Introduction
The YGFC Series Fan Coil Air Conditioners are designed specially to meet the varied requirements of
zone cooling or heating using Chilled Water or Hot Water. Fan Coils can be applied to two or four pipe
systems to satisfy the requirements of a wide variety of air conditioning or heating applications. The
YGFC is available in Concealed and Exposed versions for Ceiling and Floor mounted installation. They
offer effective zone control and are especially suitable for use in Apartments, Hotels, Shopping
Centers, Office Buildings and Hospitals.
Ten sizes with airflow capacity ranging from 250 to 2200 m3/h are available. The Ceiling Concealed unit
is suitable for external static pressures up-to 60 Pa. The cooling or heating performance of a fan coil
can vary greatly with changes in Air-inlet temperature and Humidity. It also varies with the amount of
water being circulated in the coil. The water flow rate through each unit is determined by the
specification of the system that governs the difference between the Inlet and Outlet water temperature.
District Cooling systems traditionally require a 9 Deg C difference between the inlet and outlet at
maximum load conditions , to conserve the pumping power and increase the overall system efficiency.
The YGFC has a version that meets this requirement.
To facilitate choosing the correct size of a fan coil for various inlet air dry bulb and wet bulb
temperatures, as well as various inlet water temperature and temperature rise or flow rates, a
dedicated Computer Selection Software is available. The manufacturing facility has a test-lab that
allows verification of the thermal capacities given by the Software under the specified conditions.
Compatibility Sheet
CB VC VE CE
Standard Cooling Coil [Digit - 3]
GENERAL
Motor
IP 23 - 50 Hz. [Digit - 7]
Protection
Motor
OPTIONS
IP 54 - 50 Hz. [Digit - 7]
Protection
Blue Fin [ SQ - 1 ]
Fin Black Fin [ SQ - 1 ]
Protection
SPECIAL REQUESTS
Copper Fin [ SQ - 1 ]
Plenum 6mm Plenum Insulation [ SQ - 2 ]
Insulat
Flange Inlet Flange [ SQ - 3 ]
1
Nomenclature
YGFC 10 ST CB 3 X G1 G5 L
1 2 3 4 5 6 7 8 9
YORK China Model Type No. of rows Motor Type Connection Side
Fan Coil Unit ST - Standard 3 : 3 Rows G5: IP23 50 Hz L: Left handing
DC - District 4 : 4 Rows B5: IP54 50 Hz R: Right handing
Cooling A: 3 RCC + 1 R HC
Low Noise Units have 3 fan speeds and operate very silently. Whisper quiet comfort condition results in
Level Sound Data of the units at all three speeds is satisfied occupants
available
Large Range Ten different sizes with 3 and 4 row coils to closely Better control over comfort conditions results in
of Sizes match load requirement and provide de- satisfied occupant
humidification.
Compact Size Height of Ceiling Unit is restricted to 245mm for Higher Ceiling heights result in optimum comfort
& Low Height concealed unit and 262 mm for Exposed Unit to occupants
Superior Air Four different configurations allow designers to Higher Ceiling heights result in optimum comfort
Distribution provide cooling in all areas with minimum ductwork to occupants
Easy Threaded Brass connector is provided for easy Reduces installation and commissioning time
Installation piping connection. Drain and Purge Valves are and cost
provided on all units to assist in commissioning.
Easy Filters on the Concealed Units can be removed Filters can be cleaned frequently resulting in
Maintenance from any direction. Exposed units have filters that healthier comfort conditions
slide out.
The Motor-Blower assembly can be easily removed Lowers maintenance cost
for servicing at different location. Cooling coil is
accessible
2
Guide Specification
General
Furnish and install Fan Coil Units as indicated and scheduled in the plans. Units shall be factory
assembled with coils that are pressure tested individually to 350 psi (2.8 MPa). The fans must be
factory run and manufacturer must have a facility to test the capacity of cooling coils at specified
entering air conditions and specified chilled water temperature, to assure correct capacity. In addition
the test facility shall be suitable to test air capacity at specified external pressure drop at indicated
speed setting.
Basic Unit
The basic unit shall be fabricated out of 1mm galvanized steel. The fan deck and the top of the coil
section shall be lined with 10mm coated glass fiber insulation. The fan motor shall be easily removable
for serviceability. A terminal box with terminal strip shall be provided for terminating the wiring. On
ceiling concealed units with plenum, the filter shall be easily removable from either side or the back.
Standard filter shall be 6 mm nylon media and an optional filter with 23mm aluminium media shall also
be available. Units with powder coating finish shall be available as an option.
Coils
Coils shall be made out of 3/8 inch or 9.52mm OD copper tubes. Aluminium fins shall be 0.115mm thick
and the coil shall have maximum spacing of 2.3mm between the fins. The coil shall be pressure tested
to 2.8 MPa (For a working pressure of 1600 kpa) and dehydrated before assembly. A manual air vent
shall be provided on top of the coil. The coil assembly shall be protected on the side on which piping
is to be fitted with a cover made of galvanised steel sheet. The metal sheet below the coil shall be
powder coated to avoid corrosion. Black Epoxy coated fins shall be available as an option.
Motors
Motors shall be 3 speed, permanent split capacitor type with Thermal overload protection. Motors shall
have permanently lubricated ball bearings. The motors shall have a class B insulation. Standard motor
shall be IP23, IP54 available on request.
Fans
Fans shall be centrifugal direct-drive, forward curved type. Fan wheel shall be statically and
dynamically balanced.
Terminal Box
All units shall be provided with factory installed terminal box with the fan motor wired to the box.
Drain Pan
Drain Pan shall be die-formed steel, sloped to the piping connection, which will be threaded for easy
connection. Internal surface shall be painted with anti-corrosive paint. The drain pan shall be insulated
from below with closed cell formed insulation that complies with B5476 part 6 to class 1 requirements.
Testing
Manufacturer shall have a test facility to verify the air flow rate at specified external static pressure on
all three speeds.
It shall also be possible to verify the cooling capacity with water flow rates and temperature shown in
the product guide. Verification of Airflow and Capacities shall be an option available at a declared cost.
The manufacturing process should have a certified ISO 9000 quality plan.
3
Unit Dimensions & Weight - Concealed Type
55
D
Water Outlet 3/4”
517
A 50
15
238
296
222
130
231
191
245
190
35
51
Length with Std Drain Pan Length with Ext Drain Pan Plenum Weight
Model A B D Width Height
C C^ C* C*^ Conn. Dim 3 Rows 3+1,4 Rows
YGFC 02 CB (3,4) 485 515 740 840 840 940 493 543 (560) 245 485 x 130 18.0 19.0
YGFC 03 CB (3,4) 585 615 840 940 940 1040 593 543 (560) 245 585 x 130 20.8 22.1
YGFC 04 CB (3,4) 685 715 940 1040 1040 1140 693 543 (560) 245 685 x 130 23.4 24.4
YGFC 05 CB (3,4) 767 797 1022 1122 1122 1222 775 543 (560) 245 767 x 130 24.9 26.0
YGFC 06 CB (3,4) 905 935 1160 1260 1260 1360 913 543 (560) 245 905 x 130 27.4 28.6
YGFC 07 CB (3,4) 1109 1135 1360 1460 1460 1560 1113 543 (560) 245 1105 x 130 36.3 38.5
YGFC 08 CB (3,4) 1205 1235 1460 1560 1560 1660 1213 543 (560) 245 1205 x 130 38.7 41.1
YGFC 10 CB (3,4) 1305 1335 1560 1660 1660 1760 1313 543 (560) 245 1305 x 130 40.3 42.5
YGFC 12 CB (3,4) 1505 1535 1760 1860 1860 1960 1513 543 (560) 245 1505 x 130 45.8 47.7
YGFC 14 CB (3,4) 1805 1835 2060 2160 2160 2260 1813 543 (560) 245 1805 x 130 56.5 58.8
Note : 1- C^ is the length of Unit including Extra Terminal Box. 4- Width in ( ) refers to plenum with Filter & Inlet Flange.
2- C* is the length of Unit including Extending Drain Pan. 5- Weights mentioned above are for Standard Units.
3- C*^ is the length of Unit including Extra Terminal Box & For weights including Filtes, Extended Drain Pan and
Extending Drain Pan. Terminal Box please refer to Performance Sheets.
119 A
21
B
26
142
119
549
53
310
296
87
263 C
Weight
Model A (Length) B C Width Height
3 Rows 3+1,4 Rows
YGFC 02 VC (3,4) 655 595 625 263 549 22.7 24.2
YGFC 03 VC (3,4) 755 695 725 263 5 49 24.6 26.6
YGFC 04 VC (3,4) 855 795 825 263 549 27.6 29.1
YGFC 05 VC (3,4) 955 895 925 263 549 29.3 31.1
YGFC 06 VC (3,4) 1075 1015 1045 2 63 549 32.0 34.5
YGFC 07 VC (3,4) 1255 1195 1225 263 549 42.0 44.8
YGFC 08 VC (3,4) 1375 1315 1345 263 549 44.2 47.2
YGFC 10 VC (3,4) 1475 1415 1445 263 549 46.3 48.8
YGFC 12 VC (3,4) 1675 1615 1645 263 549 52.5 55.5
YGFC 14 VC (3,4) 1915 1855 1885 263 549 63.0 66.6
4
Unit Dimensions & Weight - Exposed Type
23
296
Weight
Model A (Length) B C D Width Height
3 Rows 3+1,4 Rows
YGFC 02 CE (3,4) 906 625 725 845 262 542 32.1 34.7
YGFC 03 CE (3,4) 1026 725 846 966 262 542 34.6 37.2
YGFC 04 CE (3,4) 1147 825 966 1092 262 542 38.5 41.1
YGFC 05 CE (3,4) 1168 925 1087 1208 262 542 41.3 43.8
YGFC 06 CE (3,4) 1388 1045 1207 1328 262 542 45.8 48.4
YGFC 07 CE (3,4) 1510 1225 1328 1450 262 542 55.0 55.9
YGFC 08 CE (3,4) 1630 1345 1448 1570 262 542 61.5 62.5
YGFC 10 CE (3,4) 1750 1445 1569 1690 262 542 63.2 64.2
YGFC 12 CE (3,4) 1990 1645 1809 1930 262 542 69.2 70.3
YGFC 14 CE (3,4) 2230 1885 2049 2170 262 542 83.0 84.2
Weight
Model A (Length) B C D Width Height
3 Rows 3+1,4 Rows
YGFC 02 VE (3,4) 906 625 725 845 262 542 32.1 34.7
YGFC 03 VE (3,4) 1026 725 846 966 262 542 34.6 37.2
YGFC 04 VE (3,4) 1147 825 966 1092 262 542 38.5 41.1
YGFC 05 VE (3,4) 1168 925 1087 1208 262 542 41.3 43.8
YGFC 06 VE (3,4) 1388 1045 1207 1328 262 542 45.8 48.4
YGFC 07 VE (3,4) 1510 1225 1328 1450 262 542 55.0 55.9
YGFC 08 VE (3,4) 1630 1345 1448 1570 262 542 61.5 62.5
YGFC 10 VE (3,4) 1750 1445 1569 1690 262 542 63.2 64.2
YGFC 12 VE (3,4) 1990 1645 1809 1930 262 542 69.2 70.3
YGFC 14 VE (3,4) 2230 1885 2049 2170 262 542 83.0 84.2
5
Package Dimensions
Gross Weight
Length Width Height
Model
3 Rows 4, 3+1 Rows
mm mm mm kg. kg.
Note : Weights of CB Units with Heater Terminal Box and Standard Drain Pan.
6
Specification Standard
MODEL [ CB ] 02 03 04 05 06
PERFORMANCE
COIL
Face Area sq.m 0.097 0.118 0.139 0.156 0.183
Face Velocity m/s 0.99 0.96 1.15 1.25 1.47
MOTOR
Type 3 - Speed Permanent Split Capacitor Motor
No. of motor # 1 1 1 1 1
Total Rating Output watt 36 46 63 83 113
Amp. (220 / 1 Ph. / 50 Hz.) A 0.17 0.22 0.29 0.4 0.54
FAN
Type Centrifugal Fan (Forward Curve)
No. of Fans # 1 1 1 1 1
WATER CONTENT
3 Rows Litres 1.02 1.17 1.32 1.44 1.65
4 Rows Litres 1.29 1.49 1.69 1.86 2.14
3 + 1 Rows Litres 1.49 1.69 1.89 2.06 2.34
MODEL [ CB ] 07 08 10 12 14
PERFORMANCE
COIL
Face Area sq.m 0.224 0.245 0.265 0.305 0.366
Face Velocity m/s 1.37 1.32 1.50 1.49 1.45
MOTOR
Type 3 - Speed Permanent Split Capacitor Motor
No. of motor # 1 2 2 2 3
Total Rating Output watt 136 136 187 198 234
Amp. (220 / 1 Ph. / 50 Hz.) A 0.65 0.65 0.89 0.95 1.12
FAN
Type Centrifugal Fan (Forward Curve)
No. of Fans # 1 2 2 2 3
WATER CONTENT
3 Rows Litres 1.95 2.1 2.25 2.55 3.01
4 Rows Litres 2.54 2.74 2.94 3.34 3.94
3 + 1 Rows Litres 2.74 2.94 3.14 3.54 4.14
7
Specification Standard
MODEL [ CE/VE/VC ] 02 03 04 05 06
PERFORMANCE
COIL
Face Area sq.m 0.097 0.118 0.139 0.156 0.183
Face Velocity m/s 0.98 0.96 1.15 1.25 1.46
MOTOR
Type 3 - Speed Permanent Split Capacitor Motor
No. of motor # 1 1 1 1 1
Total Rating Output watt 36 46 63 83 113
Amp. (220 / 1 Ph. / 50 Hz.) A 0.17 0.22 0.29 0.4 0.54
FAN
Type Centrifugal Fan (Forward Curve)
No. of Fans # 1 1 1 1 1
WATER CONTENT
3 Rows Litres 1.02 1.17 1.32 1.44 1.65
4 Rows Litres 1.29 1.49 1.69 1.86 2.14
3 + 1 Rows Litres 1.49 1.69 1.89 2.06 2.34
MODEL [ CE/VE/VC ] 07 08 10 12 14
PERFORMANCE
COIL
Face Area sq.m 0.224 0.245 0.265 0.305 0.366
Face Velocity m/s 1.36 1.32 1.5 1.48 1.47
MOTOR
Type 3 - Speed Permanent Split Capacitor Motor
No. of motor # 1 2 2 2 3
Total Rating Output watt 136 136 187 198 234
Amp. (220 / 1 Ph. / 50 Hz.) A 0.65 0.65 0.89 0.95 1.12
FAN
Type Centrifugal Fan (Forward Curve)
No. of Fans # 1 2 2 2 3
WATER CONTENT
3 Rows Litres 1.95 2.1 2.25 2.55 3.01
4 Rows Litres 2.54 2.74 2.94 3.34 3.94
3 + 1 Rows Litres 2.74 2.94 3.14 3.54 4.14
8
Specification District Cooling
MODEL [ CB ] 02 03 04 05 06
PERFORMANCE
COIL
Face Area sq.m 0.097 0.118 0.139 0.156 0.183
Face Velocity m/s 0.90 1.01 1.14 1.28 1.49
MOTOR
Type 3 - Speed Permanent Split Capacitor Motor
No. of motor # 1 1 1 1 1
Total Rating Output watt 34 46 62 85 114
Amp. (220 / 1 Ph. / 50 Hz.) A 0.16 0.22 0.29 0.41 0.55
FAN
Type Centrifugal Fan (Forward Curve)
No. of Fans # 1 1 1 1 1
WATER CONTENT
3 Rows Litres 1.02 1.17 1.32 1.44 1.65
4 Rows Litres 1.29 1.49 1.69 1.86 2.14
3 + 1 Rows Litres 1.49 1.69 1.89 2.06 2.34
MODEL [ CB ] 07 08 10 12 14
PERFORMANCE
COIL
Face Area sq.m 0.224 0.245 0.265 0.305 0.366
Face Velocity m/s 1.36 1.32 1.5 1.48 1.47
MOTOR
Type 3 - Speed Permanent Split Capacitor Motor
No. of motor # 1 2 2 2 3
Total Rating Output watt 142 142 187 215 244
Amp. (220 / 1 Ph. / 50 Hz.) A 0.68 0.68 0.89 1.03 1.17
FAN
Type Centrifugal Fan (Forward Curve)
No. of Fans # 1 2 2 2 3
WATER CONTENT
3 Rows Litres 1.95 2.1 2.25 2.55 3.01
4 Rows Litres 2.54 2.74 2.94 3.34 3.94
3 + 1 Rows Litres 2.74 2.94 3.14 3.54 4.14
9
Specification District Cooling
MODEL [ CE/VE/VC ] 02 03 04 05 06
PERFORMANCE
COIL
Face Area sq.m 0.097 0.118 0.139 0.156 0.183
Face Velocity m/s 0.98 0.96 1.15 1.25 1.46
MOTOR
Type 3 - Speed Permanent Split Capacitor Motor
No. of motor # 1 1 1 1 1
Total Rating Output watt 34 46 62 85 114
Amp. (220 / 1 Ph. / 50 Hz.) A 0.16 0.22 0.29 0.41 0.55
FAN
Centrifugal Fan (Forward Curve)
No. of Fans # 1 1 1 1 1
WATER CONTENT
3 Rows Litres 1.02 1.17 1.32 1.44 1.65
4 Rows Litres 1.29 1.49 1.69 1.86 2.14
3 + 1 Rows Litres 1.49 1.69 1.89 2.06 2.34
MODEL [ CE/VE/VC ] 07 08 10 12 14
PERFORMANCE
COIL
Face Area sq.m 0.224 0.245 0.265 0.305 0.366
Face Velocity m/s 1.36 1.32 1.5 1.48 1.47
MOTOR
Type 3 - Speed Permanent Split Capacitor Motor
No. of motor # 1 2 2 2 3
Total Rating Output watt 142 142 187 215 244
Amp. (220 / 1 Ph. / 50 Hz.) A 0.68 0.68 0.89 1.03 1.17
FAN
Type Centrifugal Fan (Forward Curve)
No. of Fans # 1 2 2 2 3
WATER CONTENT
3 Rows Litres 1.95 2.1 2.25 2.55 3.01
4 Rows Litres 2.54 2.74 2.94 3.34 3.94
3 + 1 Rows Litres 2.74 2.94 3.14 3.54 4.14
10
Specification
11
Specification
12
Specification
Air Cool. Capacity Air Off FCU Water Water Power Heating Water Water
LDBT
Model Speed Flow Total Sensible DB WB Flow Pressure Input Capacity Flow Pressure
m³/h kW kW °C °C m³/h kPa Watts kW °C m³/h kPa
High 404 2.38 1.73 14.3 12.9 0.410 16.2 40 2.23 36.3 0.192 8.32
YGFC 02 ST CB A X G1 E5 L Medium 389 2.30 1.67 14.3 12.9 0.396 16.1 37 2.19 36.7 0.189 8.1
Low 291 1.82 1.31 13.6 12.5 0.314 13.2 28 1.93 39.7 0.166 6.4
High 574 3.18 2.34 14.9 13.3 0.548 10.1 52 2.92 35.1 0.251 14.5
YGFC 03 ST CB A X G1 E5 L Medium 540 2.99 2.22 14.8 13.3 0.516 9.2 49 2.84 35.6 0.245 13.8
Low 389 2.35 1.71 13.9 12.8 0.405 7.4 37 2.50 39.1 0.216 10.9
High 739 4.36 3.09 14.6 12.9 0.751 19.9 75 3.61 34.5 0.311 22.8
YGFC 04 ST CB A X G1 E5 L Medium 690 4.18 2.95 14.3 12.7 0.720 17.0 66 3.50 35.0 0.301 21.5
Low 505 3.21 2.27 13.7 12.4 0.553 12.3 50 3.05 38.0 0.263 16.7
High 945 4.86 3.64 15.6 13.8 0.838 10.5 91 4.47 34.0 0.384 35.4
YGFC 05 ST CB A X G1 E5 L Medium 855 4.46 3.34 15.4 13.7 0.767 8.9 89 4.23 34.7 0.364 32.0
Low 630 3.60 2.65 14.5 13.2 0.619 6.8 80 3.58 36.9 0.308 23.5
High 1099 5.77 4.28 15.4 13.7 0.994 13.7 125 5.50 34.8 0.473 56.1
YGFC 06 ST CB A X G1 E5 L Medium 1040 5.48 4.08 15.4 13.6 0.944 13.1 120 5.35 35.3 0.460 53.2
Low 744 4.36 3.17 14.3 13.0 0.751 8.9 101 4.46 37.8 0.384 37.9
High 1318 6.63 5.03 15.7 13.9 1.142 12.1 149 7.08 35.9 0.609 99.2
YGFC 07 ST CB A X G1 E5 L Medium 1220 6.25 4.73 15.5 13.8 1.076 11.6 145 6.86 36.7 0.590 93.5
Low 904 5.04 3.76 14.7 13.3 0.868 8.8 130 5.91 39.4 0.509 70.8
High 1408 6.76 5.26 15.9 14.2 1.164 9.2 146 7.81 36.5 0.672 124.9
YGFC 08 ST CB A X G1 E5 L Medium 1334 6.39 5.01 15.9 14.2 1.101 8.1 139 7.64 37.0 0.658 119.8
Low 999 5.20 4.01 15.1 13.7 0.896 6.5 115 6.74 40.0 0.580 94.7
High 1730 8.78 6.56 15.7 13.9 1.512 14.2 204 7.53 32.9 0.648 33.4
YGFC 10 ST CB A X G1 E5 L Medium 1578 8.20 6.11 15.5 13.7 1.411 12.5 202 7.21 33.6 0.621 30.8
Low 1148 6.73 4.87 14.4 13.0 1.158 9.6 183 6.25 36.2 0.538 23.6
High 1979 10.31 7.62 15.6 13.7 1.776 20.2 226 9.03 33.5 0.778 50.9
YGFC 12 ST CB A X G1 E5 L Medium 1913 10.06 7.42 15.5 13.7 1.732 19.9 214 8.86 33.7 0.763 49.1
Low 1310 7.95 5.67 14.2 12.7 1.369 13.8 183 7.21 36.3 0.621 33.5
High 2404 13.38 9.56 15.2 13.3 2.304 35.9 266 11.47 34.2 0.988 89.0
YGFC 14 ST CB A X G1 E5 L Medium 2214 12.36 8.89 15.1 13.3 2.128 32.6 257 11.02 34.8 0.949 82.6
Low 1555 9.93 6.93 13.8 12.4 1.710 21.6 229 9.13 37.4 0.786 58.1
NOTE : Calculation based upon 0 Pa ESP.
Air Cool. Capacity Air Off FCU Water Water Power Heating Water Water
LDBT
Model Speed Flow Total Sensible DB WB Flow Pressure Input Capacity Flow Pressure
m³/h kW kW °C °C m³/h kPa Watts kW °C m³/h kPa
High 387 2.32 1.67 14.2 12.8 0.399 15.4 40 2.19 36.8 0.188 8.0
YGFC 02 ST CE A X F1 E5 L Medium 370 2.22 1.61 14.1 12.8 0.383 15.1 37 2.14 37.2 0.185 7.8
Low 262 1.70 1.21 13.3 12.2 0.293 11.6 28 1.84 40.8 0.158 5.9
High 545 3.08 2.26 14.7 13.2 0.530 9.5 51 2.86 35.5 0.246 13.9
YGFC 03 ST CE A X F1 E5 L Medium 510 2.89 2.13 14.6 13.2 0.497 8.6 48 2.78 36.2 0.239 13.3
Low 351 2.20 1.59 13.6 12.5 0.379 6.6 36 2.39 40.2 0.206 10.1
High 707 4.25 3.00 14.4 12.8 0.732 18.9 74 3.54 34.8 0.305 22.0
YGFC 04 ST CE A X F1 E5 L Medium 657 4.07 2.85 14.1 12.6 0.700 16.1 65 3.42 35.4 0.294 20.6
Low 468 3.06 2.15 13.4 12.2 0.527 11.3 49 2.96 38.8 0.255 15.8
High 914 4.75 3.55 15.5 13.7 0.817 10.1 89 4.39 34.2 0.378 34.2
YGFC 05 ST CE A X F1 E5 L Medium 828 4.36 3.27 15.3 13.6 0.752 8.6 87 4.16 34.9 0.358 31.0
Low 606 3.51 2.58 14.4 13.0 0.605 6.6 78 3.52 37.2 0.303 22.8
High 1065 5.66 4.19 15.3 13.6 0.975 13.3 123 5.41 35.1 0.466 54.5
YGFC 06 ST CE A X F1 E5 L Medium 1007 5.37 3.98 15.3 13.6 0.925 12.6 118 5.26 35.5 0.453 51.6
Low 721 4.27 3.10 14.2 12.9 0.736 8.6 99 4.37 38.0 0.376 36.5
High 1273 6.49 4.91 15.6 13.8 1.118 11.7 146 6.98 36.3 0.601 96.6
YGFC 07 ST CE A X F1 E5 L Medium 1180 6.13 4.62 15.4 13.7 1.055 11.2 142 6.76 37.0 0.582 91.0
Low 881 4.96 3.68 14.6 13.2 0.854 8.5 128 5.82 39.6 0.501 68.9
High 1336 6.51 5.06 15.8 14.1 1.121 8.6 143 7.65 37.0 0.658 120.0
YGFC 08 ST CE A X F1 E5 L Medium 1276 6.20 4.85 15.7 14.1 1.068 7.7 137 7.50 37.4 0.646 115.9
Low 939 5.01 3.83 14.9 13.6 0.863 6.2 112 6.51 40.6 0.561 88.9
High 1675 8.61 6.42 15.6 13.8 1.483 13.7 200 7.39 33.1 0.636 32.2
YGFC 10 ST CE A X F1 E5 L Medium 1529 8.04 5.98 15.4 13.7 1.384 12.1 197 7.11 33.8 0.612 30.0
Low 1119 6.62 4.78 14.3 12.9 1.139 9.3 177 6.19 36.4 0.533 23.2
High 1928 10.17 7.48 15.5 13.6 1.751 19.7 222 8.90 33.7 0.766 49.5
YGFC 12 ST CE A X F1 E5 L Medium 1843 9.86 7.24 15.3 13.6 1.699 19.2 209 8.69 34.0 0.748 47.3
Low 1264 7.78 5.53 14.0 12.6 1.340 13.3 178 7.10 36.7 0.611 32.5
High 2315 13.04 9.30 15.1 13.2 2.245 34.3 261 11.28 34.5 0.971 86.2
YGFC 14 ST CE A X F1 E5 L Medium 2123 12.07 8.64 14.9 13.2 2.078 31.3 250 10.80 35.1 0.929 79.4
Low 1500 9.75 6.77 13.6 12.2 1.679 20.9 223 8.94 37.7 0.770 55.8
NOTE : Calculation based upon 0 Pa ESP. Also Applies to VE & VC Range
13
Specification
Air Cooling Capacity Air Off FCU Water Water Power Heating Water Water
LDBT
Model Speed Pa Flow Total Sensible DB WB Flow Pressure Input Capacity Flow Pressure
m³/h kW kW °C °C m³/h kPa Watts kW °C m³/h kPa
0 404 1.93 1.36 14.0 13.0 0.332 11.0 40 2.23 36.3 0.192 8.3
High 30 340 1.73 1.20 13.5 12.6 0.298 9.0 39 2.07 38.1 0.178 7.3
60 240 1.38 0.93 12.5 11.8 0.238 6.0 36 1.77 41.9 0.152 5.5
0 389 1.86 1.31 14.0 13.0 0.320 10.9 37 2.19 36.7 0.189 8.1
YGFC 02 ST CB A X G1 E5 L Medium 30 319 1.65 1.14 13.4 12.5 0.284 8.8 36 2.01 38.7 0.173 6.9
60 219 1.29 0.86 12.4 11.7 0.222 5.6 33 1.70 43.0 0.146 5.1
0 291 1.50 1.04 13.4 12.5 0.258 9.2 28 1.93 39.7 0.166 6.4
Low 30 206 1.19 0.80 12.5 11.8 0.204 6.1 27 1.65 43.8 0.142 4.8
60 116 0.77 0.50 11.2 10.7 0.133 2.8 24 1.21 51.1 0.104 2.8
0 574 2.54 1.83 14.5 13.4 0.438 6.8 52 2.92 35.1 0.251 14.5
High 30 474 2.27 1.60 14.0 13.0 0.392 5.6 49 2.70 36.9 0.233 12.6
60 340 1.86 1.26 13.0 12.2 0.321 4.0 46 2.36 40.6 0.203 9.8
0 540 2.40 1.73 14.5 13.4 0.414 6.3 49 2.84 35.6 0.245 13.8
YGFC 03 ST CB A X G1 E5 L Medium 30 440 2.13 1.50 13.9 12.9 0.367 5.1 46 2.62 37.7 0.226 11.9
60 309 1.71 1.16 12.8 12.1 0.295 3.5 43 2.25 41.6 0.194 9.0
0 389 1.90 1.34 13.8 12.9 0.327 5.1 37 2.50 39.1 0.216 10.9
Low 30 275 1.52 1.04 12.8 12.1 0.262 3.5 35 2.12 42.9 0.183 8.1
60 160 1.03 0.68 11.4 10.9 0.178 1.9 32 1.58 49.4 0.136 4.8
0 739 3.52 2.43 14.2 13.0 0.607 13.5 75 3.61 34.5 0.311 22.8
High 30 630 3.18 2.17 13.8 12.7 0.548 11.3 72 3.36 35.8 0.289 19.9
60 479 2.70 1.79 12.9 12.0 0.465 8.4 69 2.99 38.5 0.257 16.1
0 690 3.36 2.31 14.1 12.9 0.579 11.5 66 3.50 35.0 0.301 21.5
YGFC 04 ST CB A X G1 E5 L Medium 30 579 3.02 2.04 13.5 12.5 0.520 9.5 63 3.23 36.6 0.278 18.6
60 430 2.52 1.66 12.5 11.7 0.434 6.9 59 2.86 39.8 0.247 14.9
0 505 2.61 1.79 13.5 12.5 0.449 8.5 50 3.05 38.0 0.263 16.7
Low 30 389 2.22 1.48 12.7 11.9 0.382 6.4 47 2.75 41.0 0.237 13.8
60 260 1.68 1.09 11.6 11.0 0.290 4.0 43 2.27 45.9 0.196 9.7
0 945 3.83 2.82 15.2 13.8 0.660 6.9 91 4.47 34.0 0.384 35.4
High 30 839 3.55 2.59 14.9 13.6 0.612 6.1 86 4.19 34.8 0.361 31.4
60 690 3.17 2.25 14.3 13.2 0.545 5.0 80 3.74 36.1 0.322 25.4
0 855 3.54 2.60 15.0 13.7 0.609 6.0 89 4.23 34.7 0.364 32.0
YGFC 05 ST CB A X G1 E5 L Medium 30 759 3.30 2.39 14.7 13.5 0.568 5.3 83 3.96 35.5 0.341 28.3
60 615 2.92 2.06 14.0 13.0 0.502 4.3 75 3.54 37.1 0.305 23.0
0 630 2.89 2.07 14.2 13.2 0.498 4.8 80 3.58 36.9 0.308 23.5
Low 30 550 2.68 1.89 13.8 12.9 0.461 4.2 73 3.38 38.2 0.291 21.1
60 445 2.35 1.62 13.2 12.4 0.404 3.4 65 3.10 40.6 0.267 18.0
0 1099 4.70 3.37 14.9 13.6 0.809 9.6 125 5.50 34.8 0.473 56.1
High 30 984 4.34 3.10 14.6 13.4 0.748 8.4 119 5.20 35.7 0.448 50.5
60 829 3.90 2.74 14.2 13.1 0.671 6.9 111 4.75 37.0 0.409 42.6
0 1040 4.43 3.20 14.9 13.6 0.763 9.0 120 5.35 35.3 0.460 53.2
YGFC 06 ST CB A X G1 E5 L Medium 30 924 4.10 2.94 14.6 13.4 0.706 7.9 113 5.04 36.2 0.434 47.6
60 759 3.63 2.55 14.0 13.0 0.625 6.4 103 4.51 37.6 0.388 38.8
0 744 3.52 2.49 14.1 13.0 0.606 6.2 101 4.46 37.8 0.384 37.9
Low 30 659 3.28 2.29 13.7 12.8 0.565 5.5 93 4.14 38.6 0.356 33.0
60 535 2.88 1.97 13.1 12.3 0.496 4.4 82 3.66 40.3 0.315 26.3
0 1318 5.35 3.94 15.1 13.8 0.922 8.4 149 7.08 35.9 0.609 99.2
High 30 1169 4.94 3.61 14.8 13.6 0.850 7.4 140 6.73 37.1 0.579 90.2
60 989 4.45 3.20 14.4 13.3 0.766 6.2 130 6.20 38.6 0.534 77.4
0 1220 5.01 3.70 15.0 13.7 0.863 8.0 145 6.86 36.7 0.590 93.5
YGFC 07 ST CB A X G1 E5 L Medium 30 1089 4.66 3.40 14.7 13.6 0.802 7.1 136 6.51 37.7 0.560 84.7
60 919 4.21 3.02 14.3 13.2 0.724 5.9 123 5.96 39.3 0.513 72.0
0 904 4.07 2.94 14.3 13.3 0.701 6.2 130 5.91 39.4 0.509 70.8
Low 30 814 3.83 2.73 14.0 13.1 0.659 5.6 121 5.57 40.3 0.480 63.4
60 669 3.39 2.37 13.5 12.7 0.584 4.6 107 4.95 42.0 0.426 50.9
0 1408 5.34 4.08 15.4 14.1 0.920 6.3 146 7.81 36.5 0.672 124.9
High 30 1189 4.81 3.61 15.0 13.8 0.829 5.3 137 7.29 38.2 0.627 109.7
60 965 4.26 3.11 14.4 13.4 0.733 4.4 128 6.61 40.3 0.569 91.4
0 1334 5.07 3.89 15.3 14.1 0.874 5.6 139 7.64 37.0 0.658 119.8
YGFC 08 ST CB A X G1 E5 L Medium 30 1145 4.63 3.49 15.0 13.8 0.798 4.9 131 7.17 38.6 0.618 106.5
60 904 4.03 2.95 14.3 13.4 0.694 3.9 121 6.37 40.9 0.549 85.3
0 999 4.19 3.14 14.7 13.7 0.722 4.7 115 6.74 40.0 0.580 94.7
Low 30 809 3.70 2.69 14.1 13.2 0.637 3.8 106 5.97 41.9 0.514 75.4
60 595 3.04 2.14 13.3 12.6 0.524 2.9 95 4.89 44.4 0.421 52.0
0 1730 7.15 5.17 15.1 13.7 1.232 10.1 204 7.53 32.9 0.648 33.4
High 30 1544 6.57 4.74 14.9 13.6 1.131 8.8 191 7.14 33.7 0.615 30.2
60 1290 5.84 4.15 14.4 13.3 1.005 7.2 175 6.58 35.1 0.566 26.0
0 1578 6.59 4.79 15.0 13.7 1.135 8.7 202 7.21 33.6 0.621 30.8
YGFC 10 ST CB A X G1 E5 L Medium 30 1403 6.08 4.38 14.7 13.5 1.048 7.6 187 6.83 34.5 0.588 27.9
60 1154 5.39 3.81 14.2 13.1 0.929 6.3 168 6.27 36.1 0.539 23.7
0 1148 5.41 3.81 14.1 13.1 0.931 6.7 183 6.25 36.2 0.538 23.6
Low 30 1035 5.09 3.55 13.8 12.8 0.877 6.1 164 5.99 37.2 0.516 21.8
60 844 4.50 3.07 13.2 12.3 0.775 5.0 144 5.52 39.4 0.476 18.8
0 1979 8.51 6.05 14.9 13.5 1.466 14.6 226 9.03 33.5 0.778 50.9
High 30 1789 8.00 5.63 14.7 13.3 1.378 13.1 212 8.55 34.2 0.736 45.9
60 1488 7.14 4.95 14.1 13.0 1.230 10.8 196 7.72 35.4 0.664 37.9
0 1913 8.28 5.88 14.9 13.5 1.426 14.3 214 8.86 33.7 0.763 49.1
YGFC 12 ST CB A X G1 E5 L Medium 30 1679 7.65 5.37 14.5 13.2 1.317 12.5 198 8.26 34.6 0.711 43.1
60 1380 6.75 4.66 14.0 12.9 1.162 10.1 182 7.39 35.9 0.636 35.0
0 1310 6.48 4.47 13.9 12.8 1.116 9.8 183 7.21 36.3 0.621 33.5
Low 30 1148 5.97 4.07 13.5 12.5 1.028 8.6 168 6.81 37.6 0.586 30.0
60 914 5.18 3.46 12.8 11.9 0.892 6.8 149 6.19 40.1 0.533 25.2
0 2404 11.16 7.65 14.6 13.1 1.923 26.1 266 11.47 34.2 0.988 89.0
High 30 2103 10.40 7.02 14.1 12.8 1.791 23.1 249 10.74 35.2 0.925 78.7
60 1699 9.17 6.07 13.4 12.3 1.579 18.6 229 9.61 36.8 0.828 63.9
0 2214 10.39 7.14 14.4 13.1 1.790 24.1 257 11.02 34.8 0.949 82.6
YGFC 14 ST CB A X G1 E5 L Medium 30 1910 9.59 6.48 13.9 12.7 1.652 21.0 234 10.23 35.9 0.881 71.8
60 1504 8.29 5.49 13.2 12.1 1.427 16.3 209 8.96 37.7 0.771 56.0
0 1555 8.25 5.54 13.4 12.4 1.421 15.7 229 9.13 37.4 0.786 58.1
Low 30 1359 7.62 5.05 13.0 12.0 1.311 13.7 208 8.42 38.4 0.725 49.9
60 1069 6.52 4.24 12.2 11.4 1.122 10.5 181 7.31 40.3 0.630 38.3
14
Specification
Performance Rating : YGFC | Standard | CB | 3 Rows | 2 Pipe
Air Conditions
: EDB / EWB 24 / 18 °C Water Conditions : EWT / LWT 7 / 12 °C
Fin Material / Protection : Aluminium / None delta T 5 °C
17
Specification
Air Cool. Capacity Air Off FCU Water Water Power Heating Water
LDBT Water Flow
Model Speed Flow Total Sensible DB WB Flow Pressure Input Capacity Pressure
m³/h kW kW °C °C m³/h kPa Watts kW °C m³/h kPa
High 387 1.87 1.31 13.9 12.9 0.323 10.4 40 2.19 36.8 0.189 8.1
YGFC 02 ST CB A X G1 E5 L Medium 370 1.80 1.26 13.9 12.9 0.310 10.3 37 2.15 37.2 0.185 7.8
Low 262 1.40 0.96 13.1 12.3 0.241 8.2 28 1.81 40.5 0.156 5.7
High 545 2.47 1.76 14.4 13.3 0.425 6.4 51 2.84 35.4 0.244 13.8
YGFC 03 ST CB A X G1 E5 L Medium 510 2.32 1.66 14.3 13.2 0.400 5.9 48 2.75 36.0 0.237 13.0
Low 351 1.78 1.25 13.5 12.6 0.307 4.6 36 2.34 39.7 0.201 9.7
High 707 3.42 2.36 14.1 12.9 0.589 12.8 74 3.60 35.1 0.310 22.6
YGFC 04 ST CB A X G1 E5 L Medium 657 3.26 2.23 13.9 12.8 0.562 10.9 65 3.44 35.5 0.296 20.9
Low 468 2.50 1.70 13.2 12.3 0.430 7.9 49 2.89 38.3 0.249 15.1
High 914 3.75 2.75 15.1 13.8 0.646 6.7 89 4.52 34.7 0.389 36.2
YGFC 05 ST CB A X G1 E5 L Medium 828 3.47 2.54 14.9 13.7 0.598 5.8 87 4.28 35.3 0.369 32.7
Low 606 2.83 2.02 14.1 13.1 0.487 4.6 78 3.54 37.4 0.305 23.0
High 1065 4.59 3.29 14.8 13.5 0.791 9.2 123 5.56 35.5 0.478 57.1
YGFC 06 ST CB A X G1 E5 L Medium 1007 4.34 3.12 14.8 13.5 0.747 8.7 118 5.40 35.9 0.465 54.2
Low 721 3.45 2.43 14.0 13.0 0.595 6.0 99 4.49 38.5 0.387 38.5
High 1273 5.22 3.84 15.0 13.8 0.899 8.1 146 7.07 36.5 0.609 99.0
YGFC 07 ST CB A X G1 E5 L Medium 1180 4.91 3.61 14.9 13.7 0.845 7.7 142 6.84 37.2 0.589 93.0
Low 881 4.01 2.89 14.3 13.2 0.690 6.0 128 5.94 40.0 0.511 71.4
High 1336 5.16 3.93 15.3 14.0 0.889 5.9 143 7.75 37.2 0.667 123.0
YGFC 08 ST CB A X G1 E5 L Medium 1276 4.94 3.77 15.2 14.0 0.850 5.4 137 7.59 37.6 0.653 118.3
Low 939 4.04 3.00 14.5 13.5 0.696 4.4 112 6.53 40.6 0.562 89.2
High 1675 6.98 5.04 15.1 13.7 1.202 9.7 200 7.64 33.5 0.657 34.3
YGFC 10 ST CB A X G1 E5 L Medium 1529 6.45 4.67 14.9 13.6 1.110 8.4 197 7.26 34.1 0.625 31.2
Low 1119 5.33 3.75 14.1 13.0 0.918 6.6 177 6.12 36.2 0.527 22.7
High 1928 8.38 5.94 14.9 13.5 1.443 14.2 222 9.19 34.1 0.791 52.5
YGFC 12 ST CB A X G1 E5 L Medium 1843 8.09 5.73 14.8 13.4 1.393 13.7 209 8.97 34.4 0.772 50.2
Low 1264 6.34 4.36 13.8 12.7 1.091 9.5 178 7.18 36.9 0.618 33.2
High 2315 10.94 7.46 14.4 13.1 1.883 25.2 261 11.56 34.8 0.995 90.3
YGFC 14 ST CB A X G1 E5 L Medium 2123 10.17 6.95 14.3 13.0 1.751 23.2 250 11.08 35.5 0.954 83.4
Low 1500 8.08 5.40 13.3 12.3 1.391 15.1 223 9.19 38.2 0.791 58.7
18
Specification
Performance Rating : YGFC | District Cooling | CB | 3 Rows | 2 Pipe
Air Conditions
: EDB / EWB 24 / 18 °C Water Conditions : EWT / LWT 5.5 / 14.5 °C
Fin Material / Protection : Aluminium / None delta T 9 °C
CB Range
Ceiling Concealed with Back
Plenum Units
CE Range
Ceiling Exposed Units
VC Range
Vertical Concealed Units
VE Range
Vertical Exposed Units
22
Measured Sound Pressure Level ( LpdB(A) )
The published ‘Sound Pressure Data’ is based on actual measurement being carried out as per stated standard.
The standard requires the following requirement for the noise measuring room :
• The noise should be measured in a room that simulates a half-free field with the floor being reflecting.
• The acoustics of the room should be in accordance with the requirements in Table 1.
Types of measuring room Center Frequency of the 1/3 octave band/Hz Max. Tolerance/dB
<630 ±1.5
Free field room 800~5000 ±1.0
>6300 ±1.5
<630 ±2.5
Half-free field room 800~5000 ±2.0
>6300 ±3.0
Table 1.
The unit was tested at 230V, 50Hz at the designated High, Medium and Low speed setting with free discharge of air.
1000
Fig. 1
Fig. 1 represents the arrangement in which the unit and measuring devices were located.
23
Overall Sound Pressure Level ( LpdB(A) )
Model 02 03 04 05 06 07 08 10 12 14
High 0Pa 38.7 39.9 41.8 45.3 47.9 48.9 46.4 50.0 50.8 51.6
Mid 0Pa 37.8 37.4 39.3 42.6 46.1 46.4 45.3 47.9 49.1 49.2
Low 0Pa 30.7 30.3 32.1 35.6 38.4 38.9 37.7 40.8 40.3 40.6
The above values provide an indication of the sound levels that could be obtained in space that are similar to the measuring room.
However for more detailed analysis, the ‘Sound Power data’ published in the following pages should be used and the attenuating
values deducted. Acoustic consultants carry out the detailed analysis using methods similar to the stated in page 6.
24
Operation & Controls
6 Yellow
Red
On / Off
Valve Blue
Ground Black
Typical Yellow
Thermostat Val L N Hi Med Lo
Field Unit
Wired Wired
Fig. 1
6 Yellow
HTG
Red
On / Off
Valve Blue
CLG
Ground Black
Yellow
VAL VAL L N Hi Med Lo
HTG CLG
Field Unit
Wired Wired
Fig. 2
25
Operation & Controls
2 Pipe System with Electrical Heating and Special Terminnal Box with Relays and Fuse
Unit Junction Box
6 Yellow
Red
On / Off
Valve Blue
CLG
Ground Black
Yellow
H C L N Hi Med Lo
Field Unit
Wired Wired
R1
KMC1
Heating
KM C
Contact
N
Fig. 3
Three Speed Switch The unit motor is a single-phase, permanent split capacitor type with the three speeds tappings
high/medium/low wired to the Terminal Block with colour – coded wires.
Terminal 1 – RED – high speed
Terminal 2 – BLUE – medium speed
Terminal 3 – BLACK – low speed
The selector switch on the thermostat selects the desired operating speed.
2 Pipe System Two The cooling is controlled by either modulating or switching on and off the chilled water
Port & Three Prot supply by means of a electrically operated valve. (Refer Fig. 1)
Water Valves For
Cooling
4 Pipe System Hot The 3+1 row configuration can be used for Hot water heating. A separate Hot water valve is
Water Heating required to be installed on the 1 Row Heating Coil.
The mode of switching from cooling to Heating can be Automatic or Manual. (Refer Fig. 2)
The YGFC Type CB units can be provided with One Step Electrical Heater of following
capacities.
Size 02 to Size 05 – 1000 watts
Size 06 to Size 12 – 1500 watts
2 Pipe System With Size 14 to - 2000 watts
Electrical Heating These heaters are provided as an option at extra cost.
It is important that Electrical heaters are interlocked to ensure that the Heating Element receives
no power supply when the fan is not selected to operate. Heaters are provided with high –
temperature cut out as standard and are terminated in the Terminal Box for field wiring. (Refer
Fig. 3)
Special Terminal Box A special terminal box equipped with ‘Relays’ and ‘Fuse’ can be provided at extra cost.
This allows the power for the ‘Electrical Haters’ to be supplied separately.
26
Electrical Data
Maximum Absorbed
Model No. of Motors F.L.A (A.M.P) R.C.S mm2 C.B (AMP)
Power (each) WATT
The YGFC Fan Coil unit is equipped with three-speed, permanent split capacitor motor Sizes
Motor 02 to 06 have one motor, size 07 to size 12 have two motors, and size 14 has three motors.
All motors are equipped with internal thermal overloads.
Motor The motors have permanently lubricated ball bearings as a standard offering.
Bearings
The degree of protection is specified in accordance with DIN 40050 with publication of the IEC
Degree of by means of the letter IP (Internal Protection) and a two characteristic numerals as stated in the
Protection standard. On the YGFC, IP23 protection is provided as standard. IP42 and IP54 can be
provided with options price add.
Abbreviations :
• FLA : Full Load Ampere ( For each motor) • R.C.S : Recommended Cable Size
• C.B : Circuit Breaker • Motor : Nameplate AMPs may vary