Manual on
PROTECTION OF
GENERATORS, GENERATOR
TRANSFORMERS AND
220 kV AND 400 kV
NETWORKS
PUBLICATION NO. 274
(Revised)
Editors
C.VJ. VARMA
PK.LAL
CENTRAL BOARD OF IRRIGATION AND POWER
Malcha Marg, Chanakyapuri, New Delhi 110 021
New Delhi November 1999Section 2
LINE PROTECTION
1.0 GENERAL
‘The line protection relays are required to protect the line and clear all type of faults on it within
shortest possible time with reliability, selectivity and sensitivity. The line protection relays shall
be suitable for use with capacitive voltage transformers having passive damping and transient
response as per IEC 186.
Recommendation for provisions of line protection at different voltage levels are as follows:
1.1 400 KV Lines
‘There should be two independent high speed main protection schemes called Main-I and Main-
Il with at least one of them being carrier aided non-switched three zone distance protection.
The other protection may be a phase segregated current differential (this may require digital
communication) phase comparison, directional comparison type or a carrier aided non-switched
distance protection. Further, if Main and Main-Il are both distance protection schemes, then
they should be preferably of different types. However, they need not necessarily be of different
make. Both the protections should be suitable for single and three phase tripping. In addition
to above following shall also be provided:
{i) Two stage over-voltage protection. However in such cases where system has grown
sufficiently or in case of short lines, utilities on their discretion may decide not to provide
this protection.
(i) Auto reclose relay suitable for 1 ph/3 ph (with deadline charging and synchro check
facility) reclosure.
{it) Sensitive IDMT directional E/F relay
1.2 220 kV Lines
‘There should be atleast one carrier aided non-switched three zone distance protection scheme.
In addition to this another non-switched/switched distance scheme or directional over current
and earth fault relays should be provided as back up. Main protection should be suitable for
Single and three phase tripping, Additionally, auto-reclose relay suitable for 1 ph/3 ph (with
dead line charging and synchro-check facility) reclosure shall be provided. In case of both line
protections being Distance Protections, IDMT type E/F relay shall also be provided additionally
2.0 REQUIREMENTS
2.1 Distance Protection
Distance Protection scheme shall have the following attributes:
(i) Three independent zones
(i) Non-switched type with separate measurements for all phase to phase and phase to
ground faults.
Capable of single and three phase tripping
Directional (mho or quadrilateral or other suitably shaped) characteristics for zone 1,
zone 2 and zone 3
19(v)
(vi)
(wit)
(viii)
(ix)
(x)
(xi)
(xii)
Capable of operation for close-up three phase faults and switch on to faults
Adjustable characteristic angle to match line angle wherever applicable
Accuracy of better than or equal to 5% of set value for reach measurement in zone 1
and better than or equal to 10% of set value for zone 2 and zone 3
Accuracy of better than or equal to 5% of set value for time measurement of zone 2 and
zone 3
Variable residual compensation.
Shall include power swing detection feature for selectively blocking, as required.
Shall include suitable fuse-failure protection to monitor all types of fuse failure and block
the protection.
Maximum operating time under given set of condition shall be as follows:
{sir 4 15,
Relay setting 10 Ohms 2 Ohms
Fault location (as % of relay setting) 60% 60%
Trip duty Contacts per phase” 4 4
Fault resistance Zero Ohms Zero Ohms
Max. Operating Times 45 ms 45 ms for 3 phase faults
Including trip relays (if any) for all faults 60 ms for other faults
and with CVT
za
(i)
(i)
(ii)
(iv)
Ww
(vi)
(vii)
(viti)
2.3
‘These trip duty contacts can be provided either in-built in the distance relay or through
additional relay. Making capacity of trip contracts shall be 30 A for 0.25 $ with an
inductive load of L/R > 10 ms
Directional Comparison Protection
Shall be a unit system of protection
Shall be directional comparison type suitable for operation with one signalling channel,
e.g., PLCC
Shall have high speed fault detection based on principles like detection of post fault
travelling wave, superimposed components, etc.
Shall have high sensitivity for all types of faults
Shall be suitable for 1 and 3 phase tripping
Shall not be affected by heavy load transfer, power swings, CT saturation, CVT transients,
VT fuse failure, line charging currents, distorted primary currents and voltages, external
switching activities, sudden power reversal, zero sequence, mutual coupling, shunt reactor
“in-zone” switching ete. and lightning strokes
Shall have features like switch on to fault, weak end infeed, echo system
Shall have feature to cover nearby fault at high speed in the event of channel fail
Phase Segregated Line Differential Protec
The relay shall be all digital multi microprocessor based, designed for use with modern
digital telecommunication system multiplexer conforming to ITU-T (CCITT) specifications
and Fibre Optic medium,
20