You are on page 1of 1

H. ELECTRIC APP.

CO
TECHNICAL DATA SHEET

APPLICATIONS
(Indoor for): Audio Circuits, Control Circuits,
Initiating Circuits and Notification Circuits.

CATEGORY TYPE HEAC 2X14

Material ASTM Bare Copper


CONDUCTOR Up + 0.005
Nom. O.D (mm) 1.63
Down - 0.005
Material Low-Smoke Zero-Halogen(FPLR)
INSULATION
Diameter (mm) 2.83+/-0.10
Extemal O.D. (mm) 7.80+/-0.20
O.D thickness (mm) 1
JACKET Surface Clean, Smooth
Material Low-Smoke Zero-Halogen(FPLR)
Color RED
Item Description Standard
UL listedUL 1424, Power-Limited Fire-Alarm
1.Standard(s) for
Circuit Cables; C22.2 NO. 208-03, Fire-Alarm
Safety
and Signal Cable
PROPERTIES
20℃, Conductor<1>
2.Cond. Resistance < 9.2Ω/1000M
DC Resistance
3.Rated Volage ……. 300Volts max
4.Rated Temperature ……. -40°C ~ 105°C

You might also like