever
3 345 S|
3 +
GROUND J LeveL
Ti -| ee =
1250
200 BPH,
ZUEAN CONRETE
1400
To BE ADOPTED
230
Punt /,
fuinth _
LeveL
1050
qlee eamerer eA cise sl
=
ZLEAN CONCRETE
140
GENERALLY ADOPTED
DETAILS OF OFF SETS IN MASONRY WALL CONSTRUCTION