6KV HT Panel
3. Service Settings :
Current Protection
I0>>(1) 3I>>(1)
Operation Off Operation On
I0>(1) Num of start phase 1 out of 3
Operation ON Start value 5.0*In
Start Value 0.04*In Start value multi 1.0
Start Value Multi 1.0 Time Multiplier 0.05
Time Multiplier 0.5 Operate delay time 250ms
Operate delay time 40 ms Min Operate time 20 ms
Min Operate time 20 ms Reset delay time 20 ms
Reset delay time 20 ms Operating curve type IEC deftime
Operating current type ÌEC very Inv 3I>(1)
Type of Reset curve Immediate Operation On
I0>(2) Num of start phase 1 out of 3
Operation ON Start value 0.8*In
Start Value 0.04*In Start value multi 1.0
Start Value Multi 1.0 Time Multiplier 0.05
Time Multiplier 0.5 Operate delay time 40ms
Operate delay time 40 ms Min Operate time 20 ms
Min Operate time 20 ms Reset delay time 20 ms
Reset delay time 20 ms Operating curve type IEC NI
Operating current type ÌEC very Inv
Operated time(sec)
Ref Set current (A) Pickup current (A) TMS
X2 X5
4.2
0.5 6.42 1.66
E/F 0.04 0.046
0.5 6.55 1.71
Io> (2)
Operated time(sec)
Ref Set current (A) Pickup current (A) TMS
X2 X5
0.5 6.37 1.68
E/F 0.04 0.048
0.5 6.54 1.68
4.3 3I>> (1)
Operated
Ref Set current (A) Set time (S) Operated time(S)
current (A)
RY 5.0 5.0 0.25 0.30
YB 10.0 10.0 0.25 0.27
6. Comments : Nil.