You are on page 1of 2

1. Location : Station – 07 / 3rd floor / 6.

6KV HT Panel

Feeder Name : Incomer – 01 / P. No: 06

2. Name plate details :


Make ABB
Type / Model no REF 615
CT Ratio 600/1A

3. Service Settings :
Current Protection
I0>>(1) 3I>>(1)
Operation Off Operation On
I0>(1) Num of start phase 1 out of 3
Operation ON Start value 5.0*In
Start Value 0.04*In Start value multi 1.0
Start Value Multi 1.0 Time Multiplier 0.05
Time Multiplier 0.5 Operate delay time 250ms
Operate delay time 40 ms Min Operate time 20 ms
Min Operate time 20 ms Reset delay time 20 ms
Reset delay time 20 ms Operating curve type IEC deftime
Operating current type ÌEC very Inv 3I>(1)
Type of Reset curve Immediate Operation On
I0>(2) Num of start phase 1 out of 3
Operation ON Start value 0.8*In
Start Value 0.04*In Start value multi 1.0
Start Value Multi 1.0 Time Multiplier 0.05
Time Multiplier 0.5 Operate delay time 40ms
Operate delay time 40 ms Min Operate time 20 ms
Min Operate time 20 ms Reset delay time 20 ms
Reset delay time 20 ms Operating curve type IEC NI
Operating current type ÌEC very Inv

4. Secondary injection test:


Measurements:-

Ref Applied Current in secondary (A) Measured Current in Relay (A)


R 1.0 601
Y 1.0 602
B 1.0 601
4.1
Io> (1):

Operated time(sec)
Ref Set current (A) Pickup current (A) TMS
X2 X5
4.2
0.5 6.42 1.66
E/F 0.04 0.046
0.5 6.55 1.71
Io> (2)

Operated time(sec)
Ref Set current (A) Pickup current (A) TMS
X2 X5
0.5 6.37 1.68
E/F 0.04 0.048
0.5 6.54 1.68
4.3 3I>> (1)

Operated Operated time(sec)


4.4 Ref Set current (A) TMS
current (A) X2 X5
RY 5.0 5.0 0.05 0.50 0.29
YB 2.5 2.5 0.05 0.56 0.26
3I>> (1)

Operated
Ref Set current (A) Set time (S) Operated time(S)
current (A)
RY 5.0 5.0 0.25 0.30
YB 10.0 10.0 0.25 0.27

4.5 3I> (1)

Operated Operated time(sec)


Ref Set current (A) TMS
current (A) X2 X5
5.
RY 0.8 0.806 0.05 0.55 0.21
YB 0.8 2.016 0.05 0.50 0.25
Functional checks: (Whether Operational Checks OK / Not OK / Not Applicable)

1 Correct operation of appropriate indication/flag OK


2 Correct operation of output contacts OK

3 Correct operation of resetting knobs OK

6. Comments : Nil.

7. Result : Relay found Healthy.