Surge Protection Introduction
Surge Protection Barriers provide protection for today's sensitive electronic instrumentation – protection from the destructive
effects of lightning and the transient surges that accompany this phenomenon. Surge Protection Barriers are used in a
wide range of applications including measurement and control, instrumentation, power, and communication. The undesired
consequences of surges include both equipment damage and equipment malfunction or lockup. Damage occurs when
excessive surge voltage flashes over or punctures semiconductor junctions. Semiconductors are also sensitive to accumulated
Surge Protection
over-voltage stress. Successive surges chip away at the insulating layers in a process often referred to as "electronic rust". When
the equipment finally fails it is often not attributed to surges because the accumulative minor events actually caused the failure
rather than a recent catastrophic event such as a localized lightning strike.
Operating principle
The Surge Protection Barrier incorporates line-to-line (differential mode) and
line-to-earth (common mode) protection. This is achieved by integrating suitable
"switching" elements into the Surge Protection Barrier and guaranteeing proper
connection to ground. Gas discharge tubes are used in the first switching stage of
a Surge Protection Barrier. They are able to clamp high voltages and divert high
currents, but their slow response time still allows dangerously high energy levels
to pass through. Therefore, a second element must be implemented to control the remaining energy. This silicon avalanche
Transient Voltage Suppressor (TVS) diode type responds to lower voltage and current levels extremely fast, clamps the voltages
to non-damaging levels, and diverts the surge currents to ground. Both protection stages are decoupled with inductance
elements.
Surge Protection
DIN Rail Mount
Modules
Field Mount
Modules
Modules
Plug-In
Accessories
11/2010
908837 (US) / 208599 (EU)
Edition
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surge Protection Table of Contents
Surge Protection
Selection Tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 499
Modules
Plug-In Modules
Selection Tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 500
Field Mount
Modules
Entity Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 522
Accessories
Selection Tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 500
Modules
Plug-In
Accessories
11/2010
908837 (US) / 208599 (EU)
Edition
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
System Description Surge Protection
5 6
7 8
Modules
FS
-LB
-I
FS-LB-I
Figure 1 Various Surge Protection Barriers Figure 3 Surge protection F*-LB-I
K-System
• Protection of K-System
inputs
• For isolated barriers and
signal conditioners
• Single and dual channel
versions
11/2010
908837 (US) / 208599 (EU)
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surge Protection System Description
Surge Protection
mounting and earthing.
Topology
To protect the electrical equipment in both the control room and the hazardous area, two Surge Protection Barriers must be
integrated into the intrinsically safe circuit loop. Following the international standard EN 60079-14, intrinsically safe circuits can
either be connected "at one point to the equipotential bonding system if this exists over the whole area in which the intrinsically
safe circuits are installed" or "isolated from earth". International Standard EN 60079-14 states "if intrinsically safe apparatus
(field devices, Surge Protection Barriers and intrinsically safe barriers) do not withstand the electrical strength test with at least
500 V from earth, a connection to earth at the apparatus is to be assumed".
Modules
F*-LB-I
P
I
+ K-LB-*.* K-LB-*.*G Zener Barrier
Protected
- electrical
equipment
Field Mount
Additional field housing
Modules
Protected
field device
Modules
Plug-In
Remote earth Plant earth
Accessories
11/2010
908837 (US) / 208599 (EU)
Edition
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
System Description Surge Protection
Protected
Unprotected signal loop
Since lightning-induced signals show pulse characteristics,
Surge Protection
24 V
Field mount modules (F*-LB-I)
Modules
F*-LB-I
Field Mount
Modules
GND
Two options are available for the protection of the field device:
Option 1
Modules
Plug-In
Figure 7 Field mount module grounding The standard DIN Rail mounted K-LB-*.** is located close to
the field device. It should be placed within a field enclosure
and mounted on a grounded rail. The Surge Protection Barrier
Plug-in modules (P-LB-*.*.*) must be locally bonded to control the local potential between
the signal cables and the structure.
Option 2
Accessories
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surge Protection System Description
F*-LB-I Input
24 V
Surge Protection
K-LB-1.30
P-LB-*.*.*
Additional field housing Isolated Barrier
Modules
connected to the intrinsically safe side of the Zener Barrier.
The barrier’s earth connection is made, following the – – .
described guidelines, to the main system earth in parallel to
the equipment and Zener Barrier earth cable.
G Grounded
Safe area 6 Rated voltage 6 V
Input 30 Rated voltage 30 V
24 V
1 1-channel (2-wire protection)
Field Mount
Modules
2 2-channel (4-wire protection)
LB Lightning barrier
K DIN rail mount modules
K-LB-1.30G Zener Barrier
Modules
Plug-In
Protection with isolation
The entire intrinsically safe circuit is isolated from earth. The
Intrinsic safety Ex i
intrinsically safe barrier is an isolated barrier and no
connection to the main system earth is necessary. To LB Lightning barrier
maintain the intrinsically safe measurement loop galvanically FN Field mount modules with ½ NPT thread
isolated from earth, an isolated Surge Protection Barrier must FP Field mount modules with PG13.5 thread
be installed at both ends of the loop. This must be close to the
FS Field mount modules with M20 x 1.5 thread
Accessories
isolated barrier, connected to its intrinsically safe side in the
safe area and close to the field device in the hazardous area,
but outside Zone 0.
Plug-in modules
Safe area
Input
24 V
– – . .
Protected terminals
11/2010
1 1-channel
2 2-channel
K-LB-*.* Isolated Barrier
908837 (US) / 208599 (EU)
LB Lightning barrier
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
System Description Surge Protection
Identification for availability of explosions The quality of the ground is a significant precondition for
Modules
Laws and regulations applicable to the usage or planned protection class in accordance with EN 60529 and must be
purpose of usage must be observed. Devices are only protected against adverse environmental conditions such as
approved for proper usage in accordance with intended use. splashed water or dirt beyond pollution degree 2.
Improper handling will result in voiding of any warrantee or Depending on the ignition protection class, the circuits of
manufacturer's responsibility. Surge Protection Barriers may be directed in Zone 1 or 0.
Surge Protection Barriers are used as modules positioned Special attention must be paid to a secure separation from all
upstream in the circuit from the corresponding electrical non-intrinsically safe circuits in this context. A shortest path
equipment. They make it possible to protect against distance of at least 50 mm must be maintained between
intrinsically safe and non-intrinsically safe conducting terminal
Modules
Plug-In
Intrinsic safety circuits that were operated with circuits of other Protection Barriers and the corresponding electrical
types of protection may not be used as intrinsically safe equipment as defined by explosion protection must be
circuits afterwards. observed for interconnecting with intrinsically safe electrical
equipment (proof of intrinsic safety). EN 60079-14/
IEC 60079-14 must be observed (where appropriate).
11/2010
908837 (US) / 208599 (EU)
Edition
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surge Protection System Description
The EC-Type Examination Certificates or standard Isolation coordinates for devices with
certificates/approvals should be observed. It is especially
Ex-certificate in accordance with EN 50020
important to observe the "special conditions" if these are
included in the certificates. and EN 60079-11
The use of this device must not change the ignition protection The devices are assessed for pollution degree 2 and
Surge Protection
category of the supplying circuit. Thus, for example, ib circuits overvoltage category II according to EN 50178.
must not enter Zone 0, even if they are controlled via this For additional details, see data sheets.
device – unless otherwise stated in the related approval.
Ambient conditions
Repair and maintenance
Ambient temperature
The transfer characteristics of the devices remain stable over
long periods of time. This eliminates the need for regular -30 °C to 60 °C (-22 °F to 140 °F) for Ex application, please
adjustment. Maintenance is not required. observe EC-Type Examination Certificate
Storage temperature
Fault elimination -30 °C to 80 °C (-22 °F to 176 °F)
No changes can be made to devices that are operated in
Modules
max. 75 % without moisture condensation
Field Mount
Modules
Modules
Plug-In
Accessories
11/2010
908837 (US) / 208599 (EU)
Edition
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
System Description Surge Protection
Laws and regulations applicable to the usage or planned IEC 60079-14 must be observed (where appropriate).
purpose of usage must be observed. Devices are only
The EC-Type Examination Certificates or standard
approved for proper usage in accordance with intended use.
certificates/approvals should be observed. It is especially
Improper handling will result in voiding of any warrantee or
important to observe the "special conditions" if these are
manufacturer's responsibility.
included in the certificates.
Surge Protection Barriers are used as protective modules for
The use of this device must not change the ignition protection
intrinsically safe field devices and the corresponding electrical
category of the supplying circuit. Thus, for example, ib circuits
equipment. They make it possible to protect against
must not enter Zone 0, even if they are controlled via this
overvoltages originating from various causes (lightning
Modules
Plug-In
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surge Protection System Description
Surge Protection
applicable certificates (see data sheet) are an integral part of The quality of the ground is a significant precondition for
this document. problem-free overvoltage protection. Short connections and
large cable cross-sections are basic requirements for effective
Intended use protection. These requirements can be fulfilled through the
use of appropriate accessories (see data sheets).
Laws and regulations applicable to the usage or planned
Plug-in terminal modules are designed in the IP20 protection
purpose of usage must be observed. Devices are only
class in accordance with EN 60529 and must be accordingly
approved for proper usage in accordance with intended use.
protected against adverse environmental conditions such as
Improper handling will result in voiding of any warrantee or
splashed water or dirt beyond pollution degree 2.
manufacturer's responsibility.
Plug-in terminal modules can be installed inside the
Plug-in terminal modules are used as modules positioned
hazardous area of Zone 2/Div. 2. Since plug-in terminal
upstream in the circuit from the corresponding electrical
Modules
overvoltages originating from various causes (lightning
suitable for use in Zone 2/Div. 2. The devices of the K-System
strikes, switching processes, etc.). This is achieved by
must then be installed only in Zone 2/Div. 2 if a corresponding
diverting the transient current and limiting the voltage
Declaration of Conformity for a named location or a
throughout the duration of the overvoltage surge. Various
manufacturer's Declaration of Conformity is present. For
modules are available for protecting 2, 3, 4 or 6 conductors.
information on whether this condition has been met, please
The assignment of input connections of plug-in terminal
refer to the data sheets for the devices of the K-System. The
modules/intrinsically safe equipment (binary or analog
instruction manual, the Declaration of Conformity of a named
signals) corresponds to that of the following related
location or the manufacturer's Declaration of Conformity of
Field Mount
equipment (see the corresponding data sheets). Plug-in
Modules
devices of the K-System and the information in them must be
terminal modules should only be used in combination with a
followed.
device of the K-System.
Depending on the ignition protection class, the circuits of
Protection of operating personnel and the system is not
plug-in terminal modules may be directed in Zone 1 or 0.
ensured if the product is not used in accordance with its
Special attention must be paid to a secure separation from all
intended use.
non-intrinsically safe circuits in this context. A shortest path
Intrinsic safety circuits that were operated with circuits of other distance of at least 50 mm must be maintained between
types of protection may not be used as intrinsically safe intrinsically safe and non-intrinsically safe conducting terminal
circuits afterwards. blocks during assembly. The ignition protection class is
Modules
Plug-In
determined by the connected intrinsically safe circuit of the
Application corresponding electrical equipment.
Plug-in terminal modules can be installed within the The installation of the intrinsically safe circuits is to be
hazardous area of Zone 2/Div. 2. They can be used for conducted in accordance with the relevant installation
intrinsically safe circuits up to Ex ia IIC. The ignition protection regulations.
class is determined by the connected intrinsically safe circuit The respective maximum values of the field device, the
of the corresponding electrical equipment. plug-in terminal modules and the corresponding electrical
Accessories
Plug-in terminal modules are not used to separate intrinsically equipment as defined by explosion protection must be
safe circuits from non-intrinsically safe circuits. observed for interconnecting with intrinsically safe electrical
equipment (proof of intrinsic safety). EN 60079-14/
Plug-in terminal modules must not be installed in
IEC 60079-14 must be observed (where appropriate).
dust Ex-zones.
11/2010
908837 (US) / 208599 (EU)
Edition
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
System Description Surge Protection
The EC-Type Examination Certificates or standard Isolation coordinates for devices with
certificates/approvals should be observed. It is especially
Ex-certificate in accordance with EN 50020
important to observe the "special conditions" if these are
included in the certificates. and EN 60079-11
The terminal modules must be installed in such a way that The devices are assessed for pollution degree 2 and
Surge Protection
they are protected from electrostatic charge. overvoltage category II according to EN 50178.
The use of this device must not change the ignition protection
Ambient conditions
category of the supplying circuit. Thus, for example, ib circuits
must not enter Zone 0, even if they are controlled via this Ambient temperature
device – unless otherwise stated in the related approval.
-20 °C to 60 °C (-4 °F to 140 °F)
Repair and maintenance Storage temperature
The transfer characteristics of the devices remain stable over -30 °C to 80 °C (-22 °F to 176 °F)
long periods of time. This eliminates the need for regular
Relative humidity
adjustment. Maintenance is not required.
max. 75 % without moisture condensation
DIN Rail Mount
Fault elimination
Modules
11/2010
908837 (US) / 208599 (EU)
Edition
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surge Protection Selection Tables
DIN Rail Mount Modules
Surge Protection
Grounded
Channels
K-LB-1.30 1 30 501
K-LB-2.30 2 30 502
K-LB-1.6 1 6 503
K-LB-2.6 2 6 504
K-LB-1.30G 1 30 505
Modules
K-LB-1.6G 1 6 507
K-LB-2.6G 2 6 508
Field Mount
Model Number Page
Modules
Rated Voltage (V)
Channels
Thread
FN-LB-I 1 48 ½ NPT 509
Modules
Plug-In
FS-LB-I 1 48 M20 x 1.5 510
Accessories
11/2010
908837 (US) / 208599 (EU)
Edition
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Selection Tables Surge Protection
Plug-In Modules
For Terminals
Channels
P-LB-1.A.13 1 30 1, 3 512
P-LB-2.A.1346 2 30 1, 3; 4, 6 513
P-LB-1.B.12 1 30 1, 2 514
P-LB-2.B.1245 2 30 1, 2; 4, 5 515
P-LB-1.C.123 1 30 1, 2, 3 516
DIN Rail Mount
P-LB-2.D.123456 2 30 1, 2, 3; 4, 5, 6 517
Modules
P-LB-1.E.23 1 30 2, 3 518
P-LB-2.C.2356 2 30 2, 3; 5, 6 519
P-LB-1.D.1234 1 30 1, 2, 3, 4 520
P-LB-1.F.1236 1 30 1, 2, 3, 6 521
Field Mount
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surge Protection Barrier K-LB-1.30
Surge Protection
Rated current ≤ 250 mA
Leakage current ≤ 5 μA • Protects field or control circuit
On-state voltage ≤ 45 V inputs
Ground insulation 500 V breakdown voltage • Surge protection up to 10 kA
Ambient conditions • Provides 500 V DC of isolation
Ambient temperature -30 ... 60 °C (-22 ... 140 °F) for Ex application, please
• Uninterruptable operation
observe EC-Type Examination Certificate
(auto reset)
Mechanical specifications
Protection degree IP20
Function
Mass approx. 100 g
Dimensions 12.5 x 114 x 110 mm (0.5 x 4.5 x 4.3 in)
This Surge Protection Barrier limits
Data for application in connection see page 522 for entity parameters
induced transients of different origin (e. g.
with Ex-areas
Modules
Group, category, type of protection, ¬ II 2(1)G Ex ia IIC T6
temperature classification current to ground and limiting the signal
CSA approval line voltage to a safe level for the duration
Control drawing 116-0187 (cCSAus) of the surge.
This barrier provides low 45 V line-to-line
and 500 V line-to-ground clamping
voltage for the protected instruments. It
also protects instruments that have more
Field Mount
than 500 V isolation-to-ground, such as
Modules
intrinsic safety isolated barriers, signal
conditioners and most field instruments.
For additional information, refer to the
manual and www.pepperl-fuchs.com.
Note: Surge Protection Barriers must
always be connected to a solid and
effective ground and be at the same
equipotential level as the instrument it is
Modules
protecting. The ground system must
Plug-In
comply with all applicable regulations.
Accessories
Diagrams
Front view
Terminals
not protected
K-LB-1.30
1 2
3 4
Tag holder
11/2010
1
7
2
908837 (US) / 208599 (EU)
5 6
7 8
Terminals
protected
Shield and ground
connection
Zone 0, 1, 2
Zone 1, 2
Div. 1, 2
Div. 1, 2
Edition
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 501
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K-LB-2.30 Surge Protection Barrier
Diagrams
Front view
Terminals
not protected
K-LB-2.30
1 2
3 4
Tag holder
1
7
11/2010
2 8
908837 (US) / 208599 (EU)
3
5
4
6
5 6
7 8
Terminals
protected
Shield and ground
connection
Zone 0, 1, 2
Zone 1, 2
Div. 1, 2
Div. 1, 2
Edition
502 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surge Protection Barrier K-LB-1.6
Surge Protection
Rated current ≤ 250 mA
Leakage current ≤ 10 μA • Protects field or control circuit
On-state voltage ≤ 12 V inputs
Ground insulation 500 V breakdown voltage • Surge protection up to 10 kA
Ambient conditions • Provides 500 V DC of isolation
Ambient temperature -30 ... 60 °C (-22 ... 140 °F) for Ex application, please
• Uninterruptable operation
observe EC-Type Examination Certificate
(auto reset)
Mechanical specifications
Protection degree IP20
Function
Mass approx. 100 g
Dimensions 12.5 x 114 x 110 mm (0.5 x 4.5 x 4.3 in)
This Surge Protection Barrier limits
Data for application in connection see page 522 for entity parameters
induced transients of different origin (e. g.
with Ex-areas
Modules
Group, category, type of protection, ¬ II 2(1)G Ex ia IIC T6
temperature classification current to ground and limiting the signal
CSA approval line voltage to a safe level for the duration
Control drawing 116-0187 (cCSAus) of the surge.
This barrier provides low 12 V line-to-line
and 500 V line-to-ground clamping
voltage for the protected instruments. It
also protects instruments that have more
Field Mount
than 500 V isolation-to-ground, such as
Modules
intrinsic safety isolated barriers, signal
conditioners and most field instruments.
For additional information, refer to the
manual and www.pepperl-fuchs.com.
Note: Surge Protection Barriers must
always be connected to a solid and
effective ground and be at the same
equipotential level as the instrument it is
Modules
protecting. The ground system must
Plug-In
comply with all applicable regulations.
Accessories
Diagrams
Front view
Terminals
not protected
K-LB-1.6
1 2
3 4
Tag holder
11/2010
1
7
2
908837 (US) / 208599 (EU)
5 6
7 8
Terminals
protected
Shield and ground
connection
Zone 0, 1, 2
Zone 1, 2
Div. 1, 2
Div. 1, 2
Edition
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 503
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K-LB-2.6 Surge Protection Barrier
Diagrams
Front view
Terminals
not protected
K-LB-2.6
1 2
3 4
Tag holder
1
7
11/2010
2 8
908837 (US) / 208599 (EU)
3
5
4
6
5 6
7 8
Terminals
protected
Shield and ground
connection
Zone 0, 1, 2
Zone 1, 2
Div. 1, 2
Div. 1, 2
Edition
504 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surge Protection Barrier K-LB-1.30G
Surge Protection
Rated current ≤ 250 mA
Leakage current ≤ 5 μA • Protects field or control circuit
On-state voltage ≤ 45 V inputs
Ambient conditions • Surge protection up to 10 kA
Ambient temperature -30 ... 60 °C (-22 ... 140 °F) for Ex application, please • Uninterruptable operation
observe EC-Type Examination Certificate (auto reset)
Mechanical specifications
Protection degree IP20 Function
Mass approx. 100 g
Dimensions 12.5 x 114 x 110 mm (0.5 x 4.5 x 4.3 in) This Surge Protection Barrier limits
Data for application in connection see page 522 for entity parameters induced transients of different origin (e. g.
with Ex-areas
lightning stroke, switching impulse, etc.).
EC-Type Examination Certificate PTB 00 ATEX 2176X
Modules
temperature classification
line voltage to a safe level for the duration
CSA approval
of the surge.
Control drawing 116-0187 (cCSAus)
This barrier provides a low line-to-line and
line-to-ground clamping voltage for the
protected instrument. It also protects
instruments that have less than 500 V
isolation-to-ground, such as Zener
Barriers, standard I/O cards, and some
Field Mount
Modules
field instruments.
For additional information, refer to the
manual and www.pepperl-fuchs.com.
Note: Surge Protection Barriers must
always be connected to a solid and
effective ground and be at the same
equipotential level as the instrument it is
protecting. The ground system must
comply with all applicable regulations.
Modules
Plug-In
Accessories
Diagrams
Front view
Terminals
not protected
K-LB-1.30G
1 2
3 4
Tag holder
11/2010
1
7
2
908837 (US) / 208599 (EU)
5 6
7 8
Terminals
protected
Shield and ground
connection
Zone 0, 1, 2
Zone 1, 2
Div. 1, 2
Div. 1, 2
Edition
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 505
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K-LB-2.30G Surge Protection Barrier
temperature classification
line voltage to a safe level for the duration
CSA approval
of the surge.
Control drawing 116-0187 (cCSAus)
This barrier provides a low line-to-line and
line-to-ground clamping voltage for the
protected instrument. It also protects
instruments that have less than 500 V
isolation-to-ground, such as Zener
Barriers, standard I/O cards, and some
Field Mount
Modules
field instruments.
For additional information, refer to the
manual and www.pepperl-fuchs.com.
Note: Surge Protection Barriers must
always be connected to a solid and
effective ground and be at the same
equipotential level as the instrument it is
protecting. The ground system must
comply with all applicable regulations.
Modules
Plug-In
Accessories
Diagrams
Front view
Terminals
not protected
K-LB-2.30G
1 2
3 4
Tag holder
1
7
11/2010
2 8
908837 (US) / 208599 (EU)
3
5
4
6
5 6
7 8
Terminals
protected
Shield and ground
connection
Zone 0, 1, 2
Zone 1, 2
Div. 1, 2
Div. 1, 2
Edition
506 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surge Protection Barrier K-LB-1.6G
Surge Protection
Rated current ≤ 250 mA
Leakage current ≤ 5 μA • Protects field or control circuit
On-state voltage ≤ 12 V inputs
Ambient conditions • Surge protection up to 10 kA
Ambient temperature -30 ... 60 °C (-22 ... 140 °F) for Ex application, please • Uninterruptable operation
observe EC-Type Examination Certificate (auto reset)
Mechanical specifications
Protection degree IP20 Function
Mass approx. 100 g
Dimensions 12.5 x 114 x 110 mm (0.5 x 4.5 x 4.3 in) This Surge Protection Barrier limits
Data for application in connection see page 522 for entity parameters induced transients of different origin (e. g.
with Ex-areas
lightning stroke, switching impulse, etc.).
EC-Type Examination Certificate PTB 00 ATEX 2176X
Modules
temperature classification
line voltage to a safe level for the duration
CSA approval
of the surge.
Control drawing 116-0187 (cCSAus)
This barrier provides a low line-to-line and
line-to-ground clamping voltage for the
protected instrument. It also protects
instruments that have less than 500 V
isolation-to-ground, such as Zener
Barriers, standard I/O cards, and some
Field Mount
Modules
field instruments.
For additional information, refer to the
manual and www.pepperl-fuchs.com.
Note: Surge Protection Barriers must
always be connected to a solid and
effective ground and be at the same
equipotential level as the instrument it is
protecting. The ground system must
comply with all applicable regulations.
Modules
Plug-In
Accessories
Diagrams
Front view
Terminals
not protected
K-LB-1.6G
1 2
3 4
Tag holder
11/2010
1
7
2
908837 (US) / 208599 (EU)
5 6
7 8
Terminals
protected
Shield and ground
connection
Zone 0, 1, 2
Zone 1, 2
Div. 1, 2
Div. 1, 2
Edition
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 507
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K-LB-2.6G Surge Protection Barrier
temperature classification
line voltage to a safe level for the duration
CSA approval
of the surge.
Control drawing 116-0187 (cCSAus)
This barrier provides a low line-to-line and
line-to-ground clamping voltage for the
protected instrument. It also protects
instruments that have less than 500 V
isolation-to-ground, such as Zener
Barriers, standard I/O cards, and some
Field Mount
Modules
field instruments.
For additional information, refer to the
manual and www.pepperl-fuchs.com.
Note: Surge Protection Barriers must
always be connected to a solid and
effective ground and be at the same
equipotential level as the instrument it is
protecting. The ground system must
comply with all applicable regulations.
Modules
Plug-In
Accessories
Diagrams
Front view
Terminals
not protected
K-LB-2.6G
1 2
3 4
Tag holder
1
7
11/2010
2 8
908837 (US) / 208599 (EU)
3
5
4
6
5 6
7 8
Terminals
protected
Shield and ground
connection
Zone 0, 1, 2
Zone 1, 2
Div. 1, 2
Div. 1, 2
Edition
508 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surge Protection Barrier FN-LB-I
Surge Protection
Leakage current ≤ 5 μA
On-state voltage ≤ 85 V • Stainless steel housing
Ground insulation ≥ 500 V breakdown voltage • Discharge current 10 kA
Ambient conditions • 500 V isolation from earth
Ambient temperature -30 ... 60 °C (-22 ... 140 °F) for Ex application, please
• Suitable for hazardous area
observe EC-Type Examination Certificate
Mechanical specifications
Function
Housing material stainless steel 1.4401 (AISI 316)
surface all over polished
This Surge Protection Barrier limits
Protection degree IP20
induced transients of different origin (e. g.
Cable
lightning stroke, switching impulse, etc.).
Length L 0.4 m
This is achieved by diverting the transient
Mass approx. 200 g
Modules
Mounting ½ NPT thread
of the surge.
Data for application in connection see page 522 for entity parameters
with Ex-areas This barrier provides 85 V line-to-line and
EC-Type Examination Certificate PTB 00 ATEX 2175 500 V line-to-ground clamping voltage for
Group, category, type of protection, ¬ II 2G EEx ia IIC T6 the protected instruments. It also protects
temperature classification instruments that have less than 500 V
CSA approval isolation-to-ground.
Control drawing 116-0187 (cCSAus)
It is installed in an available conduit or
Field Mount
cable gland opening like those found on
Modules
most process transmitters.
For additional information, refer to the
manual and www.pepperl-fuchs.com.
Note: Surge Protection Barriers must
always be connected to a solid and
effective ground and be at the same
equipotential level as the instrument it is
protecting. The ground system must
Modules
Plug-In
comply with all applicable regulations.
Accessories
Diagrams
1/2" NPT
rd FN-LB-I
11/2010
GND gn/ye
bk
908837 (US) / 208599 (EU)
Zone 1, 2
Div. 1, 2
Edition
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 509
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
FS-LB-I Surge Protection Barrier
Leakage current ≤ 5 μA
• Stainless steel housing On-state voltage ≤ 85 V
• Discharge current 10 kA Ground insulation ≥ 500 V breakdown voltage
• 500 V isolation from earth Ambient conditions
Ambient temperature -30 ... 60 °C (-22 ... 140 °F) for Ex application, please
• Suitable for hazardous area
observe EC-Type Examination Certificate
Mechanical specifications
Function
Housing material stainless steel 1.4401 (AISI 316)
surface all over polished
This Surge Protection Barrier limits
Protection degree IP20
induced transients of different origin (e. g.
Cable
lightning stroke, switching impulse, etc.).
Length L 0.4 m
This is achieved by diverting the transient
Mass approx. 200 g
DIN Rail Mount
Diagrams
M20x15
FS-LB-I rd
11/2010
GND gn/ye
bk
908837 (US) / 208599 (EU)
Zone 1, 2
Div. 1, 2
Edition
510 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surge Protection Barrier FP-LB-I
Surge Protection
Leakage current ≤ 5 μA
On-state voltage ≤ 85 V • Stainless steel housing
Ground insulation ≥ 500 V breakdown voltage • Discharge current 10 kA
Ambient conditions • 500 V isolation from earth
Ambient temperature -30 ... 60 °C (-22 ... 140 °F) for Ex application, please
• Suitable for hazardous area
observe EC-Type Examination Certificate
Mechanical specifications
Function
Housing material stainless steel 1.4401 (AISI 316)
surface all over polished
This Surge Protection Barrier limits
Protection degree IP20
induced transients of different origin (e. g.
Cable
lightning stroke, switching impulse, etc.).
Length L 0.4 m
This is achieved by diverting the transient
Mass approx. 200 g
Modules
Mounting PG13.5 thread
of the surge.
Data for application in connection see page 522 for entity parameters
with Ex-areas This barrier provides 85 V line-to-line and
EC-Type Examination Certificate PTB 00 ATEX 2175 500 V line-to-ground clamping voltage for
Group, category, type of protection, ¬ II 2G EEx ia IIC T6 the protected instruments. It also protects
temperature classification instruments that have less than 500 V
CSA approval isolation-to-ground.
Control drawing 116-0187 (cCSAus)
It is installed in an available conduit or
Field Mount
cable gland opening like those found on
Modules
most process transmitters.
For additional information, refer to the
manual and www.pepperl-fuchs.com.
Note: Surge Protection Barriers must
always be connected to a solid and
effective ground and be at the same
equipotential level as the instrument it is
protecting. The ground system must
Modules
Plug-In
comply with all applicable regulations.
Accessories
Diagrams
Pg 13,5
rd FP-LB-I
11/2010
GND gn/ye
bk
908837 (US) / 208599 (EU)
Zone 1, 2
Div. 1, 2
Edition
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 511
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
P-LB-1.A.13 Surge Protection Barrier
CSA approval
different origin (e. g. lightning stroke,
Control drawing 116-0187 (cCSAus)
switching impulse, etc.). This is achieved
by diverting the transient current to
ground and limiting the signal line voltage
to a safe level for the duration of the
surge.
The end digits of the model designation
Field Mount
Diagrams
Front view
Connection to earth
P-LB-1.A.13
Removable terminal
blue, not protected
11/2010
1 (1)
3 (3)
908837 (US) / 208599 (EU)
512 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surge Protection Barrier P-LB-2.A.1346
Surge Protection
Rated current ≤ 250 mA
Leakage current ≤ 5 μA
• Analog or digital signal inputs
On-state voltage ≤ 45 V • Surge protection up to 10 kA
Ground insulation ≤ 500 V breakdown voltage • Protects leads 1, 3, 4 and 6 of
Ambient conditions KF modules
Ambient temperature -20 ... 60 °C (-4 ... 140 °F) • Uninterruptable operation
Mechanical specifications (auto reset)
Protection degree IP20
Mass approx. 70 g Function
Dimensions 20 x 62 x 115 mm (0.8 x 2.4 x 4.5 in)
Data for application in connection see page 522 for entity parameters This Surge Protection Barrier is designed
with Ex-areas for use with K-System (KF modules).
EC-Type Examination Certificate PTB 02 ATEX 2044
Modules
CSA approval
safely protected against voltage surges of
Control drawing 116-0187 (cCSAus)
different origin (e. g. lightning stroke,
switching impulse, etc.). This is achieved
by diverting the transient current to
ground and limiting the signal line voltage
to a safe level for the duration of the
surge.
Field Mount
The end digits of the model designation
Modules
correspond to the protected terminals of
the respective KF module.
For additional information, refer to the
manual and www.pepperl-fuchs.com.
Note: Surge Protection Barriers must
always be connected to a solid and
effective ground and be at the same
equipotential level as the instrument it is
Modules
protecting. The ground system must
Plug-In
comply with all applicable regulations.
Accessories
Diagrams
Front view
Connection to earth
P-LB-2.A.1346
Removable terminals
blue, not protected
11/2010
1 (1)
3 (3)
908837 (US) / 208599 (EU)
4 (4)
6 (6)
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 513
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
P-LB-1.B.12 Surge Protection Barrier
CSA approval
different origin (e. g. lightning stroke,
Control drawing 116-0187 (cCSAus)
switching impulse, etc.). This is achieved
by diverting the transient current to
ground and limiting the signal line voltage
to a safe level for the duration of the
surge.
The end digits of the model designation
Field Mount
Diagrams
Front view
Connection to earth
P-LB-1.B.12
Removable terminal
blue, not protected
11/2010
1 (1)
2 (2)
908837 (US) / 208599 (EU)
514 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surge Protection Barrier P-LB-2.B.1245
Surge Protection
Rated current ≤ 250 mA
Leakage current ≤ 5 μA
• Analog or digital signal inputs
On-state voltage ≤ 45 V • Surge protection up to 10 kA
Ground insulation ≤ 500 V breakdown voltage • Protects leads 1, 2, 4 and 5 of
Ambient conditions KF modules
Ambient temperature -20 ... 60 °C (-4 ... 140 °F) • Uninterruptable operation
Mechanical specifications (auto reset)
Protection degree IP20
Mass approx. 70 g Function
Dimensions 20 x 62 x 115 mm (0.8 x 2.4 x 4.5 in)
Data for application in connection see page 522 for entity parameters This Surge Protection Barrier is designed
with Ex-areas for use with K-System (KF modules).
EC-Type Examination Certificate PTB 02 ATEX 2044
Modules
CSA approval
safely protected against voltage surges of
Control drawing 116-0187 (cCSAus)
different origin (e. g. lightning stroke,
switching impulse, etc.). This is achieved
by diverting the transient current to
ground and limiting the signal line voltage
to a safe level for the duration of the
surge.
Field Mount
The end digits of the model designation
Modules
correspond to the protected terminals of
the respective KF module.
For additional information, refer to the
manual and www.pepperl-fuchs.com.
Note: Surge Protection Barriers must
always be connected to a solid and
effective ground and be at the same
equipotential level as the instrument it is
Modules
protecting. The ground system must
Plug-In
comply with all applicable regulations.
Accessories
Diagrams
Front view
Connection to earth
P-LB-2.B.1245
Removable terminals
blue, not protected
11/2010
1 (1)
2 (2)
908837 (US) / 208599 (EU)
4 (4)
5 (5)
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 515
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
P-LB-1.C.123 Surge Protection Barrier
CSA approval
safely protected against voltage surges of
Control drawing 116-0187 (cCSAus)
different origin (e. g. lightning stroke,
switching impulse, etc.). This is achieved
by diverting the transient current to
ground and limiting the signal line voltage
to a safe level for the duration of the
surge.
Field Mount
Diagrams
Front view
Connection to earth
P-LB-1.C.123
Removable terminal
blue, not protected
11/2010
1 (1)
2 (2)
908837 (US) / 208599 (EU)
3 (3)
516 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surge Protection Barrier P-LB-2.D.123456
Surge Protection
Rated current ≤ 250 mA
Leakage current ≤ 5 μA
• Analog or digital signal inputs
On-state voltage ≤ 45 V • Surge protection up to 10 kA
Ground insulation ≤ 500 V breakdown voltage • Protects leads 1, 2, 3, 4, 5 and 6 of
Ambient conditions KF modules
Ambient temperature -20 ... 60 °C (-4 ... 140 °F) • Uninterruptable operation
Mechanical specifications (auto reset)
Protection degree IP20
Mass approx. 70 g Function
Dimensions 20 x 62 x 115 mm (0.8 x 2.4 x 4.5 in)
Data for application in connection see page 522 for entity parameters This Surge Protection Barrier is designed
with Ex-areas for use with K-System (KF modules).
EC-Type Examination Certificate PTB 02 ATEX 2044
Modules
CSA approval
safely protected against voltage surges of
Control drawing 116-0187 (cCSAus)
different origin (e. g. lightning stroke,
switching impulse, etc.). This is achieved
by diverting the transient current to
ground and limiting the signal line voltage
to a safe level for the duration of the
surge.
Field Mount
The end digits of the model designation
Modules
correspond to the protected terminals of
the respective KF module.
For additional information, refer to the
manual and www.pepperl-fuchs.com.
Note: Surge Protection Barriers must
always be connected to a solid and
effective ground and be at the same
equipotential level as the instrument it is
Modules
protecting. The ground system must
Plug-In
comply with all applicable regulations.
Accessories
Diagrams
Front view
Connection to earth
P-LB-2.D.123456
Removable terminals
blue, not protected
1 (1)
11/2010
2 (2)
3 (3)
908837 (US) / 208599 (EU)
4 (4)
5 (5)
6 (6)
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
P-LB-1.E.23 Surge Protection Barrier
CSA approval
different origin (e. g. lightning stroke,
Control drawing 116-0187 (cCSAus)
switching impulse, etc.). This is achieved
by diverting the transient current to
ground and limiting the signal line voltage
to a safe level for the duration of the
surge.
The end digits of the model designation
Field Mount
Diagrams
Front view
Connection to earth
P-LB-1.E.23
Removable terminal
blue, not protected
11/2010
2 (2)
3 (3)
908837 (US) / 208599 (EU)
518 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surge Protection Barrier P-LB-2.C.2356
Surge Protection
Rated current ≤ 250 mA
Leakage current ≤ 5 μA
• Analog or digital signal inputs
On-state voltage ≤ 45 V • Surge protection up to 10 kA
Ground insulation ≤ 500 V breakdown voltage • Protects leads 2, 3, 5 and 6 of
Ambient conditions KF modules
Ambient temperature -20 ... 60 °C (-4 ... 140 °F) • Uninterruptable operation
Mechanical specifications (auto reset)
Protection degree IP20
Mass approx. 70 g Function
Dimensions 20 x 62 x 115 mm (0.8 x 2.4 x 4.5 in)
Data for application in connection see page 522 for entity parameters This Surge Protection Barrier is designed
with Ex-areas for use with K-System (KF modules).
EC-Type Examination Certificate PTB 02 ATEX 2044
Modules
CSA approval
safely protected against voltage surges of
Control drawing 116-0187 (cCSAus)
different origin (e. g. lightning stroke,
switching impulse, etc.). This is achieved
by diverting the transient current to
ground and limiting the signal line voltage
to a safe level for the duration of the
surge.
Field Mount
The end digits of the model designation
Modules
correspond to the protected terminals of
the respective KF module.
For additional information, refer to the
manual and www.pepperl-fuchs.com.
Note: Surge Protection Barriers must
always be connected to a solid and
effective ground and be at the same
equipotential level as the instrument it is
Modules
protecting. The ground system must
Plug-In
comply with all applicable regulations.
Accessories
Diagrams
Front view
Connection to earth
P-LB-2.C.2356
Removable terminals
blue, not protected
11/2010
2 (2)
3 (3)
908837 (US) / 208599 (EU)
5 (5)
6 (6)
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 519
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
P-LB-1.D.1234 Surge Protection Barrier
CSA approval
safely protected against voltage surges of
Control drawing 116-0187 (cCSAus)
different origin (e. g. lightning stroke,
switching impulse, etc.). This is achieved
by diverting the transient current to
ground and limiting the signal line voltage
to a safe level for the duration of the
surge.
Field Mount
Diagrams
Front view
Connection to earth
P-LB-1.D.1234
Removable terminal
blue, not protected
11/2010
1 (1)
2 (2)
908837 (US) / 208599 (EU)
3 (3)
4 (4)
520 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surge Protection Barrier P-LB-1.F.1236
Surge Protection
Rated current ≤ 250 mA
Leakage current ≤ 5 μA
• Analog or digital signal inputs
On-state voltage ≤ 45 V • Surge protection up to 10 kA
Ground insulation ≤ 500 V breakdown voltage • Protects leads 1, 2, 3 and 6 of
Ambient conditions KF modules
Ambient temperature -20 ... 60 °C (-4 ... 140 °F) • Uninterruptable operation
Mechanical specifications (auto reset)
Protection degree IP20
Mass approx. 70 g Function
Dimensions 20 x 62 x 115 mm (0.8 x 2.4 x 4.5 in)
Data for application in connection see page 522 for entity parameters This Surge Protection Barrier is designed
with Ex-areas for use with K-System (KF modules).
EC-Type Examination Certificate PTB 02 ATEX 2044
Modules
CSA approval
safely protected against voltage surges of
Control drawing 116-0187 (cCSAus)
different origin (e. g. lightning stroke,
switching impulse, etc.). This is achieved
by diverting the transient current to
ground and limiting the signal line voltage
to a safe level for the duration of the
surge.
Field Mount
The end digits of the model designation
Modules
correspond to the protected terminals of
the respective KF module.
For additional information, refer to the
manual and www.pepperl-fuchs.com.
Note: Surge Protection Barriers must
always be connected to a solid and
effective ground and be at the same
equipotential level as the instrument it is
Modules
protecting. The ground system must
Plug-In
comply with all applicable regulations.
Accessories
Diagrams
Front view
Connection to earth
P-LB-1.F.1236
Removable terminal
blue, not protected
11/2010
1 (1)
2 (2)
908837 (US) / 208599 (EU)
3 (3)
6 (6)
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 521
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Entity Parameters Surge Protection
K-LB-2.30 1, 2; 3, 4 30 250
K-LB-1.6 1, 2 6 250
K-LB-2.6 1, 2; 3, 4 6 250
K-LB-1.30G 1, 2 30 250
K-LB-2.30G 1, 2; 3, 4 30 250
K-LB-1.6G 1, 2 6 250
K-LB-2.6G 1, 2; 3, 4 6 250
FN-LB-I red, black 50 –
FP-LB-I red, black 50 –
FS-LB-I red, black 50 –
P-LB-1.A.13 1, 3 30 250
DIN Rail Mount
P-LB-2.A.1346 1, 3; 4, 6 30 250
Modules
P-LB-1.B.12 1, 2 30 250
P-LB-2.B.1245 1, 2; 4, 5 30 250
P-LB-1.C.123 1, 2, 3 30 250
P-LB-2.D.123456 1, 2, 3; 4, 5, 6 30 250
P-LB-1.E.23 2, 3 30 250
P-LB-2.C.2356 2, 3; 5, 6 30 250
P-LB-1.D.1234 1, 2, 3, 4 30 250
P-LB-1.F.1236 1, 2, 3, 6 30 250
Field Mount
Modules
K-LB-1.6 1, 2 40 250
Plug-In
K-LB-2.6 1, 2; 3, 4 40 250
K-LB-1.30G 1, 2 40 250
K-LB-2.30G 1, 2; 3, 4 40 250
K-LB-1.6G 1, 2 40 250
K-LB-2.6G 1, 2; 3, 4 40 250
FN-LB-I red, black 48 250
FP-LB-I red, black 48 250
Accessories
P-LB-2.C.2356 2, 3; 5, 6 40 250
P-LB-1.D.1234 1, 2, 3, 4 40 250
908837 (US) / 208599 (EU)
P-LB-1.F.1236 1, 2, 3, 6 40 250
Edition
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surge Protection Accessories
Insertion Strip
Label carrier
ZH-ES/LB ZH-Z.BT
Surge Protection
Label Carrier DIN rail NS 35/7.5
ZH-Z.BT 35 mm standard rail
to DIN EN 60715
Terminal Block
USLKG5
Function
DIN rail mount module grounding
Terminal block
USLKG5
Field Mount
ZH-Z.AR.85
Modules
Grounding Rail
ZH-Z.NLS-Cu3/10 Connection terminal
1
ZH-Z.AK16
15 mm (0.59'')
Function
Plug-in module grounding
Mounting block
Modules
2
Plug-In
ZH-Z.AB/SS
'')
57
(4.
6 mm
11
Accessories
ZH-Z.AK.85 ZH-Z.NLS-Cu3/10
Notes
When mounting on 35 mm DIN rail:
• installation height 15 mm: spacing roller ZH-Z.AR.85
• installation height 7.5 mm: no spacing roller necessary
Keep the drilling distance of 116 mm between center DIN rail and center
grounding bar.