You are on page 1of 1

+=============================================================================+

| Megger - VLF Sinus 45 Software Version: V 3.09 |


| Serial number: 12675020005 |
| Hardware ID: 000018D70528 |
+=============================================================================+
| Cable Test Report | Note |
| | |
| Project/Cable Information | |
| | |
| Project/Cable number: _______________________ | |
| | |
| Cable type: _________________________________ | |
| | |
| Location: ___________________________________ | |
| | |
| Cable Begin: ________________________________ | |
| | |
| Cable End: __________________________________ | |
| | |
| System voltage: _____________________________ | |
| | |
| Cross section: ______________________________ | |
| | |
| Length: _____________________________________ | |
| | |
| Station: ____________________________________ | |
| | |
+=============================================================================+
| |
| Mode: VLF tanDelta |
| Date of test: 11/28/2018 Start of test: 03:03:36 PM |
| |
| Phase L1 |
| Voltage Uo 13.8 kV |
| Frequency 0.1 Hz |
| Capacitance 351 nF |
| StdDev TD (Uo) 0.00 E-3 |
| Delta TD 0.9 E-3 |
| Avg. TD (0.50Uo) 1.0 E-3 |
| Avg. TD (1.00Uo) 1.0 E-3 |
| Avg. TD (1.50Uo) 1.9 E-3 |
| |
| Evaluation criterion: IEEE 400.2 (1.5U0) Insulation type: PE/XLPE |
| |
+-----------------------------------------------------------------------------+
| |
| Result (L1): no action required |
| |
| |
| Signature: ____________________ |
| |
+=============================================================================+