Professional Documents
Culture Documents
Engineering
Slide # 1
ELE B7
Slide # 2
Transmission lines- CONSTRUCTION ELE B7
Slide # 3
Transmission lines- VOLTAGE LEVELS ELE B7
ACSR
Slide # 5
Transmission Line- PARAMETERS ELE B7
Slide # 6
Transmission Line Parameters-RESISTANCE
ELE B7
Slide # 7
Transmission Line Parameters-RESISTANCE
ELE B7
Example:
A three-phase overhead transmission line is designed to deliver 190.5MVA at 220kV over a
distance of 63km, such that the total transmission line loss is not to exceed 2.5% of the rated
line MVA. Given the resistivity of the conductor material to be 2.84*10-8 ohm-meter.
Determine the required conductor diameter and the conductor size. Neglecting power loss
due to corona and insulator leakage and other reactive loss.
Solution:
The total transmission line loss is:
* l 2.84 10 8 * 63 10 3
PLoss 190.5 * 2.5% 4.7625 MW A
R 6.35
190.5( MVA ) A 2.81764 10 4 m 2
IL 500 A
3 ( 220 kV )
d 1.894 cm 0.7456 in 556 ,000cmil
PLoss 3 * I L 2 * R
1 in = 1000 mils
4.7625 MW 1 cmils = sq mil
R 2
6.35
3( 500 ) Slide # 8
Transmission Line Parameters-INDUCTANCE
ELE B7
Slide # 9
Transmission Line Parameters-INDUCTANCE
ELE B7
• Transposition:
When the conductors of a three-phase line are not spaced
equilaterally, the flux linkages and the inductance of each phase are
not the same. A different inductance in each phase results in
unbalance circuit.
Balance of the three phases can be restored by exchanging the
positions of the conductors at regular intervals along the line as shown
below
Pos.1 Cond. a Cond. c Cond. b
Slide # 12
Transmission Line Parameters-CAPACITANCE
ELE B7
where, rd
3
Dsb 2 d
ε0=8.85×10-12 d
Dsb 1.091 r d
4 3
r is the equivalent radius of the conductor
d d
Slide # 13
Transmission Line Parameters-CAPACITANCE
ELE B7
EXAMPLE:
A 400kV, 60Hz, three phase with bundled conductor line, two sub-conductors per-phase
as shown in the Figure. The center to center distance between adjacent phases is 12 m and
distance between sub-conductors is 45 cm. The radius of each sub-conductor is 1.6 cm.
Find the capacitance per phase per km.
D31
D12 D23
a a’ b b’ c c’
d d d
SOLUTION:
Series impedance
z r j x / mi Z z R j X
Shunt admittance
y g j b S / mi Y y G j B S
– –
Slide # 17
Two-Port Network- ABCD parameters ELE B7
ABCD parameters
IS IR
+ +
Two-port VR
VS
–
Network –
Slide # 18
ABCD Parameters – Example 1 ELE B7
IS IR
– –
KVL equation:
Y VR YZ
VS VR Z I R VS 1 VR Z I R ( 2)
2 2
KCL equation:
Y Vs Y VR Y 2Z YZ
IS IR
I S Y
VR 1 I R (3)
2 2 4 2
By inspection,
YZ YZ
A D 1 pu, B Z , C Y 1 S
2 4
Slide # 19
ABCD Parameters ELE B7
Series impedance Z: A D 1, B Z , C 0
Shunt admittance Y: A D 1, B 0, C Y S
– – – –
Slide # 20
ABCD Parameters – Example 2 ELE B7
VS 345 3
VR 222.5 0.69 kV
A 0.895110.69
VR LL 385.4 kV (12% above nominal)
Slide # 21
The long transmission line ELE B7
Slide # 22
The long transmission line ELE B7
Slide # 25
Loadability ELE B7
Slide # 26
Temperature / sag limitations ELE B7
Operating range
0 .95 V R 1 .05 pu and 0 .95 V S 1 .05 pu
Slide # 28
Stability considerations ELE B7
Real Power
ignoring distributed effects:
V RV S
P PS PR sin , V V
X s R