Sebelum Konservasi

Temperatur Setting : 16 C
Refrigeran
No Waktu Temperatur Tekanan (Psi)
T1 T2 T3 T4 P1 P2 P3
1 11:50 18.5 38.2 67.4 24.5 8 4 145
2 11:55 16.4 40.2 84.3 23.8 9 7 145
3 12:00 18.2 42.4 86.4 24.5 9 8 145
4 12:05 15.7 43.6 73.7 24.5 9 5 145
5 12:10 15.8 41.9 93.9 24.6 9 5 145
6 12:15 17.1 41.2 97.9 24.8 9 5 145
7 12:20 15.9 45.2 91.1 24.5 9 5 145
8 12:25 15.9 43 93.7 24 9 5 145
9 12:30 16.3 41.7 81.6 23.8 9 5 146
10 12:35 15.6 41.5 82.8 24.2 9 5 146
11 12:40 17.8 45.5 90.4 24.2 9 5 147
16.7 42.2 85.7 24.3 8.9 5.4 145.4
Setelah Konservasi
Temperatur Setting : 16 C
Refrigeran
No Waktu Temperatur Tekanan (Psi)
T1 T2 T3 T4 P1 P2 P3
1 14:10 18.9 27.9 71.6 23 7 3 138
2 14:15 19.2 28.9 71.5 22.6 7 3 140
3 14:20 20 29.3 72.6 23.4 8 3 140
4 14:25 20.3 26.5 70.1 23.6 8 3 140
5 14:40 24.1 26.4 28.8 25 10 12 100
6 14:45 24.6 27 27.8 24.6 10 12 100
21.2 27.7 57.1 23.7 8.3 6.0 126.3
RH Temperatur Temperatur
V Tegangan Arus
an (Psi) (%) In Out Ambient
P4 (m/s) input output C C C (Volt) (A)
130 3.6 63.7 63.4 26.6 25.9 26.6 223 2.62
135 3.6 65.7 65.5 26.7 25.7 26.7 223.9 2.64
135 3.8 66.2 65.9 25.7 24.8 25.7 224.4 2.67
135 3.7 66.7 66.3 25.9 25.2 25.9 225.2 2.65
135 3.6 67.9 67.4 26.1 25.7 26.1 225.8 2.72
135 3.7 68.1 67.6 25.5 24.9 25.5 225.5 2.74
135 3.4 68.6 67.7 25.4 24.7 25.4 225.7 2.72
135 3.4 68.3 68 25.3 24.8 25.3 225.6 2.76
135 3.3 69 68.4 25.3 24.8 25.3 224.9 2.72
135 3.7 67.4 67.1 25.2 24.7 25.2 225 2.7
135 3.5 67.4 66.7 25.5 25 25.5 224.8 2.71
134.5 3.6 67.2 66.7 25.7 25.1 25.7 224.9 2.7

RH Temperatur Temperatur
V Tegangan Arus
an (Psi) (%) In Out Ambient
P4 (m/s) input output C C (Volt) (A)
125 3.4 76.5 76.2 25.3 24.9 25.3 222.5 2.57
125 3.5 76.9 76.6 25.1 24.8 25.1 222.6 2.58
127 3.7 77.2 76.4 25.2 24.8 25.2 222.6 2.59
127 3.5 77.5 76.5 25.1 24.8 25.1 223 2.58
87 3.5 81.1 80.6 25 24.8 25 223.7 0.29
87 3.4 78.5 77.8 25.1 24.8 24.9 223.6 0.29
113.0 3.5 78.0 77.4 25.1 24.8 25.1 223.0 1.8
Konversi
cos phi Tekanan (Bar) selisih
P1 P2 P3 P4
0.823 0.544 0.272 9.864 8.844 0.272 1.020
0.825 0.612 0.476 9.864 9.184 0.136 0.680
0.824 0.612 0.544 9.864 9.184 0.068 0.680
0.833 0.612 0.340 9.864 9.184 0.272 0.680
0.817 0.612 0.340 9.864 9.184 0.272 0.680
0.815 0.612 0.340 9.864 9.184 0.272 0.680
0.823 0.612 0.340 9.864 9.184 0.272 0.680
0.818 0.612 0.340 9.864 9.184 0.272 0.680
0.824 0.612 0.340 9.932 9.184 0.272 0.748
0.83 0.612 0.340 9.932 9.184 0.272 0.748
0.83 0.612 0.340 10.000 9.184 0.272 0.816
0.8 0.6 0.4 9.9 9.2 0.241 0.736

Konversi
T in T air T out
cos phi Tekanan (Bar)
C C C P1 P2 P3 P4
0.838 24.9 23.3 27.3 0.476 0.204 9.388 8.503
0.835 24.8 23.1 27.3 0.476 0.204 9.524 8.503
0.835 24.8 22.7 27.3 0.544 0.204 9.524 8.639
0.839 24.8 22.6 27.3 0.544 0.204 9.524 8.639
0.995 24.8 22.7 27.3 0.680 0.816 6.803 5.918
0.995 24.8 22.7 27.3 0.680 0.816 6.803 5.918
0.9 24.8 22.9 27.3 0.6 0.4 8.6 7.7
selisih
0.272 0.884
0.272 1.020
0.340 0.884
0.340 0.884
-0.136 0.884
-0.136 0.884
0.159 0.907
Sebelum Konservasi
Indoor Unit
Waktu Tu in RH in hin rhoUin Tu out RH out hout
C (%) (kj/kg) (kg/m^3) C (%) (kj/kg)
11:50 26.6 63.7 62.574 0.8687 16 63.4 34.21
11:55 26.7 65.7 64.061 0.8697 16 65.5 34.82
12:00 25.7 66.2 60.984 0.8657 16 65.9 34.92
12:05 25.9 66.7 61.932 0.8667 16 66.3 35.05
12:10 26.1 67.9 63.278 0.8679 16 67.4 35.36
12:15 25.5 68.1 61.329 0.8654 16 67.6 35.43
12:20 25.4 68.6 61.252 0.8652 16 67.7 35.46
12:25 25.3 68.3 60.749 0.8647 16 68 35.54
12:30 25.3 69 61.120 0.8649 16 68.4 35.66
12:35 25.2 67.4 59.933 0.864 16 67.1 35.28
12:40 25.5 67.4 60.954 0.8652 16 66.7 35.15
25.75 67.18 61.65 0.87 16.00 66.73 35.17

Setelah Konservasi
Indoor Unit
Waktu Tu in RH in hin pin Tu out RH out hout
C (%) (kj/kg) (kg/m^3) C (%) (kj/kg)
14:10 25.3 76.5 65.0957 0.867 16 76.2 37.91
14:15 25.1 76.9 64.5571 0.8662 16 76.6 38.02
14:20 25.2 77.2 65.0911 0.8667 16 76.4 37.96
14:25 25.1 77.5 64.8716 0.8864 16 76.5 37.99
14:40 25 81.1 66.3703 0.8669 16 80.6 39.19
14:45 25.1 78.5 65.3962 0.8667 16 77.8 38.39
25.13 77.95 65.23 0.87 16.00 77.35 38.24
nit
pout v pu ER Waktu Tegangan Arus
(kg/m^3) m/s (Kg/m^3) (kW) Volt Ampere
1.22 3.6 1.044 2.986 0 11:50 223 2.62
1.22 3.6 1.045 3.080 5 11:55 223.9 2.64
1.22 3.8 1.043 2.892 10 12:00 224.4 2.67
1.22 3.7 1.043 2.906 15 12:05 225.2 2.65
1.21 3.6 1.039 2.924 20 12:10 225.8 2.72
1.21 3.7 1.038 2.784 25 12:15 225.5 2.74
1.21 3.4 1.038 2.548 30 12:20 225.7 2.72
1.21 3.4 1.037 2.490 35 12:25 225.6 2.76
1.21 3.3 1.037 2.441 40 12:30 224.9 2.72
1.22 3.7 1.042 2.661 45 12:35 225 2.7
1.22 3.5 1.043 2.637 50 12:40 224.8 2.71
1.22 3.57 1.04 2.76 224.89 2.70

nit
pout v pu ER Waktu Tegangan Arus
(kg/m^3) m/s (kg/m^3) Kw Volt Ampere
1.21 3.4 1.0385 2.98 0 14:10 222.5 2.57
1.21 3.5 1.0381 2.69972 5 14:15 222.6 2.58
1.21 3.7 1.03835 2.918575 10 14:20 222.6 2.59
1.21 3.5 1.0482 2.761375 15 14:25 223 2.58
1.21 3.5 1.03845 2.766087 20 14:40 223.7 0.29
0.8652 3.4 0.86595 2.226349 25 14:45 223.6 0.29
1.15 3.50 1.01 2.73 223.00 1.82

8 4 145 130 7
9 7 145 135 7
9 8 145 135 8
9 5 145 135 8
9 5 145 135 10
9 5 145 135 10
9 5 145 135
9 5 145 135
9 5 146 135
9 5 147 135
9 5 147 135
Outdoor Unit
Cos phi T1 P1 h1 s1 T2
C Bar (kj/kg) (kj/kg. C) C
0.823 18.5 0.544 286.18 1.296 38.2
0.825 16.4 0.612 317.09 1.405 40.2
0.824 18.2 0.612 323.79 1.426 42.4
0.833 15.7 0.612 297.25 1.337 43.6
0.817 15.8 0.612 342.7 1.493 41.9
0.815 17.1 0.612 352.99 1.527 41.2
0.823 15.9 0.612 333.48 1.461 45.2
0.818 15.9 0.612 341.92 1.491 43
0.824 16.3 0.612 311.59 1.395 41.7
0.83 15.6 0.612 313.71 1.393 41.5
0.83 17.8 0.612 313.84 1.392 45.5
0.82 16.65 0.61 321.32 1.42 42.22

Outdoor Unit
Cos phi T1 P1 h1 s1 T2
C Bar (kj/kg) (kj/kg. C) C
0.838 18.5 0.476 293.27 1.321 38.2
0.835 16.4 0.476 293.27 1.319 40.2
0.835 18.2 0.544 294.93 1.324 42.4
0.839 15.7 0.544 290.83 1.31 43.6
0.995 15.8 0.680 231.34 1.108 41.9
0.995 17.1 0.680 231.1 1.104 41.2
0.89 16.95 0.57 272.46 1.25 41.25

3 138 125
3 140 125
3 140 127
3 140 127
12 100 87
12 100 87
Outdoor Unit
P2 h2 s2 T3 P3 h3
Bar (kj/kg) (kj/kg. C) C Bar (kj/kg)
0.272 411.4 1.726 67.4 9.864 440.45
0.476 419.87 1.729 84.3 9.864 450.55
0.544 411.71 1.728 86.4 9.864 450.52
0.340 411.37 1.733 73.7 9.864 445.55
0.340 411.37 1.733 93.9 9.864 455.17
0.340 411.37 1.73 97.9 9.864 455.5
0.340 411.01 1.731 91.1 9.864 453.8
0.340 410.88 1.731 93.7 9.864 455.05
0.340 410.87 1.73 81.6 9.932 449
0.340 410.87 1.731 82.8 10.000 449.99
0.340 411.71 1.729 90.4 10.000 448.84
0.36 412.04 1.73 85.75 9.89 450.40

Outdoor Unit
P2 h2 s2 T3 P3 h3
Bar (kj/kg) (kj/kg. C) C Bar (kj/kg)
0.204 412.04 1.728 67.4 9.388 442.23
0.204 412.37 1.728 84.3 9.524 442.89
0.204 412.04 1.725 86.4 9.524 442.56
0.204 412.14 1.725 73.7 9.524 441.09
0.816 413.08 1.719 93.9 6.803 415.97
0.816 413.13 1.719 97.9 6.803 415.39
0.41 412.47 1.72 83.93 8.59 433.36
Daya Kerja
Efektifitas Evaporator Laju aliran massa Kompresor
T4 P4 h4 Evaporator refrigernt (kg/s)
C Bar (kj/kg) (kW) (Watt)
24.5 8.844 286.18 2.43 1227.710 0.009804 480.846
23.8 9.184 317.09 2.31 1332.811 0.012968 487.654
24.5 9.184 323.79 3.23 896.280 0.010194 493.698
24.5 9.184 297.25 2.74 1062.281 0.009308 497.118
24.6 9.184 342.7 2.53 1153.815 0.016802 501.782
24.8 9.184 352.99 2.87 970.458 0.016623 503.564
24.5 9.184 333.48 3.08 826.063 0.010655 505.243
24 9.184 341.92 2.88 863.525 0.012522 509.333
23.8 9.184 311.59 2.82 864.781 0.008711 504.064
24.2 9.184 313.71 2.70 986.436 0.010153 504.225
24.2 9.184 313.84 3.60 732.895 0.007488 505.643
24.31 9.15 321.32 2.84 992.46 0.01 499.38

Daya yang
Efektivitas Daya
T4 P4 h4 diserap air
Evporator Evaporator Laju aliran massa (watt)
C Bar (kj/kg) (kW) refrigerant mr
24.5 8.503 293.27 2.430 1.226 0.0103253 0.167256
23.8 8.503 293.27 2.736 0.987 0.0082861 0.174225
24.5 8.639 294.93 3.457 0.844 0.0072087 0.174225
24.5 8.639 290.83 2.968 0.930 0.0076692 0.174225
24.6 5.918 231.34 2.837 0.975 0.0053649 0.174225
24.8 5.918 231.1 3.013 0.739 0.0040600 0.174225
24.45 7.69 272.46 2.91 0.95 0.01 0.17
Performa HVAC terhadap Waktu
COP
18.000

2.553 15.000
2.733 12.000
1.815
9.000
COP

2.137
2.299 6.000

1.927 3.000
1.635
0.000
1.695 0 5 10 15 20 25 30 35 40 45 50 55
1.716 Waktu (menit) Sebel um
Kons ervs i
1.956 Setel ah Kons erva s i
1.449
1.99

Nilai Daya kondensor Daya yang dilepas Daya Listrik


Efektifitas Kompresor COP
total (kW) kondensor (kW)
HE (kW)
1.009 1.538 1.3723621505 0.48 2.559
1.017 1.240 1.0684184408 0.48 2.058
1.005 1.064 0.8908462992 0.48 1.754
1.006 1.152 0.9792175209 0.48 1.927
1.003 0.991 0.8168017579 0.06 15.105
1.000 0.748 0.5739875524 0.06 11.454
1.01 1.12 0.95 0.34 5.81
Heat Exchnger
Waktu Tair in Tair out Tf Cpa pa Va t pemanasan
C C C (Kj/Kg. C)(kg/m^3) m^3 s
14:10 24.9 27.3 26.1 4.1814 1000 0.05 3000
14:15 24.8 27.3 26.05 4.1814 1000 0.05 3000
14:20 24.8 27.3 26.05 4.1814 1000 0.05 3000
14:25 24.8 27.3 26.05 4.1814 1000 0.05 3000
14:40 24.8 27.3 26.05 4.1814 1000 0.05 3000
14:45 24.8 27.3 26.05 4.1814 1000 0.05 3000
eat Exchnger
Trf Cpr ma Qa Cr Ca
C (kj/kg. C) kg/s (kW) (kW/.C) (kW/.C)
45.95 0.624 0.0167 0.167256 0.006443 0.043174
54.05 0.625 0.0167 0.174225 0.005179 0.034647
55.45 0.626 0.0167 0.174225 0.004513 0.030143
49.1 0.623 0.0167 0.174225 0.004778 0.032068
59.25 0.617 0.0167 0.174225 0.00331 0.022433
61.35 0.618 0.0167 0.174225 0.002509 0.016976