You are on page 1of 3

Learn to Do It Right the First Time:

Guidelines
for Designing
Water Softeners
By Robert Slovak

Summary: Water softener design and setup for regeneration, and of resin produce a bed depth of just un-
can be a confusing thing to learn regardless • It takes up to three hours (depend- der 26 inches (65 cm), which creates the
of the application. Here are basic guidelines ing on temperature) to make a saturated 24" minimum resin bed depth require-
for engineers and technicians to study to gain salt solution in the brine tank. ment of the resin manufacturer. Also be
a fundamental understanding of this process. aware that if the service flow is too low,
Learn this–Resin volume vs. the water can “channel” through the

T
he following is an introductory service flow rate resin bed only using a fraction of the
article offering practical advice The volume of cation resin required resin’s capacity. Use a lower flow limit of
on sizing and setting up water for a given flow rate can be determined no less than 1 gpm/ft3 (8 m3 /h/m3 ).
softeners for residential, commercial and two ways: 1) By the volume of resin
non-critical industrial applications. There which concerns contact time, and 2) by Learn this–Resin capacity vs.
are significant variations and details not the resin bed (the tank) cross section area salt dose
within the scope of this presentation but that concerns pressure drop in the resin The resin capacity for hardness, or
that deserve further investigation such bed. See Table 1 to determine the cross amount of hardness that can be re-
as alternate methods of brining and re- section area of the most popular size moved by cation resin, depends on how
generation cycle programming. Feel tanks. much salt is used (dosage) to regenerate
free to surf the WC&P “archives” at By contact time—Use 5 gallons per each liter or cubic foot of cation resin.
www.wcponline.com for more on these minute per cubic foot (gpm/ft3 ), or 42 The normal range is 6 pounds of salt per
subjects. Meanwhile, read on. cubic meters per hour per cubic meter cubic foot (lbs salt/ft3 or lbs/ft3 ) of
(m3 /h/m3), for continuous flow and 7.5 resin—about 100 grams salt per liter
STEP 1: Select the control valve you gpm/ft3 (60 m3 /h/m3 ) for peak flow. To (g salt/L or g/L) of resin—to 15 lbs salt/
want to use based on the service flow achieve low hardness leakage as re- ft3 (about 240 g salt/L) for standard mesh
requirements of the application—The quired in applications like boiler water resin. The capacity for each salt dosage
first objective is to select a valve that treatment, the flow rate should be lim- can be approximated in the following:
offers acceptable pressure drop from the ited to 3 gpm/ft3 . Low limit salt dosage—6 lbs salt/ft3
inlet to the outlet of the softener at the By resin bed area— Use 10 gpm per (about 100 g salt/L) resin gives hard-
service flow required for the application. square foot (ft2 ), or 25 m3/h per square ness removal capacity of approximately
Use a maximum service flow pressure meter (m2 ), for continuous flow and 15 21,000 grains/ft3 —48 grams of hardness
drop guideline of 15 pounds per square gpm/ft2 (37 m3/hr/m 2 ) for peak flow. as calcium carbonate (CaCO3 ) per liter
inch (psi)—1 bar—for the valve alone. To assure low hardness leakage, limit [g(CaCO 3)/L] or 0.96 equivalents per li-
the area flow to 8 gpm/ft2 . ter (eq/L).
STEP 2: Determine volume of cat- For example, assume the service Medium salt dosage—9 lbs salt/ft3
ion resin required—The volume of cat- flow is 15 gpm—56.8 liters per minute (about 150 g salt/L) resin gives hard-
ion resin is generally determined by (L/min). Based on the guideline above, ness removal capacity of approximately
four things: the recommended resin volume is 15 26,000 grains/ft 3 —60 g(CaCO3 )/L or
a. The service flow rate, gpm/5 gpm/ft 3 = 3 ft 3. The cross sec- 1.19 eq/L.
b. Hardness of the water, tion area guideline recommends a resin High salt dosage—12 lbs/ft3 (about 200
c. The volume of water to be bed area of 15 gpm/10 gpm/ft2 = 1.5 ft2 , g salt/L) resin gives hardness removal
treated, and which corresponds to a 16-inch ( ") tank capacity of approximately 29,000 grains/
d. The number of times a day the (1.4 ft2 ) and a resin volume of 4.6 ft3 . ft3 —66 g(CaCO3 )/L or 1.33 eq/L).
softener can be regenerated (i.e., valves You have the choice of using a 16" tank Maximum limit salt dosage —15 lbs
with flow meters allow multiple regen- with 3 ft3 (84.9 L) or use a normal resin salt/ft3 (about 250 g salt/L) resin gives
eration per day). Usually three times is volume of 4.6 ft 3 (130.2 L) for added ca- hardness removal capacity of approxi-
the practical maximum number of re- pacity to meet future expansion or in- mately 31,000 grains/ft3—71 g(CaCO 3)/
generations per day because: crease in hardness. L or 1.42 eq/L.
• It typically takes up to two hours Bear in mind, the 16" tank with 3 ft3 Notice that even though the salt

12 Water Conditioning & Purification MARCH 2004


Table 1. Water softener sizing and performance chart
Minimum salt Medium salt High salt Maximum salt
dosage dosage dosage dosage
6 lbs/ft3 9 lbs/ft3 12 lbs/ft 3 approx. 15 lbs/ft3
(100 g/L) (150 g/L) (200 g/L) (250 g/L)
Backwash 2
Resin @60F & 77F Service Peak Regen. System Regen. System Regen. System Regen. System
Tank Tank vol.1 @15C &25C flow flow salt capacity3 salt capacity3 salt capacity3 salt capacity3
size area ft3 gpm60 / gpm77 gpm gpm lbs grains lbs grains lbs grains lbs grains
D” x H” ft2 (m 2) (liters) (lpm15 / lpm25) (lpm) (lpm) (kg) (kg) (kg) (kg) (kg) (kg) (kg) (kg)
6 x 35 0.19 0.4 1.0/1.3 2.0 3.0 2.4 8,400 3.6 10,400 4.8 11,600 6.0 12,400
(0.018) (10) (3.6/4.9) (7.6) (11.4) (1.0) (0.48) (1.5) (0.60) (2.0) (0.66) (2.5) (0.71)
7 x 44 0.27 0.6 1.3/1.8 3.0 4.5 3.6 12,600 5.4 15,600 7.2 17,400 9.0 18,600
(0.025) (15) (5.1/6.8) (11) (16.5) (1.5) (0.72) (2.3) (0.90) (3.0) (0.99) (3.8) (1.07)
8 x 44 0.34 0.8 1.7/2.3 4.0 6.0 4.8 16,800 7.3 20.800 9.6 23,200 12.0 24,800
(0.032) (20) (6.5/8.7) (15) (22.5) (2.0) (0.96) (3.0) (1.20) (4.0) (1.32) (5.0) (1.42)
9 x 48 0.44 1 2.2/3.0 5.0 7.5 6.0 21,000 9.0 26,000 11 29,000 15.0 31,000
(0.041) (25) (8.3/11.2) (19) (28.5) (2.5) (1.20) (3.8) (1.50) (5.0) (1.65) (6.3) (1.78)
10 x 54 0.54 1.3 2.7/3.7 6.5 9.8 7.8 27,300 11.7 33,800 15.6 37,700 19.5 40,300
(0.051) (35) (10.4/13.9) (30) (45.0) (3.5) (1.68) (5.3) (2.10) (7.0) (2.31) (8.8) (2.49)
12 x 52 0.78 2.0 3.9/5.3 10.0 (15) 12.0 42,000 18.0 52,000 24.0 58,000 30.0 62,000
(0.073) (55) (14.8/19.9) (38) (57) (5.5) (2.64) (8.3) (3.30) (11.0) (3.63) (13.8) (3.91)
13 x 54 0.91 2.2 4.6/6.1 11.0 16.5 13.2 46,200 19.8 57,000 26.4 63,800 33.0 68,200
(0.085) (60) (17.3/23.2) (44) (66) (6.0) (2.88) (9.8) (3.60) (13.0) (3.96) (16.3) (4.26)
14 x 65 1.07 3.0 5.4/7.2 15.0 22.5 18.0 63,000 27.0 78,000 36.0 87,000 45.0 93,000
(0.100) (85) (20.3/27.3) (57) (85.5) (8.5) (4.08) (15.0) (5.10) (20.0) (5.61) (25.0) (6.04)
16 x 65 1.41 4.0 7.0/9.5 20.0 30 24 84,000 36.0 104.000 48.0 116,000 60.0 124,000
(0.131) (115) (26.6/35.8) (76) (114) (11.5) (5.52) (19.5) (6.90) (26.0) (7.59) (32.5) (8.17)
18 x 65 1.76 5.0 8.8/11.8 25.0 37.5 30 105,000 45.0 130,000 60.0 145,000 75.0 155,000
(0.164) (140) (33.3/44.8) (95) (143) (14.0) (6.72) (24.8) (8.40) (33.0) (9.24) (41.3) (9.94)
21 x 62 2.40 6.5 10.8/14.6 32.5 48.8 39 136,500 58.5 169,000 78.0 188,500 97.5 201,500
(0.223) (185) (41.0/55.1) (123) (185) (18.5) (8.88) (30.0) (11.10) (40.0) (12.21) (50.0) (13.14)
1. The listed resin volumes are nominal values and are subject to change based on user preference and experience.
2. The water temperature determines the backwash flow rate. Colder water temperature requires less backwash flow. Refer to water viscosity charts for other temperatures.
3. These are approximate capacities based on the resin volume. Small inconsistencies may result from rounding off and unit conversions.
SOURCE: AquaCorp. Ltda., Rio de Janeiro, Brazil (aquacorp@aquacorp.com.br)

dosage more than doubles, the hardness foot of resin has a capacity of 26,000 one-third the amount of resin is re-
removal capacity doesn’t. The higher grains (each liter of resin can remove quired or 3 ft 3 (85 L) for this example.
the salt dosage, the lower the salt effi- 0.060 kg hardness). If you are limited to But let’s check if this reduced vol-
ciency. only one regeneration per day (as with ume of resin can meet the service flow
Bear in mind, the above capacity val- a timer-controlled valve), then a volume rate requirement of 15 gpm. Referring
ues are only approximate. Consult the of 260,000/26,000 = 10 ft3 (about 283 L) to “Resin volume vs. service flow rate”
specifications from your resin supplier of resin is required. This typically re- section, 15 gpm (57 L/min or 1 pm) ser-
for more accurate capacity specifications. quires a 24" × 72" tank. vice flow requires at least 3 ft3 of resin.
Consider multiple regenerations—It’s The flow rate is compatible with the
Learn this–Resin volume vs. important to understand that multiple resin volume required for the hardness
volume of treated water daily softener regenerations can reduce capacity. Now, instead of a 24" tank with
To determine the volume of resin system size and cost. If the application is 9 ft3 of resin, the system can be reduced
by volume of water treated and hard- suited for multiple regenerations per day to:
ness, start by estimating the maximum [you need an alternating multiple-tank 1. A twin-metered alternating soft-
total grains (or kilograms) of hardness system or a cistern (reservoir) that can ener using 16" tanks with 3 ft3 of resin
that must be removed each day. supply treated water for the customer (each regenerates three times every two
For example, assume the water has during regeneration], then a more cost days—about every 16 hours) where con-
a hardness—as (CaCO3 )—of 13 grains/ effective softener system can be de- tinuous direct flow of softened water is
gallon [222 milligrams per liter (mg/L), signed. This is an especially good strat- required
calculated by multiplying 13 grains by egy where cisterns are commonly used 2. A single-metered softener using
17.1]—and that 20,000 gallons (75.8 m3 ) to store treated water before the points a 16” tank with 3 ft3 of resin (which re-
of water must be treated. The total hard- of use (as in Latin America). Consider generates three times per day) where a
ness is 13 grains/gallon × 20,000 gallons using three regenerations per day cistern of treated water is available to
= 260,000 grains—16.9 kilograms (kg)— (roughly every eight hours for continu- supply the customer with a continuous
of hardness per day. ous flow) for the example above. Then, supply of softened water.
At the medium salt dose, each cubic to meet the capacity requirement, only

MARCH 2004 Water Conditioning & Purification 13


STEP 3: Determine the tank size— Backwash–Downflow Brine/Slow Rinse– 23 minutes. The total brine and slow
Generally, the tank is filled to ½ to 2/3 Fast Rinse–Salt Tank Refill–Return to Ser- rinse cycle should be 3 × 23 minutes = 69
of the total tank volume. The depth of vice minutes.
cation resin should be at least 24” (0.6 Fast rinse function—The fast rinse
m) in smaller tanks and 30” (0.75 m) in Learn this–Softener flows through the backwash flow con-
larger tanks. The tank should be tall regeneration function times trol so its flow rate is the same. For most
enough so the resin can expand to at Backwash function—Eight to 15 min- applications, the fast rinse time should
least 50 percent of its normal depth into utes is recommended depending on the be 6 to 12 minutes depending on the vol-
the void space. Refer to the accompany- amount of particulate matter (sediment) ume of resin and the application. For
ing chart for standard tank sizes. in the water supply and water scarcity. instance, most domestic and commer-
STEP 4: Determine the backwash If iron is present, use the upper range. cial applications can use the lower range
flow rate— The backwash segment of The backwash flow is regulated by a while reverse osmosis (RO) and deion-
the regeneration removes dirt and de- control orifice that restricts the drain ization (DI) pretreatment and boiler
bris from the resin and is determined by flow to the specified flow rate. feed and industrial process applications
two things: Downflow brine function—It’s impor- should have longer rinse times.
a. Diameter of the tank —Refer to the tant to understand that the downflow Salt tank refill function—During this
accompanying design chart (see Table 1 ) brine function is only the first part of cycle, a controlled stream of water flows
for cross section area. the complete “downflow brine/slow into the salt tank to make up a saturated
b. Temperature of the water—This de- rinse” task. The control valve remains brine solution for the next regeneration.
termines the water viscosity as an in- in the same position for the entire func- The salt tank refill time should be based
verse relationship. As water tempera- tion. During this first part, saturated salt on the fact that 1 gallon of fresh water
ture decreases, it becomes more viscous brine solution is sucked (“educted” or dissolves approximately 3 lbs (1 L dis-
(thicker) and will cause greater expan- “drawn”) from the brine tank, mixes solves 360 g) of salt.
sion of the resin bed during backwash. with the venturi injector water stream For example, consider the situation
(to a concentration of about 10 to 13 per- above. The amount of salt required for
Learn this–Backwash flow cent), and flows through the resin bed the medium salt setting is 42.9 lbs. (19.5
rate vs. water temperature to regenerate it (or chemically displace kg). The manual says the salt tank refill
This requirement of correct softener the hardness removed). The NaCl con- flow rate is 0.5 gpm (2 L/min). The vol-
design may be the most overlooked fac- tent of saturated brine is 2.7 lbs/gallon ume of water required to dissolve 42.9
tor, especially in warm water regions (300 g/L). The brine function time is de- lbs of salt is therefore 14.3 gallons (54.1
such as Latin America. The flow must be termined by: L) and the time is 28.6 minutes.
sufficient to expand the bed at least 50 1. The amount of salt required to
percent. Use the following guidelines regenerate the resin bed (refer to accom- Conclusion
but, for exact backwash flow require- panying design chart) The softener design guidelines out-
ments, refer to the backwash require- 2. The flow rate that the injector lined in this article and accompanying
ments vs. water viscosity chart from educts brine into the resin bed (consult chart are intended to provide a base of
your resin supplier. the control valve manual for the this information for general purpose soft-
• 4.2 gpm/ft2 (10.3 m3/h/m2 ) back- specification) ening applications such as domestic use,
wash flow at 10°C (50°F) For example, assume you have commercial and institutional washing
• 5.0 gpm/ft2 (12.3 m3/h/m2 ) back- specified the size of the softener to be a and laundry, non-critical industrial pro-
wash flow at 15°C (59°F) 16” × 65” tank with 4.6 ft3 (130 L) of cesses, low pressure boilers, cooling
• 5.5 gpm/ft2 (13.5 m 3 /m2) back- resin. You decide to choose the medium towers, and RO and DI pretreatment.
wash flow at 20°C (68°F) salt setting of 9 lbs/ft3 (150 g/L), refer- More demanding applications like high-
• 6.7 gpm/ft2 (16.4 m3/h/m2 ) back- ring to the accompanying design chart. pressure boilers, medical autoclaves and
wash flow at 25°C (77°F) The amount of salt required is 42.9 lbs water sources containing problem con-
(19.5 kg) and the amount of salt brine taminants like iron and manganese re-
STEP 5: Determine the brine injec- containing this is 15.9 gallons (60 L) satu- quire additional special considerations.
tor size—The injector creates suction for rated brine. The control valve manual Thus, you should consult your other
the salt solution. During regeneration, says that the injector for a 16” diameter professional sources for specific appli-
water flows through the injector ven- tank educts the saturated salt brine at a cation guidelines.
turi and creates a vacuum to pull salt rate of 0.7 gpm (2.6 L/min). Therefore,
brine from the salt tank. The injector is the downflow brine time required is 22.7 About the author
primarily determined by the diameter minutes. 6 Robert Slovak is president of Aroman Inc.,
of the tank. The proper injector selec- Slow rinse function— As stated a water treatment consulting company in
tion is found in the manual of the con- above, the slow rinse cycle is actually an Incline Village, Nev., and currently serves
trol valve you’re using. extension of the “downflow brine/slow as a water consultant and manufacturer’s
rinse” function”—but with no salt brine representative in Brazil for products im-
STEP 6: Determine the regeneration being educted. The continued water flow ported by AquaCorp LTDA in Rio de Janeiro.
function times—The regeneration cycle through the injector provides this slow He is also a member of the technical advisory
consists of a sequence of functions that rinse. The recommended guideline is to committee of Agua Latinoamérica, a sister
correspond to control valve “positions.” have the entire downflow brine and slow publication to WC&P, and a former member
For most customers who only have to rinse cycle be three times as long as the of a similar WC&P committee. He and his
remove hardness, the following se- brine cycle. brother, Jack, were founders of Water Fac-
quence of regeneration functions is rec- For example, consider the instance tory Systems, now a division of CUNO Inc.
ommended: above. The brine time is approximately Slovak can be reached by email:
robtslovak@aol.com
14 Water Conditioning & Purification MARCH 2004

You might also like