You are on page 1of 1

1. Location : Station -05/PMCC 415V, TS-19 Date: 07.07.

2018

Feeder Name : G – 40B/P.NO-9R3

2. Name plate details:

Make Areva
Type CTUM15
Sl.No. 97091625038
Aux. Volt 24– 250V DC

3. General Inspection: Ok

4. Service Setting:

Is 30mA
Ts 0.56 Sec

5. Secondary Injection Test:

Ref Set Current (A) Operating Current (A) Set Time (S) Operating Time (S)

0.03 0.032 0.56 0.62


E/F
0.16 0.158 0.56 0.63

6. Functional checks: (Whether Operational Checks OK / Not OK / Not Applicable)

1 Correct operation of appropriate indication/flag OK


2 Correct operation of output contacts OK
3 Correct operation of resetting knobs OK

7. Comments : Nil.

8. Result : Relay Found Healthy.