= 0.30
ctor (CF = 1 - BF) = 0.70
CFM Ventilation
30.00 No = 6.00 = 180.00
0.33 Sqft x 54.32 = 17.92
Per Hour (CFM) = 1.00
543.15 x 1.00 x1/60 = 9.05
CFM Infiltration
x cfm/window = 0.00
Doors (People) x cfm/door = 0.00
x cfm/door = 0.00
x cfm/ft = 0.00
0.00
Supply CFM from Machine
oom Sensible Heat Factor =
oom Sensible Heat/Eff Room Total Heat =
Apparatus Dew Point (ADP)
=
= 52.00
Dehumidified Rise
- ADP) x CF = 16.10
FIED Cfm (AIR QUANTITY)
oom Sensible Heat
ed Rise x 1.08 = 547.59 CFM
= 257.37 L/s
AT CAPACITY
TR = 1.37
CFM =547.59
HEAT CAPACITY
= 1.44 TR ACCEPT THIS TR
577.57 cfm ACCEPT THIS CFM
VEN IN BLUE COLOR BOXES ONLY
PROJECT G+5 BUILDING HEAT LOAD FLOOR
LOCATION Laxmi nagar , New delhi. SPACE REFERENCE
CLIENT XYZ AREA ( SqFt)
CONSULTANT ABC Height (Ft)
Volume (CuFt)
Area or Sun Gain or Estimate for
Item Factor Btu/Hour W
Quantity Temp. Diff. Design Conditions
ROOM HEAT Ambient
ROOM SENSIBLE HEAT Room
Solar Gain - Glass Difference
Glass - N SqFt x F x 0.00
Glass - NE SqFt x F x 0.00
Glass - E SqFt x F x 0.00 By Pass Factor (BF)
Glass - SE SqFt x F x 0.00 Contact Factor (CF = 1 - BF)
Glass - S SqFt x F x 0.00 CFM Ven
Glass - SW SqFt x F x 0.00 CFM Per Person
Glass - W 164.00 SqFt x 40.00 F x 0.65 4,264.00 CFM Per SqFt
Glass - NW SqFt x F x 0.00 Air Change Per Hour (CFM)
Skylight SqFt x F x 0.00 CFM Cu.ft
Solar & Transmission Gain - Walls & Roof CFM Inf
Wall - N 0.00 SqFt x 0.00 F x 0.00 0.00 window
Wall - NE SqFt x F x 0.00 Revolving Doors (People)
Wall - E SqFt x F x 0.00 Open Doors
Wall - SE SqFt x F x 0.00 Crack (feet)
Wall - S 59.10 SqFt x 43.00 F x 0.48 1,219.82
Wall - SW SqFt x F x 0.00 Supply CFM f
Wall - W 0.00 SqFt x 0.00 F x 0.00 0.00 Effective Room Sensible Heat Facto
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff R
Roof 0.00 SqFt x 0.00 F x 0.00 0.00 Apparatus Dew
Transmission Gain - Except Walls & Roof Indicated ADP (F)
All Glass 40.00 SqFt x 35.00 F x 0.65 910.00 Selected ADP (F)
Partition 101.60 SqFt x 30.00 F x 0.32 975.36 Dehumidi
Ceiling 148.68 SqFt x 30.00 F x 0.16 713.66 (Room DB - ADP) x CF
Floor 148.68 SqFt x 30.00 F x 0.16 713.66 DEHUMIDIFIED Cfm (AIR QUANT
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat
Infiltration 76.00 CFM x 35.00 T.Diff x 1.08 2,872.80 Dehumidified Rise x 1.08
Outside Air 60.00 CFM x 35.00 T.Diff x 0.3x 1.08 680.40
Internal Heat
People 2.00 Nos. x 245.00 Btu/Hour Per Person 490.00 TOTAL HEAT CAPACITY
Lighting 148.68 SqFt x 0.40 W/SqFt x 3.41 204.57 2.48
Equipments 148.68 SqFt x 2.35 W/SqFt x 3.41 1,193.48
Power 0.00 kW/Hpx 0.00 0.00
Sub Total 14,237.76
Factor 5-10% 1,423.78
Effective Room Sensible Heat 15,661.54 1.00 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat
Infiltration 76.00 CFM x 9.00 Gr/Lb x 0.68 465.12 12,000.00
Outside Air 60.00 CFM x 9.00 Gr/Lb x BFx0.68 110.16
People 2.00 Nos. x 205.00 Btu/Hour Per Person 410.00
Sub Total 985.28
Factor 2.5 - 5% 49.26
Effective Room Latent Heat 1,034.54 2.00
EFFECTIVE ROOM TOTAL HEAT 16,696.08
OUTSIDE AIR HEAT
Sensible 60.00 CFM x 35.00 F(TD) x CF x 1.08 1,587.60 3.00
Latent 60.00 CFM x 9.00 Gr/Lb x CF x 0.68 257.04 4.00
OUTSIDE AIR TOTAL HEAT 1,844.64 Notes:
GRAND SUB-TOTAL HEAT 18,540.72
Factor 1 - 3% 556.22
GRAND TOTAL HEAT 19,096.94
TONS=GRAND TOTAL HEAT/12000 1.59
1st floor Right side DIMENSION
BEDROOM 10.5 14.16
148.68 Area 148.68
10.00
INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BO
1,486.80
Summer
DB (F) WB (F) RH (%) SH Gr/Lb
110.00 75.00 20.00 75.00
75.00 63.00 50.00 66.00
35.00 - - 9.00
= 0.30
ctor (CF = 1 - BF) = 0.70
CFM Ventilation
30.00 No = 2.00 = 60.00
0.33 Sqft x 148.68 = 49.06
Per Hour (CFM) = 1.00
1,486.80 x 1.00 x1/60 = 24.78
CFM Infiltration
x cfm/window = 0.00
Doors (People) x cfm/door = 0.00
x cfm/door = 0.00
x cfm/ft = 0.00
0.00
Supply CFM from Machine
oom Sensible Heat Factor =
oom Sensible Heat/Eff Room Total Heat =
Apparatus Dew Point (ADP)
=
= 54.15
Dehumidified Rise
- ADP) x CF = 14.60
FIED Cfm (AIR QUANTITY)
oom Sensible Heat
ed Rise x 1.08 = 993.59 CFM
= 466.99 L/s
AT CAPACITY
TR = 2.48 ACCEPT THIS TR
CFM =993.59
HEAT CAPACITY
= 1.59 TR
636.56 cfm ACCEPT THIS CFM
VEN IN BLUE COLOR BOXES ONLY
PROJECT G+5 BUILDING HEAT LOAD FLOOR
LOCATION Laxmi nagar , New delhi. SPACE REFERENCE
CLIENT XYZ AREA ( SqFt)
CONSULTANT ABC Height (Ft)
Volume (CuFt)
Area or Sun Gain or Estimate for
Item Factor Btu/Hour W
Quantity Temp. Diff. Design Conditions
ROOM HEAT Ambient
ROOM SENSIBLE HEAT Room
Solar Gain - Glass Difference
Glass - N SqFt x F x 0.00
Glass - NE SqFt x F x 0.00
Glass - E 40.00 SqFt x 12.00 F x 0.65 312.00 By Pass Factor (BF)
Glass - SE SqFt x F x 0.00 Contact Factor (CF = 1 - BF)
Glass - S SqFt x F x 0.00 CFM Ven
Glass - SW SqFt x F x 0.00 CFM Per Person
Glass - W SqFt x F x 0.00 CFM Per SqFt
Glass - NW SqFt x F x 0.00 Air Change Per Hour (CFM)
Skylight SqFt x F x 0.00 CFM Cu.ft
Solar & Transmission Gain - Walls & Roof CFM Inf
Wall - N 0.00 SqFt x 0.00 F x 0.00 0.00 window
Wall - NE SqFt x F x 0.00 Revolving Doors (People)
Wall - E 101.60 SqFt x 29.00 F x 0.48 1,414.27 Open Doors
Wall - SE SqFt x F x 0.00 Crack (feet)
Wall - S SqFt x F x 0.00
Wall - SW SqFt x F x 0.00 Supply CFM f
Wall - W 0.00 SqFt x 0.00 F x 0.00 0.00 Effective Room Sensible Heat Facto
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff R
Roof 0.00 SqFt x 0.00 F x 0.00 0.00 Apparatus Dew
Transmission Gain - Except Walls & Roof Indicated ADP (F)
All Glass 40.00 SqFt x 35.00 F x 0.65 910.00 Selected ADP (F)
Partition 161.60 SqFt x 30.00 F x 0.32 1,551.36 Dehumidi
Ceiling 172.19 SqFt x 30.00 F x 0.16 826.49 (Room DB - ADP) x CF
Floor 172.19 SqFt x 30.00 F x 0.16 826.49 DEHUMIDIFIED Cfm (AIR QUANT
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat
Infiltration 56.00 CFM x 35.00 T.Diff x 1.08 2,116.80 Dehumidified Rise x 1.08
Outside Air 120.00 CFM x 35.00 T.Diff x 0.3x 1.08 1,360.80
Internal Heat
People 4.00 Nos. x 245.00 Btu/Hour Per Person 980.00 TOTAL HEAT CAPACITY
Lighting 172.19 SqFt x 0.58 W/SqFt x 3.41 340.99 2.06
Equipments 172.19 SqFt x 2.61 W/SqFt x 3.41 1,534.41
Power 0.00 kW/Hpx 0.00 0.00
Sub Total 12,173.61
Factor 5-10% 1,217.36
Effective Room Sensible Heat 13,390.97 1.00 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat
Infiltration 56.00 CFM x 9.00 Gr/Lb x 0.68 342.72 12,000.00
Outside Air 120.00 CFM x 9.00 Gr/Lb x BFx0.68 220.32
People 4.00 Nos. x 205.00 Btu/Hour Per Person 820.00
Sub Total 1,383.04
Factor 2.5 - 5% 69.15
Effective Room Latent Heat 1,452.19 2.00
EFFECTIVE ROOM TOTAL HEAT 14,843.16
OUTSIDE AIR HEAT
Sensible 120.00 CFM x 35.00 F(TD) x CF x 1.08 3,175.20 3.00
Latent 120.00 CFM x 9.00 Gr/Lb x CF x 0.68 514.08 4.00
OUTSIDE AIR TOTAL HEAT 3,689.28 Notes:
GRAND SUB-TOTAL HEAT 18,532.44
Factor 1 - 3% 555.97
GRAND TOTAL HEAT 19,088.42
TONS=GRAND TOTAL HEAT/12000 1.59
1st floor Right side DIMENSION
MASTER BEDROOM 12.16 14.16
172.19 Area 172.1856
10.00
INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BO
1,721.86
Summer
DB (F) WB (F) RH (%) SH Gr/Lb
110.00 75.00 20.00 75.00
75.00 63.00 50.00 66.00
35.00 - - 9.00
= 0.30
ctor (CF = 1 - BF) = 0.70
CFM Ventilation
30.00 No = 4.00 = 120.00
0.33 Sqft x 172.19 = 56.82
Per Hour (CFM) = 1.00
1,721.86 x 1.00 x1/60 = 28.70
CFM Infiltration
x cfm/window = 0.00
Doors (People) x cfm/door = 0.00
x cfm/door = 0.00
x cfm/ft = 0.00
0.00
Supply CFM from Machine
oom Sensible Heat Factor =
oom Sensible Heat/Eff Room Total Heat =
Apparatus Dew Point (ADP)
=
= 53.50
Dehumidified Rise
- ADP) x CF = 15.05
FIED Cfm (AIR QUANTITY)
oom Sensible Heat
ed Rise x 1.08 = 823.86 CFM
= 387.21 L/s
AT CAPACITY
TR = 2.06 ACCEPT THIS TR
CFM =823.86
HEAT CAPACITY
= 1.59 TR
636.28 cfm ACCEPT THIS CFM
VEN IN BLUE COLOR BOXES ONLY
PROJECT G+5 BUILDING HEAT LOAD FLOOR 1st floor Right side
LOCATION Laxmi nagar , New delhi. SPACE REFERENCE HALL
CLIENT XYZ AREA ( SqFt) 160.97
CONSULTANT ABC Height (Ft) 10.00
Volume (CuFt) 1,609.65
Area or Sun Gain or Estimate for Summer
Item Factor Btu/Hour W
Quantity Temp. Diff. Design Conditions DB (F) WB (F) RH (%) SH Gr/Lb
ROOM HEAT Ambient 110.00 75.00 20.00 75.00
ROOM SENSIBLE HEAT Room 75.00 63.00 50.00 66.00
Solar Gain - Glass Difference 35.00 - - 9.00
Glass - N SqFt x F x 0.00
Glass - NE SqFt x F x 0.00
Glass - E SqFt x F x 0.00 By Pass Factor (BF) = 0.30
Glass - SE SqFt x F x 0.00 Contact Factor (CF = 1 - BF) = 0.70
Glass - S SqFt x F x 0.00 CFM Ventilation
Glass - SW SqFt x F x 0.00 CFM Per Person 30.00 No = 6.00 = 180.00
Glass - W 164.00 SqFt x 40.00 F x 0.65 4,264.00 CFM Per SqFt 0.33 Sqft x 160.97 = 53.12
Glass - NW SqFt x F x 0.00 Air Change Per Hour (CFM) = 1.00
Skylight SqFt x F x 0.00 CFM Cu.ft 1,609.65 x 1.00 x1/60 = 26.83
Solar & Transmission Gain - Walls & Roof CFM Infiltration
Wall - N 0.00 SqFt x 0.00 F x 0.00 0.00 window x cfm/window = 0.00
Wall - NE SqFt x F x 0.00 Revolving Doors (People) x cfm/door = 0.00
Wall - E SqFt x F x 0.00 Open Doors x cfm/door = 0.00
Wall - SE SqFt x F x 0.00 Crack (feet) x cfm/ft = 0.00
Wall - S SqFt x F x 0.00 0.00
Wall - SW SqFt x F x 0.00 Supply CFM from Machine
Wall - W 0.00 SqFt x 0.00 F x 0.00 0.00 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat =
Roof 0.00 SqFt x 0.00 F x 0.00 0.00 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (F) =
All Glass 40.00 SqFt x 35.00 F x 0.65 910.00 Selected ADP (F) = 53.25
Partition 218.30 SqFt x 30.00 F x 0.32 2,095.68 Dehumidified Rise
Ceiling 160.97 SqFt x 30.00 F x 0.16 772.63 (Room DB - ADP) x CF = 15.23
Floor 160.97 SqFt x 30.00 F x 0.16 772.63 DEHUMIDIFIED Cfm (AIR QUANTITY)
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat
Infiltration 76.00 CFM x 35.00 T.Diff x 1.08 2,872.80 Dehumidified Rise x 1.08 = 1,135.39 CFM
Outside Air 180.00 CFM x 35.00 T.Diff x 0.3x 1.08 2,041.20
Internal Heat = 533.63 L/s
People 6.00 Nos. x 245.00 Btu/Hour Per Person 1,470.00 TOTAL HEAT CAPACITY
Lighting 160.97 SqFt x 0.75 W/SqFt x 3.41 409.14 2.84 TR = 2.84
Equipments 160.97 SqFt x 2.48 W/SqFt x 3.41 1,363.94 CFM =1135.39
Power 0.00 kW/Hpx 0.00 0.00
Sub Total 16,972.03
Factor 5-10% 1,697.20
Effective Room Sensible Heat 18,669.23 1.00 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat = 2.26 TR
Infiltration 76.00 CFM x 9.00 Gr/Lb x 0.68 465.12 12,000.00 904.00 cfm
Outside Air 180.00 CFM x 9.00 Gr/Lb x BFx0.68 330.48
People 6.00 Nos. x 205.00 Btu/Hour Per Person 1,230.00
Sub Total 2,025.60
Factor 2.5 - 5% 101.28
Effective Room Latent Heat 2,126.88 2.00
EFFECTIVE ROOM TOTAL HEAT 20,796.11
OUTSIDE AIR HEAT
Sensible 180.00 CFM x 35.00 F(TD) x CF x 1.08 4,762.80 3.00
Latent 180.00 CFM x 9.00 Gr/Lb x CF x 0.68 771.12 4.00
OUTSIDE AIR TOTAL HEAT 5,533.92 Notes:
GRAND SUB-TOTAL HEAT 26,330.03
Factor 1 - 3% 789.90
GRAND TOTAL HEAT 27,119.93
TONS=GRAND TOTAL HEAT/12000 2.26
PROJECT G+5 BUILDING HEAT LOAD FLOOR
LOCATION Laxmi nagar , New delhi. SPACE REFERENCE
CLIENT XYZ AREA ( SqFt)
CONSULTANT ABC Height (Ft)
Volume (CuFt)
Area or Sun Gain or Estimate for
Item Factor Btu/Hour W
Quantity Temp. Diff. Design Conditions
ROOM HEAT Ambient
ROOM SENSIBLE HEAT Room
Solar Gain - Glass Difference
Glass - N 0.00 SqFt x 0.00 F x 0.00 0.00
Glass - NE SqFt x F x 0.00
Glass - E SqFt x F x 0.00 By Pass Factor (BF)
Glass - SE SqFt x F x 0.00 Contact Factor (CF = 1 - BF)
Glass - S SqFt x F x 0.00 CFM Ven
Glass - SW SqFt x F x 0.00 CFM Per Person
Glass - W SqFt x F x 0.00 CFM Per SqFt
Glass - NW SqFt x F x 0.00 Air Change Per Hour (CFM)
Skylight SqFt x F x 0.00 CFM Cu.ft
Solar & Transmission Gain - Walls & Roof CFM Inf
Wall - N 0.00 SqFt x 0.00 F x 0.00 0.00 window
Wall - NE SqFt x F x 0.00 Revolving Doors (People)
Wall - E SqFt x F x 0.00 Open Doors
Wall - SE SqFt x F x 0.00 Crack (feet)
Wall - S SqFt x F x 0.00
Wall - SW SqFt x F x 0.00 Supply CFM f
Wall - W 0.00 SqFt x 0.00 F x 0.00 0.00 Effective Room Sensible Heat Facto
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff R
Roof 0.00 SqFt x 0.00 F x 0.00 0.00 Apparatus Dew
Transmission Gain - Except Walls & Roof Indicated ADP (F)
All Glass 0.00 SqFt x 35.00 F x 0.65 0.00 Selected ADP (F)
Partition 156.60 SqFt x 30.00 F x 0.32 1,503.36 Dehumidi
Ceiling 61.20 SqFt x 30.00 F x 0.16 293.76 (Room DB - ADP) x CF
Floor 61.20 SqFt x 30.00 F x 0.16 293.76 DEHUMIDIFIED Cfm (AIR QUANT
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat
Infiltration 20.00 CFM x 35.00 T.Diff x 1.08 756.00 Dehumidified Rise x 1.08
Outside Air 180.00 CFM x 35.00 T.Diff x 0.3x 1.08 2,041.20
Internal Heat
People 6.00 Nos. x 245.00 Btu/Hour Per Person 1,470.00 TOTAL HEAT CAPACITY
Lighting 61.20 SqFt x 1.96 W/SqFt x 3.41 409.04 1.39
Equipments 61.20 SqFt x 9.80 W/SqFt x 3.41 2,046.00
Power 0.00 kW/Hpx 0.00 0.00
Sub Total 8,813.12
Factor 5-10% 881.31
Effective Room Sensible Heat 9,694.43 1.00 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat
Infiltration 20.00 CFM x 9.00 Gr/Lb x 0.68 122.40 12,000.00
Outside Air 180.00 CFM x 9.00 Gr/Lb x BFx0.68 330.48
People 6.00 Nos. x 205.00 Btu/Hour Per Person 1,230.00
Sub Total 1,682.88
Factor 2.5 - 5% 84.14
Effective Room Latent Heat 1,767.02 2.00
EFFECTIVE ROOM TOTAL HEAT 11,461.45
OUTSIDE AIR HEAT
Sensible 180.00 CFM x 35.00 F(TD) x CF x 1.08 4,762.80 3.00
Latent 180.00 CFM x 9.00 Gr/Lb x CF x 0.68 771.12 4.00
OUTSIDE AIR TOTAL HEAT 5,533.92 Notes:
GRAND SUB-TOTAL HEAT 16,995.37
Factor 1 - 3% 509.86
GRAND TOTAL HEAT 17,505.23
TONS=GRAND TOTAL HEAT/12000 1.46
1st floor Right side DIMENSION
DINING 7.5 8.16
61.20 Area 61.2
10.00
INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BOXES ON
612.00
Summer
DB (F) WB (F) RH (%) SH Gr/Lb
110.00 75.00 20.00 75.00
75.00 63.00 50.00 66.00
35.00 - - 9.00
= 0.30
ctor (CF = 1 - BF) = 0.70
CFM Ventilation
30.00 No = 6.00 = 180.00
0.33 Sqft x 61.20 = 20.20
Per Hour (CFM) = 1.00
612.00 x 1.00 x1/60 = 10.20
CFM Infiltration
x cfm/window = 0.00
Doors (People) x cfm/door = 0.00
x cfm/door = 0.00
x cfm/ft = 0.00
0.00
Supply CFM from Machine
oom Sensible Heat Factor =
oom Sensible Heat/Eff Room Total Heat =
Apparatus Dew Point (ADP)
=
= 52.00
Dehumidified Rise
- ADP) x CF = 16.10
FIED Cfm (AIR QUANTITY)
oom Sensible Heat
ed Rise x 1.08 = 557.54 CFM
= 262.04 L/s
AT CAPACITY
TR = 1.39
CFM =557.54
HEAT CAPACITY
= 1.46 TR ACCEPT THIS TR
583.51 cfm ACCEPT THIS CFM
VEN IN BLUE COLOR BOXES ONLY
PROJECT G+5 BUILDING HEAT LOAD FLOOR
LOCATION Laxmi nagar , New delhi. SPACE REFERENCE
CLIENT XYZ AREA ( SqFt)
CONSULTANT ABC Height (Ft)
Volume (CuFt)
Area or Sun Gain or Estimate for
Item Factor Btu/Hour W
Quantity Temp. Diff. Design Conditions
ROOM HEAT Ambient
ROOM SENSIBLE HEAT Room
Solar Gain - Glass Difference
Glass - N SqFt x F x 0.00
Glass - NE SqFt x F x 0.00
Glass - E SqFt x F x 0.00 By Pass Factor (BF)
Glass - SE SqFt x F x 0.00 Contact Factor (CF = 1 - BF)
Glass - S SqFt x F x 0.00 CFM Ven
Glass - SW SqFt x F x 0.00 CFM Per Person
Glass - W 164.00 SqFt x 20.00 F x 0.65 2,132.00 CFM Per SqFt
Glass - NW SqFt x F x 0.00 Air Change Per Hour (CFM)
Skylight SqFt x F x 0.00 CFM Cu.ft
Solar & Transmission Gain - Walls & Roof CFM Inf
Wall - N 105.00 SqFt x 27.00 F x 0.48 1,360.80 window
Wall - NE SqFt x F x 0.00 Revolving Doors (People)
Wall - E SqFt x F x 0.00 Open Doors
Wall - SE SqFt x F x 0.00 Crack (feet)
Wall - S 0.00 SqFt x 0.00 F x 0.00 0.00
Wall - SW SqFt x F x 0.00 Supply CFM f
Wall - W 0.00 SqFt x 0.00 F x 0.00 0.00 Effective Room Sensible Heat Facto
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff R
Roof 0.00 SqFt x 0.00 F x 0.00 0.00 Apparatus Dew
Transmission Gain - Except Walls & Roof Indicated ADP (F)
All Glass 20.00 SqFt x 35.00 F x 0.65 455.00 Selected ADP (F)
Partition 181.60 SqFt x 30.00 F x 0.32 1,743.36 Dehumidi
Ceiling 148.68 SqFt x 30.00 F x 0.16 713.66 (Room DB - ADP) x CF
Floor 148.68 SqFt x 30.00 F x 0.16 713.66 DEHUMIDIFIED Cfm (AIR QUANT
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat
Infiltration 38.00 CFM x 35.00 T.Diff x 1.08 1,436.40 Dehumidified Rise x 1.08
Outside Air 60.00 CFM x 35.00 T.Diff x 0.3x 1.08 680.40
Internal Heat
People 2.00 Nos. x 245.00 Btu/Hour Per Person 490.00 TOTAL HEAT CAPACITY
Lighting 148.68 SqFt x 0.40 W/SqFt x 3.41 204.57 1.95
Equipments 148.68 SqFt x 2.35 W/SqFt x 3.41 1,193.48
Power 0.00 kW/Hpx 0.00 0.00
Sub Total 11,123.34
Factor 5-10% 1,112.33
Effective Room Sensible Heat 12,235.67 1.00 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat
Infiltration 38.00 CFM x 9.00 Gr/Lb x 0.68 232.56 12,000.00
Outside Air 60.00 CFM x 9.00 Gr/Lb x BFx0.68 110.16
People 2.00 Nos. x 205.00 Btu/Hour Per Person 410.00
Sub Total 752.72
Factor 2.5 - 5% 37.64
Effective Room Latent Heat 790.36 2.00
EFFECTIVE ROOM TOTAL HEAT 13,026.03
OUTSIDE AIR HEAT
Sensible 60.00 CFM x 35.00 F(TD) x CF x 1.08 1,587.60 3.00
Latent 60.00 CFM x 9.00 Gr/Lb x CF x 0.68 257.04 4.00
OUTSIDE AIR TOTAL HEAT 1,844.64 Notes:
GRAND SUB-TOTAL HEAT 14,870.67
Factor 1 - 3% 446.12
GRAND TOTAL HEAT 15,316.79
TONS=GRAND TOTAL HEAT/12000 1.28
1st floor Right side DIMENSION
BEDROOM 10.5 14.16
148.68 Area 148.68
10.00
INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BO
1,486.80
Summer
DB (F) WB (F) RH (%) SH Gr/Lb
110.00 75.00 20.00 75.00
75.00 63.00 50.00 66.00
35.00 - - 9.00
= 0.30
ctor (CF = 1 - BF) = 0.70
CFM Ventilation
30.00 No = 2.00 = 60.00
0.33 Sqft x 148.68 = 49.06
Per Hour (CFM) = 1.00
1,486.80 x 1.00 x1/60 = 24.78
CFM Infiltration
x cfm/window = 0.00
Doors (People) x cfm/door = 0.00
x cfm/door = 0.00
x cfm/ft = 0.00
0.00
Supply CFM from Machine
oom Sensible Heat Factor =
oom Sensible Heat/Eff Room Total Heat =
Apparatus Dew Point (ADP)
=
= 54.30
Dehumidified Rise
- ADP) x CF = 14.49
FIED Cfm (AIR QUANTITY)
oom Sensible Heat
ed Rise x 1.08 = 781.87 CFM
= 367.48 L/s
AT CAPACITY
TR = 1.95 ACCEPT THIS TR
CFM =781.87
HEAT CAPACITY
= 1.28 TR
510.56 cfm ACCEPT THIS CFM
VEN IN BLUE COLOR BOXES ONLY
PROJECT G+5 BUILDING HEAT LOAD FLOOR
LOCATION Laxmi nagar , New delhi. SPACE REFERENCE
CLIENT XYZ AREA ( SqFt)
CONSULTANT ABC Height (Ft)
Volume (CuFt)
Area or Sun Gain or Estimate for
Item Factor Btu/Hour W
Quantity Temp. Diff. Design Conditions
ROOM HEAT Ambient
ROOM SENSIBLE HEAT Room
Solar Gain - Glass Difference
Glass - N SqFt x F x 0.00
Glass - NE SqFt x F x 0.00
Glass - E 20.00 SqFt x 12.00 F x 0.65 156.00 By Pass Factor (BF)
Glass - SE SqFt x F x 0.00 Contact Factor (CF = 1 - BF)
Glass - S SqFt x F x 0.00 CFM Ven
Glass - SW SqFt x F x 0.00 CFM Per Person
Glass - W SqFt x F x 0.00 CFM Per SqFt
Glass - NW SqFt x F x 0.00 Air Change Per Hour (CFM)
Skylight SqFt x F x 0.00 CFM Cu.ft
Solar & Transmission Gain - Walls & Roof CFM Inf
Wall - N 0.00 SqFt x 0.00 F x 0.00 0.00 window
Wall - NE SqFt x F x 0.00 Revolving Doors (People)
Wall - E 86.60 SqFt x 29.00 F x 0.48 1,205.47 Open Doors
Wall - SE SqFt x F x 0.00 Crack (feet)
Wall - S SqFt x F x 0.00
Wall - SW SqFt x F x 0.00 Supply CFM f
Wall - W 0.00 SqFt x 0.00 F x 0.00 0.00 Effective Room Sensible Heat Facto
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff R
Roof 0.00 SqFt x 0.00 F x 0.00 0.00 Apparatus Dew
Transmission Gain - Except Walls & Roof Indicated ADP (F)
All Glass 20.00 SqFt x 35.00 F x 0.65 455.00 Selected ADP (F)
Partition 201.60 SqFt x 30.00 F x 0.32 1,935.36 Dehumidi
Ceiling 129.63 SqFt x 30.00 F x 0.16 622.20 (Room DB - ADP) x CF
Floor 129.63 SqFt x 30.00 F x 0.16 622.20 DEHUMIDIFIED Cfm (AIR QUANT
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat
Infiltration 38.00 CFM x 35.00 T.Diff x 1.08 1,436.40 Dehumidified Rise x 1.08
Outside Air 120.00 CFM x 35.00 T.Diff x 0.3x 1.08 1,360.80
Internal Heat
People 4.00 Nos. x 245.00 Btu/Hour Per Person 980.00 TOTAL HEAT CAPACITY
Lighting 129.63 SqFt x 0.77 W/SqFt x 3.41 340.99 1.78
Equipments 129.63 SqFt x 3.47 W/SqFt x 3.41 1,534.44
Power 0.00 kW/Hpx 0.00 0.00
Sub Total 10,648.86
Factor 5-10% 1,064.89
Effective Room Sensible Heat 11,713.75 1.00 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat
Infiltration 38.00 CFM x 9.00 Gr/Lb x 0.68 232.56 12,000.00
Outside Air 120.00 CFM x 9.00 Gr/Lb x BFx0.68 220.32
People 4.00 Nos. x 205.00 Btu/Hour Per Person 820.00
Sub Total 1,272.88
Factor 2.5 - 5% 63.64
Effective Room Latent Heat 1,336.52 2.00
EFFECTIVE ROOM TOTAL HEAT 13,050.27
OUTSIDE AIR HEAT
Sensible 120.00 CFM x 35.00 F(TD) x CF x 1.08 3,175.20 3.00
Latent 120.00 CFM x 9.00 Gr/Lb x CF x 0.68 514.08 4.00
OUTSIDE AIR TOTAL HEAT 3,689.28 Notes:
GRAND SUB-TOTAL HEAT 16,739.55
Factor 1 - 3% 502.19
GRAND TOTAL HEAT 17,241.74
TONS=GRAND TOTAL HEAT/12000 1.44
1st floor Right side DIMENSION
MASTER BEDROOM 12.16 10.66
129.63 Area 129.6256
10.00
INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BO
1,296.26
Summer
DB (F) WB (F) RH (%) SH Gr/Lb
110.00 75.00 20.00 75.00
75.00 63.00 50.00 66.00
35.00 - - 9.00
= 0.30
ctor (CF = 1 - BF) = 0.70
CFM Ventilation
30.00 No = 4.00 = 120.00
0.33 Sqft x 129.63 = 42.78
Per Hour (CFM) = 1.00
1,296.26 x 1.00 x1/60 = 21.60
CFM Infiltration
x cfm/window = 0.00
Doors (People) x cfm/door = 0.00
x cfm/door = 0.00
x cfm/ft = 0.00
0.00
Supply CFM from Machine
oom Sensible Heat Factor =
oom Sensible Heat/Eff Room Total Heat =
Apparatus Dew Point (ADP)
=
= 53.25
Dehumidified Rise
- ADP) x CF = 15.23
FIED Cfm (AIR QUANTITY)
oom Sensible Heat
ed Rise x 1.08 = 712.39 CFM
= 334.82 L/s
AT CAPACITY
TR = 1.78 ACCEPT THIS TR
CFM =712.39
HEAT CAPACITY
= 1.44 TR
574.72 cfm ACCEPT THIS CFM
VEN IN BLUE COLOR BOXES ONLY
G+5 BUILDING HEAT LOAD 1ST FLO
TOTAL TR 7.31 TR
TOTAL CFM 2333.83 CFM
LEFT TOP
RIGHT TOP
TOTAL TR 7.88 TR
TOTAL CFM 2365.39 CFM
LEFT BOTTOM
RIGHT BOTTOM