SEQUENCE OF OPERATION
FOR
OUTOTEC ENERGY PRODUCTS
Over Bed Burner
This Sequence of Operation isa guide to operating the combustion system only after the system has been
confirmed suitable forthe introduction of fuels and oxidants and the system has been fully commissioned by
trained personnel
“This conirol panel is tntended for Name safeguard only and does not constitute a comple safeguard
system. Logie for purge, and temperature control is the tesponsibilty ofthe customer's DCS and the
‘operation of whieh is not described in this document
‘System Pre-Start
1. Qualified personnel should instal all field wiring
2 Open any manual valves andl reset any manual limits required to safely operate this system.
3. Responsible parties may remove any lockouttazout devices
4, With Fuel and Air pressures normal, the HIGH OIL NORMAL, LOW OIL NORMAL, LOW
ATOMIZING AIR NORMAL, and AIR FLOW NORMAL lamps will be energize
15, Pull the red EMERGENCY BURNER STOP mushroom head button out to its furthest position
‘System Start
21. Withthe common, fuel, and DCS limits made:
22. Theair flow switch test is conducted,
22.1. Air pressure switch solenoid 31SOL is energized and bleeds air to atmosphere from 28PS.
222 Airflow switch 28PS opens
223. AIR PRESSURE NORMAL lamp is de-energizes
224 Air pressure switch check relay 30CR is energized and latches itself.
225. Airpressure switch 31SOl is de-energized and re-establishes pressure to 28PS,
226. Airflow switch 28PS makes
227. AIR PRESSURE NORMAL lamp is energized
23.
‘The high energy igniter insert solenoid 28SOL is energized.
Page 1 of 3
February 8, 2016
Shop Onder No.: 2258367
Panel Number: $800-1-021327Afi Pebruary 8, 2016
ives Shop Order No. 2258367
Fives North American Combustion, inc. Panel Number: 8800-1-213278
4455 East Tit Street - Cleveland, OH 44105 USA
Tel: 216.271.6000 - Fax 216,641 7852
24, With the high energy igniter inserted limit switch made, the HIGH ENERGY IGNITER
INSERTED lamp is energized.
25, The operator may now start the system. This system will automatically advance through burner light-
off sequences once statis initiated.
26 Pull the PULL TO START/PUSH TO STOP mushroom heat! button out to its furthest position. A.
contact closure is given to the BMS.
3. Purge Cycle, A minimum of 8 air volume exchanges are required prior to ignition,
3.1. Purge is @ DCS function, when completed;
3.1.1. The fuel and combustion air valve control motors must be atthe low flow position,
3.1.2. With the lov fire light off switches made (Low Start Limits) and the high energy ignited
inserted limit switch made, the tral for ignition is started.
4. Light-Of Sequence
1, The RM7830 makes its safe start check (3 sec.)
42. The ignition transformer, the upstream and downstream oill safety shutoff valves, and the MAIN
FUEL ON lamp are energized.
43, After 10 seconds the ignition transformer is de-energized,
44. With flame being sensed, the FLAME LED on the RM7830 flame relay is energized
45, The high energy igniter insert solenoid and the HIGH ENERGY IGNITER INSERTED lamp is de-
energized.
46, Ifthe flame detector has not sensed flame atthe end of the ignition timing period the system will fault
and indicate an alarm.
47, The alarm must be reset.
47.1. Deptess the FLAME FAILURE/RESET lighted pushbuston,
Note!
I all limits are still made and the fuel valve is at low flow, the bumer will stat the light-off sequence
Burner Shut Down Procedure
5.1, Push the PULL TO START/PUSH TO STOP mushroom head button in, A contact closure is given
tothe DCS,
Caution: Depressing the blue reset button on the 7890 flame relay will shut off the burner and
result in an attempted re-light without re-purging.
6. Burner Fault Shut-Down
6.1, The bumer will shut down with the following:
6.1.1. Depressing the EMERGENCY BURNER STOP push-button,
6.1.2. Loss of any limit. Manual resetting of limit may be required.
61.3, Power failure,
880041-021327A, seq doc Page 2 of3February 8, 2016
fives sept nese See?
Fives North American Combustion, Inc. Panel Number: $800-1-021327A
4455 East 71st Steet ~ Cleveland, OH 44105 USA
Tel: 216.271.6000 - Fax: 216.641.7852
6.1.4, Flame failure. This failure will also result ina lockout ofthe flame controler.
Note 1: Certain limit devioes are required by federal, state or local codes and regulations. It isthe customer’
responsibility to see that these codes and regulations are abserved and camplied with.
880041-021327A. seq doc Page 3 of 3