ABB Technical Note - Cooling Systems PDF
ABB Technical Note - Cooling Systems PDF
One of the factors that determine the lifetime of a gen- Open ventilated (IC3A1)
erator is temperature. As all losses generate heat it is Pre-engineered generators are equipped as standard with an
important to have a cooling system that can maintain a open ventilated (IC3A1) cooling system with ducts on the air
sufficiently low operating temperature within all parts of inlets and outlet. The ducts are fitted with flanges for the con-
the generator. In order to achieve this, pre-engineered nection of external air channels. The inlet air channels must
generators use a symmetrical cooling principle that be equipped with filters (minimum filter class F6). This cooling
allows uniform cooling within the generator. method is more dependent on ambient conditions than the
others, as dirt can be sucked into the generator and cause
contamination.
Available cooling systems
The pre-engineered generator line can be provided with three The open ventilated cooling method also requires greater at-
different cooling methods depending on the ambient condi- tention to the design of the external air channels, for example:
tions.
−− Cold environment - avoiding stand-still draft into the gene-
−− Open ventilated where the ambient air is used directly for rator.
cooling. −− Pressure drop - maximum allowed pressure drop is 400Pa
−− Air-to-water cooler where the internal air in the generator for the external ducts
is cooled by a top mounted water cooler. −− Noise level - without external ducts the noise is typically
−− Air-to-air cooler where the internal air is cooled by the 15dB higher than for an enclosed water cooled generator.
ambient air through a top mounted tube heat exchanger. −− Mix of cold and warm air - as a minimum requires external
intake duct.
Air-to-water cooler (IC8A1W7)
Pre-engineered generators can also be provided with an air-
to-water cooler. This cooling method is preferable if there is
access to cooling water. The air-to-water cooler is designed
for easy withdrawal of the cooler battery from the cooler top.
It is cleanable and provided with drain holes. The air-to-water
cooler is prepared for industrial charged, fresh or brackish
water and calculated and designed for a maximum fouling
factor of 0.00009.
−− Inner tube material: copper-nickel (90/10) For more information please visit:
−− Outer tube material for double tube cooler: copper www.abb.com/motors&generators
−− Plate fin material: aluminum
−− Cooler top housing material: Painted carbon steel
−− Tube sheet material: naval brass (CuZn38Sn1)
−− Header material: rilsan coated steel (polyamide 11) We reserve the right to make technical changes or modify the contents of this
−− Cooler element casing material: galvanized steel document without prior notice. With regard to purchase orders, the agreed
particulars shall prevail. ABB Ltd does not accept any responsibility whatso-
ever for potential errors or possible lack of information in this document.
Air-to-air cooler (IC6A1A6) We reserve all rights in this document and in the subject matter and illustra-
This cooling method is suitable for generators installed in loca- tions contained herein. Any reproduction, disclosure to third parties or utiliza-
tion of its contents - in whole or in part- is forbidden without prior written
tions with limited or no access to cooling water. The standard
consent of ABB Ltd.
air-to-air cooler is fitted with two external fans, each delivering
50% of the required cooling capacity. © Copyright 2013 ABB. All Rights Reserved
Please note that the delivery time of the complete generator may
be affected by the choice of options.