ESDU 98005Issued July 1998

With Amendments A to C
October 2007
Supersedes ESDU 91036
Supersedes in part
ESDU 89016
ESDU 87020
ESDU 88021

Design and performance evaluation


of heat exchangers:
ESDU Copyright material. For current status contact ESDU.

The effectiveness – NTU method

Part 3: Graphical and analytical data

Endorsed by
The Institution of Chemical Engineers
The Institution of Mechanical Engineers
ESDU 98005
ESDU DATA ITEMS

Data Items provide validated information in engineering design and analysis for use by, or under the supervision
of, professionally qualified engineers. The data are founded on an evaluation of all the relevant information, both
published and unpublished, and are invariably supported by original work of ESDU staff engineers or consultants.
The whole process is subject to independent review for which crucial support is provided by industrial companies,
government research laboratories, universities and others from around the world through the participation of some
of their leading experts on ESDU Technical Committees. This process ensures that the results of much valuable
work (theoretical, experimental and operational), which may not be widely available or in a readily usable form, can
be communicated concisely and accurately to the engineering community.

We are constantly striving to develop new work and review data already issued. Any comments arising out of your
use of our data, or any suggestions for new topics or information that might lead to improvements, will help us to
provide a better service.

THE PREPARATION OF THIS DATA ITEM

The work on this particular Data Item was monitored and guided by the Working Party on behalf of the Heat
ESDU Copyright material. For current status contact ESDU.

Transfer Steering Group.

Prof. P.J. Heggs — UMIST


Mr G.H. Walter — Independent.

This Heat Transfer Steering Group first met in 1966 and now has the following membership:

Chairman
Prof. P.J. Heggs — UMIST

Vice-Chairman
Dr R. Cheesewright — Brunel University

Members
Dr T.R. Bott — Birmingham University
Eur. Ing. R.J. Brogan — HTFS, Hyprotech
Eur. Ing. T.J. Loraine — Stone & Webster Engineering Ltd
Dr A.C. Pauls* — Independent
Mr R.E. Sacks — Air Products Ltd
Dr J. Taborek* — Independent
Eur. Ing. M.A. Taylor — Independent
Mr G.H. Walter — Independent
Dr D. Wilkie — Independent.
*
Corresponding Member

This Data Item is one of a group that supersedes Data Items developed for ESDU under contract by

Mr J.A. Ward — Harwell Laboratory

who undertook the technical work involved in the assessment of the available information and the construction and
subsequent development of the original Data Items.

The members of Staff involved with the reassessment of the data, the incorporation of new data for plate-type
exchangers (provided by Mr J.A. Ward) and the development of the new group of Data Items were

Mr S.J. Garvey — Engineer


Mr M.J. Hirt — Engineer
Mr S.J. Pugh — Head of Thermofluids Group.

The person with overall responsibility for the work in this subject area is Mr S.J. Pugh, Head of Thermofluids Group.
ESDU 98005
DESIGN AND PERFORMANCE EVALUATION OF HEAT EXCHANGERS:
THE EFFECTIVENESS – NTU METHOD

PART 3: GRAPHICAL AND ANALYTICAL DATA

CONTENTS
Page

1. NOTATION AND UNITS 1

2. PURPOSE AND SCOPE 2


ESDU Copyright material. For current status contact ESDU.

3. GUIDE TO PRESENTATION OF DATA 3


3.1 Heat Exchanger Family Groups and Key to Index of Geometries 3
3.2 How to Use the Index of Geometries 4
3.2.1 Summary 4
3.2.2 Reference information 4
3.2.3 Relationship between E, NTU and C* 5
3.2.4 Asymptotic expressions 5
3.2.5 Empirical relationship coefficients 5
3.2.6 Acronym Definition 6

4. INDEX OF GEOMETRIES FOR BASIC CONFIGURATIONS 7


4.1 Pure Counter- and Co-current Flows 7

5. INDEX OF GEOMETRIES FOR CROSSFLOW CONFIGURATIONS 8


5.1 Crossflow, Single-pass Configurations, Various Mixing Assumptions 8
5.2 Crossflow, Multi-pass, Unmixed Flow in Exchanger - Counter-current 8
5.3 Crossflow, Multi-pass, Unmixed Flow in Exchanger - Co-current 9
5.4 Crossflow, Tubular Exchangers, Single-pass 10
5.5 Crossflow, Tubular Exchangers, Multi-pass - Counter-current 11
5.6 Crossflow, Tubular Exchangers, Multi-pass - Co-current 12

6. INDEX OF GEOMETRIES FOR SERPENTINE CONFIGURATIONS 13


6.1 Serpentine - Counter-current 13
6.2 Serpentine - Co-current 14

7. INDEX OF GEOMETRIES FOR SHELL-AND-TUBE CONFIGURATIONS 15


7.1 Single E-shell 15
7.2 Multiple E-shells 16
7.3 Single F-shell 17
7.4 Single G-shell 17
7.5 Single J-shell 18
7.6 Multiple J-shells 19
7.7 Single X-shell 19

i
ESDU 98005
8. INDEX OF GEOMETRIES FOR PLATE-TYPE CONFIGURATIONS 20
8.1 One Pass/One Pass, Counter-current (1 of Nch,1 versus 1 of Nch,2) 20
8.2 One Pass/One Pass, Co-current (1 of Nch,1 versus 1 of Nch,2) 20

9. DERIVATION AND REFERENCES 21


9.1 Derivation 21
9.2 References 21

10. DATA FOR BASIC CONFIGURATIONS 22

11. DATA FOR CROSSFLOW CONFIGURATIONS 26


11.1 Crossflow, Single-pass, Various mixing Assumptions 26
11.2 Crossflow, Multi-pass, Unmixed Flow in Exchanger – Counter-current 34
11.3 Crossflow, Multi-pass, Unmixed Flow in Exchanger – Co-current 38
ESDU Copyright material. For current status contact ESDU.

11.4 Crossflow, Tubular Configurations, Single-pass 46


11.5 Crossflow, Tubular Configurations, Multi-pass – Counter-current 64
11.6 Crossflow, Tubular Exchangers, Multi-pass – Co-current 78

12. DATA FOR SERPENTINE CONFIGURATIONS 122


12.1 Serpentine, Counter-current 122
12.2 Serpentine, Co-current 138

13. DATA FOR SHELL-AND-TUBE CONFIGURATIONS 150


13.1 Single E-shell 150
13.2 Multiple E-shells 172
13.3 Single F-shells 194
13.4 Single G-shells 202
13.5 Single J-shells 206
13.6 Multiple J-shells 232
13.7 Single X-shells 248

14. DATA FOR PLATE-TYPE CONFIGURATIONS 252


14.1 One Pass/One Pass, Counter-current 252
14.2 One Pass/One Pass, Co-current 258

ii
ESDU 98005
DESIGN AND PERFORMANCE EVALUATION OF HEAT EXCHANGERS:
THE EFFECTIVENESS – NTU METHOD

PART 3: GRAPHICAL AND ANALYTICAL DATA

1. NOTATION AND UNITS

Two sets of self-consistent units are given.

Units

SI British
ESDU Copyright material. For current status contact ESDU.

C* thermal capacity ratio, defined in Section 4.2.3 of Part 1 – –

cp specific heat capacity J/kg K Btu/lb°F

E thermal effectiveness, defined in Section 4.2.1 of Part 1 – –


· mass flow rate kg/s lb/h
M

Np number of thermal plates – –

N TU number of heat transfer units, defined in Section 4.2.2 of – –


Part 1

S number of shells – –

Y ratio of potential for heat transfer across baffle and between – –


streams in F-shell heat exchanger (defined in Section 4.5.1 of
Part 2)
Subscripts

asymp value as N TU tended towards

larger larger value of parameter in streams

smaller smaller value of parameter in streams

1 refers to stream number 1 or location 1

2 refers to stream number 2 or location 2

Note:
A number of additional symbols are defined and used in the algebraic expressions presented in the
data tables.

Issued July 1998


With Amendments A to C, October 2007
1
ESDU 98005
2. PURPOSE AND SCOPE

This is the third of a group of Data Items concerning the effectiveness (E) - number of heat transfer units
( N TU ) method for the thermal analysis of two-stream heat exchangers. Aspects of the method presented
in the Data Items in the group are as follows.

Data Item
Title Description
Number

98003 Part 1. Introduction Description and overview of the E– N TU method.


98004 Part 2. Comparison of Comparative performance and performance
performance of various limitations of particular heat exchanger
configurations and selection of configurations.
ESDU Copyright material. For current status contact ESDU.

configurations presented in
Part 3
98005 Part 3. Graphical representation Data required to use the method. The range of
heat exchangers covered includes pure
counter-current, pure co-current, crossflow,
shell-and-tube and plate heat exchanger
configurations.
98006 Part 4. Case studies Case studies, incorporating all elements of the
method presented.
98007 Part 5. Analytical techniques Numerical and algebraic techniques for relating
heat transfer effectiveness, E, to the number of
heat transfer units, N TU .

This Data Item provides graphical and analytical data for a wide range of practical heat exchanger types
and configurations. To allow the engineer rapid access to the data this Item is divided into the following
main sections.

Section 3 A guide to the presentation of the data, which are presented in “family groups” based on
exchanger types (see Sketch 3.1), and guidance on the use of the Index of Geometries
(see Section 3.2).
Sections 4 For each family group there is an Index of Geometries, in which each particular
to 8 configuration is identified by a concise description and is assigned a unique acronym
(see Section 3.2.6).
Sections 10 For each exchanger family group the E – N TU data are presented in data sheet form,
to 14 where for each configuration graphical information is presented on right hand pages and
a detailed description is presented on facing left hand pages.

2
3. GUIDE TO PRESENTATION OF DATA

3.1 Heat Exchanger Family Groups and Key to Index of Geometries

BASIC CONFIGURATION (Section 4) SERPENTINE CONFIGS (Section 6) PLATE-TYPE CONFIGS. (Section 8)

One-pass/one pass
Pure counter-current Counter-current (6.1) counter-current (8.1)
(4.1)
Pure co-current Co-current (6.2) One pass/one pass,
(4.1) co-current (8.2)
ESDU Copyright material. For current status contact ESDU.

CROSSFLOW CONFIGURATIONS (Section 5) SHELL-AND-TUBE CONFIGURATIONS (Section 7)

Single-pass, various mixing assumptions (5.1) E-Shells J-Shells


Single (7.1) Single (7.5)
3

Multi-pass, unmixed Multiple (7.2)


in exchanger Multiple (7.6)
Counter-current (5.2)
Co-current (5.3)
Single F-shell (7.3) Single X-shell (7.7)

ESDU 98005
Tubular crossflow exchangers
Single-pass (5.4) Multi-pass, counter-current (5.5)
Multi-pass, co-current (5.6)

Single G-shell (7.4)

Sketch 3.1 Schematic diagram of heat exchanger family groups


ESDU 98005
3.2 How to Use the Index of Geometries

3.2.1 Summary

Each unique heat exchanger configuration is identified in Sections 4, 5, 6 and 7 by its location within its
family group (see Sketch 3.1) and by its reference information. For each configuration a unique acronym
is provided that is noted on the data sheets and graphs.

For all exchanger configurations (as applicable) the following information is stated:

• the flow configuration,

• the number of tube or flow channel passes,

• the stream mixing assumptions,


ESDU Copyright material. For current status contact ESDU.

• the number of tube rows per pass,

• the pass connections,

• the number of shells and their configuration (shell-and-tube configurations only),

• the number of baffles (shell-and-tube configurations only),


·
• the position of ( M c p ) smaller .

Graphical and analytical data are provided for each exchanger configuration in data sheet form. For a single
configuration, the reference information (see Section 3.2.2) and data are presented on facing pages. The
analytical data are presented in three forms, as follows.

(1) Algebraic relationship between effectiveness, E, number of heat transfer units, N TU , and thermal
capacity ratio, C* . (See Section 3.2.3.)

(2) Expression (where available) and table for E asymp . (See Section 3.2.4.)

(3) Empirical relationship coefficients (where available). (See Section 3.2.5.)

Entries are omitted where information is not available.

3.2.2 Reference information

In addition to the schematic diagrams, seven categories are illustrated in Sketch 3.2 that are used to describe
fully all exchanger configurations. A null entry is shown by a ‘-’, and indicates that either the entry does
not apply to the particular configuration or the entry is irrelevant.

In some cases data for a single exchanger type apply to more than one configuration; this is illustrated in
the schematic diagrams on the data tables.

4
ESDU 98005
(1) Exchanger type Crossflow
(2) Number of 2 Passes
passes/shells/thermal plates
2 Tube rows per pass
(3) Exchanger configuration ·
( M c p ) smaller inside tubes
·
(4) Stream with ( M c p ) smaller All connections
(5) Pass connections Part mixed/Unmixed
(6) Mixing in the exchanger -
(tubeside/shellside or
ductside)
ESDU Copyright material. For current status contact ESDU.

(7) Mixing between passes


(Shellside or ductside/
tubeside)
or
flow configuration

Sketch 3.2 Reference Information

3.2.3 Relationship between E , N TU and C*

The graphical relationship between E , N TU and C* is, in some cases, described by the analytical
expression.

E = function ( N TU ,C* ) .

Where available, the sources of the analytical expressions are noted on the data sheets. The analytical
techniques used to generate data for heat exchanger configurations for which expressions were not available
are discussed in Part 5 of the group of Data Items.

3.2.4 Asymptotic expressions

In general, heat transfer effectiveness, E, increases with increasing values of N TU , reaching a maximum
as N TU tends to infinity. For some types of heat exchanger, the value of E passes through a maximum
before falling to a lower asymptotic value as NTU tends to infinity.

In designing a heat exchanger, for those exchangers for which E has no maximum, the asymptotic or
maximum value of E is important because it represents the performance limit that can be achieved for any
particular value of C*, no matter how large the heat exchanger is made. In such situations, for a given
configuration the asymptotic or maximum values of E for each curve are tabulated. A further explanation
of these values can be found in Part 1 of this group of Data Items.

3.2.5 Empirical relationship coefficients

For certain exchanger configurations empirical relationships relating E, N TU and C* have been developed.
For each of those configurations a set of coefficients is presented in a table. The full form of this equation
is given in Part 1 of the group of Data Items.

5
ESDU 98005
3.2.6 Acronym Definition

Each exchanger configuration presented in this group of Data Items is identified by a unique acronym. This
acronym describes the generic family group of the heat exchanger and identifies its particular configuration.
The definitions of the individual components of the acronyms are listed in Sketch 3.3.

Top Level

PURE Used for pure counter-current or co-current configurations


CRO Crossflow configurations
SERP Serpentine configurations
ESDU Copyright material. For current status contact ESDU.

SAT Shell-and-tube configurations


PLATE Plate-type configurations

Lower levels
1:1 Refers to one pass/one pass plate-type configurations

CO Co-current flow
CU Counter-current flow
E E-shell
F F-shell
G G-shell

J J-shell
MIX Fully-mixed flow in stream
MP Multiple passes
MS Multiple shells
SP Single pass
SS Single shell
UNMIX Unmixed flow in stream
X X-shell

Sketch 3.3 Acronym Components and Heirarchy

6
ESDU 98005
4. INDEX OF GEOMETRIES FOR BASIC CONFIGURATIONS

4.1 Pure Counter- and Co-current Flows

See Sketch 3.1 for exchanger family groups Position of ( M· c p ) smaller

Flow
Figure No. Acronym No. passes Either stream
config.

1 PURE-CU Cu 1 Yes

2 PURE-CO Co 1 Yes
ESDU Copyright material. For current status contact ESDU.

7
5. INDEX OF GEOMETRIES FOR CROSSFLOW CONFIGURATIONS

5.1 Crossflow, Single-pass Configurations, Various Mixing Assumptions

See Sketch 3.1 for exchanger family groups Position of ( M· c p ) smaller

Stream mixing assumptions


Either Mixed Unmixed
Figure No. Acronym No. passes
stream stream stream
Stream 1 Stream 2
ESDU Copyright material. For current status contact ESDU.

3 CRO-MIX/MIX 1 Mixed Mixed Yes

CRO-UNMIX/MIX-1
4 1 Mixed Unmixed Yes
(also CRO-TUBE-SP-1)

CRO-UNMIX/MIX-2
5 1 Mixed Unmixed Yes
(also CRO-TUBE-SP-2)
8

6 CRO-UNMIX/UNMIX 1 Unmixed Unmixed Yes

5.2 Crossflow, Multi-pass, Unmixed Flow in Exchanger - Counter-current

See Sketch 3.1 for exchanger family groups Position of ( M· c p ) smaller

ESDU 98005
Stream mixing
No. tube/ No. tube/ Pass connections
Figure Flow assumptions
Acronym channel channel Either stream
No. config.
passes rows/pass
Stream 1 Stream 2 Stream 1 Stream 2

7 CRO-UNMIX-MP-CU-1 Cu 2 >3 Unmixed Unmixed Any Any Yes

8 CRO-UNMIX-MP-CU-2 Cu 3 >2 Unmixed Unmixed Any Any Yes


5.3 Crossflow, Multi-pass, Unmixed Flow in Exchanger - Co-current

See Sketch 3.1 for exchanger family groups Position of ( M· c p ) smaller

Stream mixing
No. tube/ No. tube/ Pass connections
Flow assumptions Either Mixed Unmixed
Figure No. Acronym channel channel
config. stream Stream Stream
passes rows/pass
Stream 1 Stream 2 Stream 1 Stream 2

9 CRO-UNMIX-MP-CO-1 Co 2 >3 Unmixed Unmixed Mixed Mixed Yes


ESDU Copyright material. For current status contact ESDU.

10 CRO-UNMIX-MP-CO-2 Co 2 >3 Unmixed Unmixed Mixed Unmixed Yes

11 CRO-UNMIX-MP-CO-3 Co 2 >3 Unmixed Unmixed Mixed Unmixed Yes

12 CRO-UNMIX-MP-CO-4 Co 2 >3 Unmixed Unmixed Unmixed Unmixed Yes


9

ESDU 98005
5.4 Crossflow, Tubular Exchangers, Single-pass

See Sketch 3.1 for exchanger family groups Position of ( M· c p ) smaller

Stream mixing
assumptions
No. tube No. tube No. tubes Either Inside Outside
Figure No. Acronym
passes rows/pass per row stream tubes tubes
Inside Outside
tubes tubes
ESDU Copyright material. For current status contact ESDU.

CRO-TUBE-SP-1
13 1 1 Any Mixed Unmixed Yes
(also CRO-UNMIX/MIX-2)

CRO-TUBE-SP-2
14 1 1 Any Mixed Unmixed Yes
(also CRO-UNMIX/MIX-1)

15 CRO-TUBE-SP-3 1 2 Any Part-mixed Unmixed Yes


10

16 CRO-TUBE-SP-4 1 2 Any Part-mixed Unmixed Yes

17 CRO-TUBE-SP-5 1 3 Any Part-mixed Unmixed Yes

18 CRO-TUBE-SP-6 1 3 Any Part-mixed Unmixed Yes

19 CRO-TUBE-SP-7 1 4 Any Part-mixed Unmixed Yes

ESDU 98005
20 CRO-TUBE-SP-8 1 4 Any Part-mixed Unmixed Yes

CRO-TUBE-SP-9
21 1 >4 Any Unmixed Unmixed Yes
(also CRO-UNMIX/UNMIX)
5.5 Crossflow, Tubular Exchangers, Multi-pass - Counter-current

See Sketch 3.1 for exchanger family groups


Position of ( M· c p ) smaller
Note: for one tube row per pass (serpentine), see Section 6.1

Stream mixing
* assumptions
Flow No. tube No. tube No. tubes Tube pass Either Inside Outside
Figure No. Acronym
config. passes rows/pass per row connections stream tubes tubes
Inside Outside
tubes tubes
ESDU Copyright material. For current status contact ESDU.

22 CRO-TUBE-MP-CU-1 Cu 2 2 Any Part-mixed Unmixed Any Yes

23 CRO-TUBE-MP-CU-2 Cu 2 2 Any Part-mixed Unmixed Any Yes

24 CRO-TUBE-MP-CU-3 Cu 2 3 Any Part-mixed Unmixed Any Yes


11

25 CRO-TUBE-MP-CU-4 Cu 2 >3 Any Unmixed Unmixed Any Yes

26 CRO-TUBE-MP-CU-5 Cu 3 2 Any Part-mixed Unmixed Any Yes

ESDU 98005
27 CRO-TUBE-MP-CU-6 Cu 3 >2 Any Unmixed Unmixed Any Yes

28 CRO-TUBE-MP-CU-7 Cu 4 >1 Any Unmixed Unmixed Any Yes

* A counter-current arrangement is defined as one where the tubeside inlet is located adjacent to the exit of the crossflow stream.
5.6 Crossflow, Tubular Exchangers, Multi-pass - Co-current

See Sketch 3.1 for exchanger family groups Position of


Note: for one tube row per pass (serpentine), see Section 6.2 ( M· c p ) smaller
*Flow No. No. Stream mixing assumptions
Figure No. tube Inside Outside
Acronym tube tubes per Inside Outside Tube pass connections
No. config. rows/pass tubes tubes
passes row tubes tubes
29 CRO-TUBE-MP-CO-1 Co 2 2 Any Part-mixed Unmixed Mixed Yes
30 CRO-TUBE-MP-CO-2 Co 2 2 Any Part-mixed Unmixed Mixed Yes
31 CRO-TUBE-MP-CO-3 Co 2 2 Any Part-mixed Unmixed U-tube, inverted Yes
32 CRO-TUBE-MP-CO-4 Co 2 2 Any Part-mixed Unmixed U-tube, inverted Yes
ESDU Copyright material. For current status contact ESDU.

33 CRO-TUBE-MP-CO-5 Co 2 2 Any Part-mixed Unmixed U-tube, non-inverted Yes


34 CRO-TUBE-MP-CO-6 Co 2 2 Any Part-mixed Unmixed U-tube, non-inverted Yes
35 CRO-TUBE-MP-CO-7 Co 2 3 Any Part-mixed Unmixed Mixed Yes
36 CRO-TUBE-MP-CO-8 Co 2 3 Any Part-mixed Unmixed Mixed Yes
37 CRO-TUBE-MP-CO-9 Co 2 >3 Any Unmixed Unmixed Mixed Yes
38 CRO-TUBE-MP-CO-10 Co 2 >3 Any Unmixed Unmixed Mixed Yes
12

39 CRO-TUBE-MP-CO-11 Co 3 2 Any Part-mixed Unmixed Mixed Yes


40 CRO-TUBE-MP-CO-12 Co 3 2 Any Part-mixed Unmixed Any connections Yes
41 CRO-TUBE-MP-CO-13 Co 3 2 Any Part-mixed Unmixed U-tube, inverted Yes
42 CRO-TUBE-MP-CO-14 Co 3 2 Any Part-mixed Unmixed U-tube, inverted Yes
43 CRO-TUBE-MP-CO-15 Co 3 2 Any Part-mixed Unmixed U-tube, non-inverted Yes

ESDU 98005
44 CRO-TUBE-MP-CO-16 Co 3 2 Any Part-mixed Unmixed U-tube, non-inverted Yes
45 CRO-TUBE-MP-CO-17 Co 3 >2 Any Unmixed Unmixed Mixed Yes
46 CRO-TUBE-MP-CO-18 Co 3 >2 Any Unmixed Unmixed Mixed Yes

47 CRO-TUBE-MP-CO-19 Co 4 2 Any Part-mixed Unmixed U-tube, inverted Yes


48 CRO-TUBE-MP-CO-20 Co 4 2 Any Part-mixed Unmixed U-tube, inverted Yes
49 CRO-TUBE-MP-CO-21 Co 4 Any Any Mixed or unmixed Unmixed Header or U-tube, non-inverted Yes
50 CRO-TUBE-MP-CO-22 Co 4 Any Any Mixed or unmixed Unmixed Header or U-tube, non-inverted Yes
*
A co-current arrangement is defined as one where the tubeside inlet is located adjacent to the inlet of the crossflow stream.
6. INDEX OF GEOMETRIES FOR SERPENTINE CONFIGURATIONS

6.1 Serpentine - Counter-current

See Sketch 3.1 for exchanger family groups Position of ( M· c p ) smaller

Stream mixing
Flow No. tube No. tube No. tubes Either Inside Outside
Figure No. Acronym
Config. passes rows/pass per row Inside Outside stream tubes tubes
tubes tubes
ESDU Copyright material. For current status contact ESDU.

51 SERP-CU-1 Cu 2 1 Any Mixed Unmixed Yes

52 SERP-CU-2 Cu 2 1 Any Mixed Unmixed Yes

53 SERP-CU-3 Cu 3 1 Any Mixed Unmixed Yes

54 SERP-CU-4 Cu 3 1 Any Mixed Unmixed Yes


13

55 SERP-CU-5 Cu 4 1 Any Mixed Unmixed Yes

56 SERP-CU-6 Cu 4 1 Any Mixed Unmixed Yes

ESDU 98005
57 SERP-CU-7 Cu 6 1 Any Mixed Unmixed Yes

58 SERP-CU-8 Cu 9 1 Any Mixed Unmixed Yes


6.2 Serpentine - Co-current

See Sketch 3.1 for exchanger family groups Position of ( M· c p ) smaller

Stream mixing
Flow No. tube No. tube No. tubes Either Inside Outside
Figure No. Acronym
config. passes rows/pass per row Inside Outside stream tubes tubes
tubes tubes

59 SERP-CO-1 Co 2 1 Any Mixed Unmixed Yes


ESDU Copyright material. For current status contact ESDU.

60 SERP-CO-2 Co 2 1 Any Mixed Unmixed Yes

61 SERP-CO-3 Co 3 1 Any Mixed Unmixed Yes

62 SERP-CO-4 Co 3 1 Any Mixed Unmixed Yes


14

SERP-CO-5
63 Co 4 1 Any Mixed Unmixed Yes
(also CRO-TUBE-MP-21)

SERP-CO-6
64 Co 4 1 Any Mixed Unmixed Yes
(also CRO-TUBE-MP-22)

ESDU 98005
7. INDEX OF GEOMETRIES FOR SHELL-AND-TUBE CONFIGURATIONS

7.1 Single E-shell

See Sketch 3.1 for exchanger family groups Position of ( M· c p ) smaller

No. tube No. tube No. tubes No. shells No. *Flow Either
Figure No. Acronym Tubeside Shellside
passes rows/pass per row in series baffles configuration stream

65 SAT-E-SS-1 Even no. Any Any 1 >5 – Yes


ESDU Copyright material. For current status contact ESDU.

66 SAT-E-SS-2 3 Any Any 1 >5 – Yes

67 SAT-E-SS-3 3 Any Any 1 >5 – Yes


15

68 SAT-E-SS-4 2 Any Any 1 1 Co-current Yes

69 SAT-E-SS-5 2 Any Any 1 1 Counter-current Yes

70 SAT-E-SS-6 2 Any Any 1 2 Co-current Yes

ESDU 98005
71 SAT-E-SS-7 2 Any Any 1 2 Counter-current Yes

72 SAT-E-SS-8 2 Any Any 1 3 Co-current Yes

73 SAT-E-SS-9 2 Any Any 1 3 Counter-current Yes

74 SAT-E-SS-10 2 Any Any 1 4 Co-current Yes

75 SAT-E-SS-11 2 Any Any 1 4 Counter-current Yes

*
A counter-current configurations is defined as one where the tubeside outlet is located adjacent to the shellside inlet.
A co-current configuration is defined as one where the tubeside inlet is located adjacent to the shellside inlet.
7.2 Multiple E-shells

See Sketch 3.1 for exchanger family groups Position of ( M· c p ) smaller

No. tube No. tube No. tubes No. shells No. Flow
Figure No. Acronym Flow config. Either stream Side
passes rows/pass per row in series baffles configuration

Overall
76 SAT-E-MS-1 Series/series Even no. Any Any 2 >5 Yes
counter-current
ESDU Copyright material. For current status contact ESDU.

Overall
77 SAT-E-MS-2 Series/series Even no. Any Any 3 >5 Yes
counter-current

Overall
78 SAT-E-MS-3 Series/series Even no. Any Any 4 >5 Yes
counter-current

Overall
79 SAT-E-MS-4 Series/series Even no. Any Any 5 >5 Yes
16

counter-current

Overall
80 SAT-E-MS-5 Series/series Even no. Any Any 6 >5 Yes
counter-current

ESDU 98005
81 SAT-E-MS-6 Series/parallel Even no. Any Any 2 >5 – Parallel

82 SAT-E-MS-7 Series/parallel Even no. Any Any 2 >5 – Series

83 SAT-E-MS-8 Series/parallel Even no. Any Any3 3 >5 – Parallel

84 SAT-E-MS-9 Series/parallel Even no. Any Any 3 >5 – Series

85 SAT-E-MS-10 Series/parallel Even no. Any Any 4 >5 – Parallel

86 SAT-E-MS-11 Series/parallel Even no. Any Any 4 >5 – Series


7.3 Single F-shell

See Sketch 3.1 for exchanger family groups Position of ( M· c p ) smaller

No. tube No. tubes


Figure No. Acronym Y Tubeside Shellside
rows/pass per row

87 SAT-F-SS-1 Any Any 0.02 Yes

88 SAT-F-SS-2 Any Any 0.02 Yes


ESDU Copyright material. For current status contact ESDU.

89 SAT-F-SS-3 Any Any 0.04 Yes

90 SAT-F-SS-4 Any Any 0.04 Yes


17

7.4 Single G-shell

See Sketch 3.1 for exchanger family


Position of ( M· c p ) smaller
groups

ESDU 98005
No. tube
Figure No. Acronym Tubeside Shellside
passes

91 SAT-G-SS-1 2 Yes

92 SAT-G-SS-2 2 Yes
7.5 Single J-shell

See Sketch 3.1 for exchanger family groups Position of ( M· c p ) smaller


*Flow
No. tube No. Either
Figure No. Acronym Tubeside Shellside
passes baffles configuration stream

93 SAT-J-SS-1 1 >9 Yes

94 SAT-J-SS-2 1 >9 Yes

95 SAT-J-SS-3 2 >9 Counter-current Yes


ESDU Copyright material. For current status contact ESDU.

96 SAT-J-SS-4 2 >9 Counter-current Yes

97 SAT-J-SS-5 >2 >9 Counter-current Yes

98 SAT-J-SS-6 2 5 Counter-current Yes


18

99 SAT-J-SS-7 2 5 Counter-current Yes

100 SAT-J-SS-8 2 5 Co-current Yes

101 SAT-J-SS-9 2 5 Co-current Yes

ESDU 98005
102 SAT-J-SS-10 2 9 Counter-current Yes

103 SAT-J-SS-11 2 9 Counter-current Yes

104 SAT-J-SS-12 2 9 Co-current Yes

105 SAT-J-SS-13 2 9 Co-current Yes

* A counter-current configuration is defined as one where the tubeside inlet is located adjacent to a shellside outlet port.
A co-current arrangement is defined as one where the tubeside outlet is located adjacent to a shellside outlet port.
7.6 Multiple J-shells

See Sketch 3.1 for exchanger family groups Position of ( M· c p ) smaller

No. tube Tubeside Shellside


No. shells Shellside
Figure No. Acronym Flow config. passes per
in series connections
shell

106 SAT-J-MS-1 Overall counter-current 1 2 Cross connections Yes

107 SAT-J-MS-2 Overall counter-current 1 2 Cross connections Yes


ESDU Copyright material. For current status contact ESDU.

108 SAT-J-MS-3 Overall counter-current 1 2 Mixed connections Yes

109 SAT-J-MS-4 Overall counter-current 1 2 Mixed connections Yes

110 SAT-J-MS-5 Overall counter-current 1 2 Direct connections Yes

111 SAT-J-MS-6 Overall counter-current 1 2 Direct connections Yes


19

112 SAT-J-MS-7 Overall counter-current 2 2 Mixed connections Yes

113 SAT-J-MS-8 Overall counter-current 2 2 Mixed connections Yes

ESDU 98005
7.7 Single X-shell

See Sketch 3.1 for exchanger family groups Position of ( M· c p ) smaller

No. tube Tubeside pass


Figure No. Acronym Flow config. Either stream
passes connections

114 SAT-X-SS-CU Overall counter-current 2 U-tube Yes

115 SAT-X-SS-CO Overall co-current 2 U-tube Yes


8. INDEX OF GEOMETRIES FOR PLATE-TYPE CONFIGURATIONS

8.1 One Pass/One Pass, Counter-current (1 of Nch,1 versus 1 of Nch,2)

Position of
See Sketch 3.1 for exchanger family groups
( M· c p ) smaller

Figure No. Acronym Flow config. No. thermal plates Either stream

116 PLATE-1:1-CU-1 Counter-current 1, 2 or ≥ 14 Yes

117 PLATE-1:1-CU-2 Counter-current 4, 6 to 13 Yes


ESDU Copyright material. For current status contact ESDU.

118 PLATE-1:1-CU-3 Counter-current 3, 5 Yes

8.2 One Pass/One Pass, Co-current (1 of Nch,1 versus 1 of Nch,2)

Position of
See Sketch 3.1 for exchanger family groups
( M· c p ) smaller
20

Figure No. Acronym Flow config. No. thermal plates Either stream

119 PLATE-1:1-CO-1 Counter-current 1, 2, 4, 6, 8, 10 or ≥ 12 Yes

120 PLATE-1:1-CO-2 Counter-current 5, 7, 9 or 11 Yes

ESDU 98005
121 PLATE-1:1-CO-3 Counter-current 3 Yes
ESDU 98005
9. DERIVATION AND REFERENCES

9.1 Derivation

The following sources have assisted in the preparation of this Item.

1. UNDERWOOD, J.A.V. The calculation of mean temperature difference in multi-pass heat


exchangers. J. Inst. Pet. Technology, Vol. 22, pp. 145-158, 1934.
2. BOWMAN, R.A. Mean temperature difference correction in multi-pass exchangers. Ind.
Engng Chem., Vol. 28, pp. 541-544, 1936.
3. FISCHER, F.K. Mean temperature difference correction in multi-pass exchangers. Ind.
Engng. Chem, Vol. 30, No. 4, pp. 377-382, 1938.
4. STEVENS, R.A. Mean temperature difference in one, two and three pass crossflow heat
FERNANDEZ, J. exchangers. Trans ASME, pp. 287-297, February 1957.
ESDU Copyright material. For current status contact ESDU.

WOOLF, J.R.
5. SCHLINDER, D.L. True temperature difference in a 1-2 divided flow heat exchanger.
BATES, H.T. Chem. Engng Prog., Symp. Series, Vol. 56, No. 30, pp. 203-206, 1960.
6. JAW, L. Temperature relations in shell and tube exchangers having one-pass
split-flow shells. Trans ASME, J. Heat Transfer, pp. 408-416, August
1964.
7. ROZENMAN, T. The effect of leakage through the longitudinal baffle on the
TABOREK, J. performance of two-pass shell exchangers. AIChemE, Symp. Series,
Vol. 68, No. 118, pp. 12-20, 1972.
8. TABOREK, J. Heat Exchanger Design Handbook, Section 1.5, Hemisphere
Publishing Corporation, 1983.
9. PIGNOTTI, A. Matrix formalism for complex heat exchangers. Trans ASME, J. Heat
Transfer, Vol. 106, pp. 352-360, May 1984.

9.2 References

The following sources provide additional guidance on the E – N TU method. A full bibliography for the
group of Data Items is given in Part 5.

10. TEN BROECK, H. Multi-pass exchanger calculations. Ind. Engng Chem., Vol. 30,
pp. 1041-1042, 1938.
11. WHISTLER, A.M. Correction for heat conduction through longitudinal baffle of heat
exchanger. Trans ASME, Vol. 69, pp.683-685, 1947.
12. KERN, D.Q. Process Heat Transfer. 1st Ed., McGraw-Hill, 1950.
13. NICOLE, F.J.L. Council for Scientific and Industrial Research (CSIR) Rep. Chem. 223,
Pretoria, S. Africa, 1972.
14. DODD, R. Temperature efficiency of heat exchangers with one shell pass and even
numbers of tube passes. Trans I. Chem. Eng., Vol. 60, pp. 364-368,
1982.
15. TABOREK, J. Private communication. 1982.
16. KAYS, W. Compact Heat Exchangers. 3rd Ed., McGraw-Hill, 1984.
LONDON, A.L.
17. PIGNOTTI, A. Effectiveness of series assemblies of divided-flow heat exchangers.
Trans ASME, J. Heat Transfer, Vol. 108, pp. 141-146, February 1986.

21
ESDU 98005
10. DATA FOR BASIC CONFIGURATIONS

TABLE 10.1
Pure counter-current PURE-CU
Single pass

·c )
(M p smaller in either stream


-

ESDU Copyright material. For current status contact ESDU.

Relationship between E , N TU and C*

log e  ----------------------
1 – EC*
 1–E  E
N TU = --------------------------------------- = -------------- , or
1 – C* C∗ ≠ 1 1 – E C∗ = 1

1 – exp [ N TU ( 1 – C * ) ] N TU
E = ---------------------------------------------------------------- = --------------------- .
C* – exp [ N TU ( 1 – C * ) ] 1 + N TU C∗ = 1
C∗ ≠ 1

Asymptotic expression

E asymp = E max = 1.0 for all values of C* .

Algebraic coefficients

0 1 2 3 4
a 1 0 0
b 0 0 0 0 0
c 100
d 0 0 0 0 0
g 0.5 0.6197 –0.1940

22
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

PURE-CU
0.9 0.9

0. 6 . 7
0
C* 0. 8
0.8
0.0 0.9 0.8
0.1 1.0
0.2 C*
0.3
ESDU Copyright material. For current status contact ESDU.

0.4
0.7 0.7
0.5

E E

0.6 0.6
23

0.5 0.5
95% of Emax
Temperature meet
0.4 0.4

ESDU 98005
Configuration Data
0.3 See Table 10.1 0.3
Index of Geometries
See Section 4.1

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
FIGURE 1 PURE COUNTER-CURRENT
ESDU 98005
TABLE 10.2
Pure co-current PURE-CO
Single pass
-
·
( M c p ) smaller in either stream

Relationship between E , N TU and C*


– log e [ 1 – E ( 1 + C* ) ]
ESDU Copyright material. For current status contact ESDU.

N TU = --------------------------------------------------------- , or
C* + 1
1 – exp [ – N TU ( 1 + C* ) ]
E = ---------------------------------------------------------------- .
1 + C*

Asymptotic expression

1
E asymp = E max = ------------------ for all values of C* .
C* + 1
Tabulated values of E max are given in the following table.

C* E max
0 1
0.1 0.91
0.2 0.83
0.3 0.77
0.4 0.71
0.5 0.67
0.6 0.63
0.7 0.59
0.8 0.56
0.9 0.53
1.0 0.5

Algebraic coefficients

0 1 2 3 4
a 1 0 0
b 0 0 0 0 0
c 100
d 0 0 0 0 0
g 0.5 0.6197 –0.1940

24
NTU

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10


1.0 1.0

PURE-CO
0.9 0.9

C*
0.8 0.0 0.8
0.1
0.2
ESDU Copyright material. For current status contact ESDU.

0.3
0.4
0.7 0.5 0.7

E E
0.6
0.6 0.7 0.6

0.8
0.9
25

0.5 1.0 0.5


C*
95% of Emax

0.4 0.4
Configuration Data

ESDU 98005
See Table 10.2
Index of Geometries
0.3 See Section 4.1 0.3

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
FIGURE 2 PURE CO-CURRENT
ESDU 98005
11. DATA FOR CROSSFLOW CONFIGURATIONS

11.1 Crossflow, Single-pass, Various mixing Assumptions

TABLE 11.1
Crossflow CRO-MIX/MIX
Single pass

·c )
(M p smaller in either stream

Both streams fully mixed
ESDU Copyright material. For current status contact ESDU.


Relationship between E , N TU and C* . (See Derivation 4.)
1
E = ----------------------------------------------------------------- ,where φ = exp [ N TU ] .
C*
C∗ φ φ 1
-------------------- + ------------- – ---------------
C* φ – 1 loge φ
φ –1
Asymptotic expression
1
E asymp = ------------------ .
1 + C*
Since the curves pass through a maximum before reaching the asymptotic value, the following data are provided
to assist their use.
C* E max N TU for E max E asymp
0 1 inf. 1
0.1 0.946 7.12 0.91
0.2 0.891 5.78 0.83
0.3 0.838 5.02 0.77
0.4 0.789 4.50 0.71
0.5 0.742 4.10 0.67
0.6 0.700 3.79 0.63
0.7 0.662 3.54 0.59
0.8 0.626 3.32 0.56
0.9 0.594 3.14 0.53
1 0.565 2.98 0.50

Algebraic coefficients
0 1 2 3 4
a 0.4219 –0.4810 0.1880
b 1.3350 –1.6590 –0.8430 2.1900 –0.7320
c 100.0000
d 0.0000 –4.1440 11.6760 –12.5030 4.6080
g 0.3352 0.7187 –0.1931

26
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

CRO-MIX/MIX
0.9 0.9

C*
0.8 0.0 0.8
0.1
0.2
0.3
ESDU Copyright material. For current status contact ESDU.

0.4
0.7 0.5 0.7
0.6
0. 7
E E
0.8
0.6 0.9 0.6
1.0
C*
27

0.5 0.5
95% of Emax
Temperature meet
0.4 0.4

Configuration Data

ESDU 98005
See Table 11.1
0.3 Index of Geometries 0.3
See Section 4.1

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
FIGURE 3 CROSSFLOW, SINGLE PASS, MIXED/MIXED
ESDU 98005
TABLE 11.2
Crossflow
CRO-UNMIX/MIX-1
Single pass
Infinite tube rows
·c )
(M p smaller in unmixed
stream

Equivalent to
Mixed/unmixed CRO-TUBE-SP-2

Relationship between E , N TU and C* . (See Derivation 4.)
ESDU Copyright material. For current status contact ESDU.

1 – exp [ – C* ( 1 – exp ( – N TU ) ) ]
E = ---------------------------------------------------------------------------------- .
C*

Asymptotic expression
E asymp = ( 1 – exp [ – C* ] )/C* .

C* E asymp
0 1.00
0.1 0.95
0.2 0.91
0.3 0.86
0.4 0.82
0.5 0.79
0.6 0.75
0.7 0.72
0.8 0.69
0.9 0.66
1 0.63

Algebraic coefficients
0 1 2 3 4
a 0.4939 –0.3019 0.0722
b 0.2886 2.1267 –6.6072 6.7717 –2.3616
c 100.0000
d –0.6400 0.6117 –0.7777 1.2072 –0.5900
g 0.3749 0.7021 –0.2012

28
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

CRO-UNMIX/MIX-1
0.9 0.9

0.8 C* 0.8
0.0
0.1 0.6
0.2
ESDU Copyright material. For current status contact ESDU.

0.3 0.7
0.7 0.4 0.8 0.7
0.5
0.9
E 1.0 E
*
C
0.6 0.6
29

0.5 0.5
95% of Emax
Temperature meet
0.4 0.4

Configuration Data

ESDU 98005
See Table 11.2
Index of Geometries
0.3 0.3
See Section 5.1

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU

·c )
FIGURE 4 CROSSFLOW, SINGLE PASS, MIXED/UNMIXED, ( M p smaller ON UNMIXED SIDE
ESDU 98005
TABLE 11.3
Crossflow CRO-UNMIX/MIX-2
Single pass
1 Tube row
·c )
(M p smaller in mixed stream


Mixed/unmixed Equivalent to
– CRO-TUBE-SP-1

Relationship between E , N TU and C* . (See Derivation 4.)


ESDU Copyright material. For current status contact ESDU.

– ( 1 – exp ( – N TU C* ) )
E = 1 – exp --------------------------------------------------------
C*

Asymptotic expression
E asymp = 1 – exp [ – 1/C* ] .

C* E asymp
0 1
0.1 1
0.2 0.99
0.3 0.96
0.4 0.92
0.5 0.86
0.6 0.81
0.7 0.76
0.8 0.71
0.9 0.67
1 0.63

Algebraic coefficients
0 1 2 3 4
a 1.3249 –1.8438 0.7831
b –7.1739 37.6000 –73.1022 63.8124 –20.9271
c 100.00
d –0.2330 –0.8090 2.8338 –3.3782 1.3972
g 0.3572 0.8252 –0.2785

30
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

CRO-UNMIX/MIX-2
0.9 0.9

C* 0.6
0.8 0.0 0.8
0.1
0.7
0.2
0.3
ESDU Copyright material. For current status contact ESDU.

0.4 0.8
0.7 0.5 0.7
0.9
E 1.0 E

0.6 C* 0.6
31

0.5 0.5
95% of Emax
Temperature meet
0.4 0.4
Configuration Data

ESDU 98005
See Table 11.3
Index of Geometries
0.3 See Section 5.1 0.3

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU

·c )
FIGURE 5 CROSSFLOW, SINGLE PASS, MIXED/UNMIXED, ( M p smaller ON MIXED SIDE
ESDU 98005
TABLE 11.4
Crossflow
CRO-UNMIX/UNMIX
Single-pass
Infinite channels/tube rows in
both streams
·c )
(M p smaller in either stream


Unmixed/unmixed

Relationship between E , N TU and C*
ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5.

Asymptotic expression

E asymp = 1 .

Algebraic coefficients
0 1 2 3 4
a 1.0000 0.0000 0.0000
b –8.0303 41.3607 –85.1402 78.4532 –26.8626
c 100.0000
d –0.7007 1.9395 –2.4416 1.7539 –0.5991
g 0.4233 0.7017 –0.2189

32
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

CRO-UNMIX/UNMIX
0.9 0.9

0. 6
0. 7
0.8 0.8 0.8
C*
0.0 0. 9
0.1 1.0
ESDU Copyright material. For current status contact ESDU.

0.2
0.3 C*
0.7 0.7
0.4
0.5
E E

0.6 0.6
33

0.5 0.5
95% of Emax
Temperature meet
0.4 0.4

ESDU 98005
Configuration Data
See Table 11.4
Index of Geometries
0.3 0.3
See Section 4.1

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU

FIGURE 6 CROSSFLOW, SINGLE PASS, UNMIXED/UNMIXED


ESDU 98005
11.2 Crossflow, Multi-pass, Unmixed Flow in Exchanger – Counter-current

TABLE 11.5
Crossflow
2 Passes CRO-UNMIX-MP-CU-1
Infinite channels/tube rows
in both streams
·
( M c p ) smaller in either stream

All connections
Unmixed/unmixed
Mixed/unmixed
ESDU Copyright material. For current status contact ESDU.

Relationship between E , N TU and C*


The analytical procedure used to generate the data is described in Part 5 and Derivation 4.

Asymptotic expression

E asymp = 1 .

34
NTU

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10


1.0 1.0

CRO-UNMIX-MP-CU-1
0.9 0.9

0.6
0. 7
0.8 0 .8 0.8
C*
0.0 0.9
0.1 1 .0
ESDU Copyright material. For current status contact ESDU.

0.2
0.3 C*
0.7 0.7
0.4
0.5
E E

0.6 0.6
35

0.5 0.5
95% of Emax
Temperature meet
0.4 Configuration Data 0.4
See Table 11.5

ESDU 98005
Index of Geometries
See Section 5.2
0.3 0.3

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 7 TWO-PASS COUNTER-CURRENT CROSSFLOW, UNMIXED/MIXED BETWEEN PASSES, ( M p smaller IN EITHER STREAM
ESDU 98005
TABLE 11.6
Crossflow CRO-UNMIX-MP-CU-2
3 Passes
Infinite channels/tube rows
in both streams
·
( M c p ) smaller in either stream

All connections
Unmixed/unmixed
Mixed/unmixed
ESDU Copyright material. For current status contact ESDU.

Relationship between E , N TU and C*


The analytical procedure used to generate the data is described in Part 5 and Derivation 4.

Asymptotic expression

E asymp = 1 .

36
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 *
1.0
C
CRO-UNMIX-MP-CU-2 0
0.1 0. 6
0.2 0. 7
0.9 0.3 0.9
0.4 0. 8
0.5 0. 9
1 .0
0.8 0.8
C*
ESDU Copyright material. For current status contact ESDU.

0.7 0.7

E E

0.6 0.6
37

0.5 0.5
95% of Emax
Temperature meet

0.4 Configuration Data 0.4


See Table 11.6

ESDU 98005
Index of Geometries
See Section 5.2
0.3 0.3

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 8 THREE-PASS COUNTER-CURRENT CROSSFLOW, UNMIXED/UNMIXED BETWEEN PASSES, ( M p smaller IN EITHER STREAM
ESDU 98005
11.3 Crossflow, Multi-pass, Unmixed Flow in Exchanger – Co-current

TABLE 11.7
Crossflow
2 Passes
CRO-UNMIX-MP-CO-1
Infinite channels/tube rows
in both streams
·c )
(M p smaller in either stream


Unmixed/unmixed
Mixed/mixed
ESDU Copyright material. For current status contact ESDU.

Relationship between E , N TU and C*


The analytical procedure used to generate the data is described in Part 5 and Derivation 4.

Asymptotic expression
Since the curves pass through a maximum before reaching the asymptotic value, the following data are provided
to assist their use.

C∗ E max E for N TU = 100 Easymp

0 1 1 1
0.1 0.91 0.9000 0.9
0.2 0.83 0.8000 0.8
0.3 0.77 0.7000 0.7
0.4 0.71 0.6000 0.6
0.5 0.67 0.5000 0.5
0.6 0.63 0.4007 0.4
0.7 0.59 0.3061 0.3
0.8 0.56 0.2254 0.2
0.9 0.53 0.1694 0.1
1 0.50 0.1448 0

38
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

CRO-UNMIX-MP-CO-1
0.9 0.9
C*
0.0
0.1
0.2
0.8 0.3 0.8
0.4
0.5
ESDU Copyright material. For current status contact ESDU.

0.7 0.7

E E
0.6

0.6 0.7 0.6


0.8
0.9
39

1.0
0.5 0.5
*
C

0.4 0.4
No
No local temperature
local temperature crossmeet

ESDU 98005
95% of Emax

0.3 Configuration Data 0.3


See Table 11.7
Index of Geometries
See Section 5.3
0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
FIGURE 9 TWO-PASS CROSSFLOW WITH CO-CURRENT FLOW, BOTH STREAMS MIXED BETWEEN PASSES
ESDU 98005
TABLE 11.8
Crossflow
2 Passes
CRO-UNMIX-MP-CO-2
Infinite channels/tube rows in
both stream
·c )
(M p smaller in stream
unmixed between passes

Unmixed/unmixed
Mixed/unmixed
ESDU Copyright material. For current status contact ESDU.

Relationship between E , N TU and C*


The analytical procedure used to generate the data is described in Part 5 and Derivation 4.

Asymptotic expression
Since the curves pass through a maximum before reaching the asymptotic value, the following data are provided
to assist their use.

C∗ E max E for N TU = 100


0 1 1
0.1 0.885 0.347
0.2 0.808 0.249
0.3 0.745 0.204
0.4 0.692 0.177
0.5 0.649 0.158
0.6 0.610 0.145
0.7 0.576 0.134
0.8 0.544 0.130
0.9 0.517 0.128
1.0 0.493 0.127

Algebraic coefficients
0 1 2 3 4
a –0.0027 –0.0265 0.0131
b 0.5600 –0.5567 –1.0433 2.3217 –0.7717
c 100.0000
d –0.2600 0.5983 –4.7800 6.5767 –4.1250
g 0 0 0

40
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0
0
CRO-UNMIX-MP-CO-2
0.9 0.1 0.9

0.2
0.8 0.8

0.3
ESDU Copyright material. For current status contact ESDU.

0.4 C*
0.7 0.7

0.5
E E
0.6
0.6 0.6
0.7
0.8
0.9
41

0.5 0.5
1.0

0.4 0.4

No
Nolocal temperature
local temperature meetmeet

ESDU 98005
0.3 Configuration Data 0.3
See Table 11.8
95% of Emax Index of Geometries
See Section 5.3
0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 10 TWO-PASS CROSSFLOW WITH CO-CURRENT FLOW, ONE STREAM MIXED, THE OTHER UNMIXED BETWEEN PASSES, ( M p smaller
IN UNMIXED STREAM
ESDU 98005
TABLE 11.9
Crossflow
CRO-UNMIX-MP-CO-3
2 Passes
Infinite channels/tube rows
in both streams
·c )
(M p smaller in stream mixed
between passes

Unmixed/unmixed
Mixed/unmixed
ESDU Copyright material. For current status contact ESDU.

Relationship between E , N TU and C*


The analytical procedure used to generate the data is described in Part 5 and Derivation 4.

Asymptotic expression
Since the curves pass through a maximum before reaching the asymptotic value, the following data are provided
to assist their use.

C∗ E max E for N TU = 100 E asymp

0 1 1 1
0.1 0.909 0.9000 0.9
0.2 0.832 0.8000 0.8
0.3 0.767 0.7000 0.7
0.4 0.712 0.6000 0.6
0.5 0.662 0.5000 0.5
0.6 0.621 0.4007 0.4
0.7 0.582 0.3006 0.3
0.8 0.548 0.2243 0.2
0.9 0.518 0.1642 0.1
1 0.493 0.1267 0

Algebraic coefficients
0 1 2 3 4
a –0.1575 0.2726 –0.1312
b 6.8700 –30.0608 54.9996 –47.5842 16.1154
c 100.0000
d –1.0000 –0.0100 0.0000 –0.0100 –0.5000
g 0.0 0.0 0.0

42
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0
*
C 0
CRO-UNMIX-MP-CO-3
0.1
0.9 0.9

0.2

0.8 0.8
0.3
ESDU Copyright material. For current status contact ESDU.

0.4
0.7 0.7
0.5
E E
0.6
0.6 0.7 0.6

0.8
0.9
43

0.5 0.5
1.0

C*

0.4 0.4
NoNo
local
localtemperature meet
temperature meet

ESDU 98005
0.3 Configuration Data 0.3
See Table 11.9
95% of Emax Index of Geometries
See Section 5.3
0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 11 TWO-PASS CROSSFLOW WITH CO-CURRENT FLOW, ONE STREAM MIXED, THE OTHER UNMIXED BETWEEN PASSES, ( M p smaller
IN MIXED STREAM
ESDU 98005
TABLE 11.10
Crossflow
CRO-UNMIX-MP-CO-4
2 Passes
Infinite channels/tube rows in
both streams
·c )
(M p smaller in either stream


Unmixed/unmixed
Unmixed/unmixed
Relationship between E , N TU and C*
ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5 and Derivation 4.

Asymptotic expression
Since the curves pass through a maximum before reaching the asymptotic value, the following data are provided
to assist their use.

C∗ E max E for N TU = 100 E asymp

0 1 1 0
0.1 0.883 0.3478 0
0.2 0.805 0.2488 0
0.3 0.745 0.2039 0
0.4 0.689 0.1768 0
0.5 0.644 0.1582 0
0.6 0.605 0.1445 0
0.7 0.570 0.1337 0
0.8 0.535 0.1248 0
0.9 0.509 0.1167 0
1 0.482 0.1087 0

Algebraic coefficients
0 1 2 3 4
a –0.1590 0.2744 –0.1320
b 6.8600 –30.0708 54.9996 –47.5942 16.4554
c 100
d –1.0100 –0.0400 –0.2000 –0.1000 –1.4000
g 0 0 0

44
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0
0
CRO-UNMIX-MP-CO-4
C*
0.9 0.9
0.1

0.2
0.8 0.8

0.3
ESDU Copyright material. For current status contact ESDU.

0.7 0.4 0.7

0.5
E E
0.6
0.6 0.6
0.7
0.8
45

0.9
0.5 0.5
1.0

C*

0.4 0.4
NoNolocal
localtemperature meet
temperature meet

ESDU 98005
Configuration Data
0.3 See Table 11.10 0.3

95% of Emax Index of Geometries


See Section 5.3

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
FIGURE 12 TWO-PASS CROSSFLOW WITH CO-CURRENT FLOW, BOTH STREAMS UNMIXED BETWEEN PASSES
ESDU 98005
11.4 Crossflow, Tubular Configurations, Single-pass

TABLE 11.11
Crossflow CRO-TUBE-SP-1
Single pass
1 Tube row
·c )
(M p smaller inside tubes


Mixed/Unmixed
Equivalent to
– CRO-UNMIX/MIX-2

Relationship between E , N TU and C∗


ESDU Copyright material. For current status contact ESDU.

– ( 1 – exp [ – N TU C∗ ] )
E = 1 – exp -------------------------------------------------------- .
C∗

Asymptotic expression
E asymp = 1 – exp [ – 1/C∗ ] .

C∗ E asymp C∗ E asymp
0 1 0.6 0.81
0.1 1 0.7 0.76
0.2 0.99 0.8 0.71
0.3 0.96 0.9 0.67
0.4 0.92 1 0.63
0.5 0.86

Algebraic coefficients
0 1 2 3 4
a 1.3249 –1.8438 0.7831
b –7.1739 37.6000 –73.1022 63.8124 –20.9271
c 100
d –0.2330 –0.8090 2.8338 –3.3782 1.3972
g 0.3572 0.8252 –0.2785

46
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

CRO-TUBE-SP-1
(Also CRO-UNMIX/MIX-2)
0.9 0.9

C* 0.6
0.8 0.0 0.8
0.1
0.7
0.2
ESDU Copyright material. For current status contact ESDU.

0.3
0.4 0.8
0.7 0.5 0.7
0.9
E 1.0 E
*
0.6 C 0.6
47

0.5 0.5
95% of Emax
Temperature meet
0.4 0.4
Configuration Data

ESDU 98005
See Table 11.11
Index of Geometries
0.3 See Section 5.4 0.3

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·
FIGURE 13 CROSSFLOW, SINGLE-PASS, ONE TUBE ROW, ( M c p ) smaller INSIDE TUBES
ESDU 98005
TABLE 11.12
Crossflow CRO-TUBE-SP-2
Single pass
1 Tube row
·c )
(M p smaller outside tubes


Mixed/Unmixed
Equivalent to
– CRO-UNMIX/MIX-1

Relationship between E , N TU and C∗


ESDU Copyright material. For current status contact ESDU.

1 – exp [ – C∗ ( 1 – exp [ – N TU ] ) ]
E = ---------------------------------------------------------------------------------- .
C∗

Asymptotic expression
1 – exp [ – C∗ ]
E asymp = ------------------------------------ .
C∗
C∗ E asymp
0 1
0.1 0.95
0.2 0.91
0.3 0.86
0.4 0.82
0.5 0.79
0.6 0.75
0.7 0.72
0.8 0.69
0.9 0.66
1.0 0.63

Algebraic coefficients
0 1 2 3 4
a 0.4939 –0.3019 0.0722
b 0.2886 2.1267 –6.6072 6.7717 –2.3616
c 100
d –0.6400 0.6117 –0.7777 1.2072 –0.5900
g 0.3749 0.7021 –0.2012

48
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

CRO-TUBE-SP-2
0.9 (Also CRO-UNMIX/MIX-1) 0.9

0.8 C* 0.8
0.0
0.1 0.6
0.2
ESDU Copyright material. For current status contact ESDU.

0.3 0.7
0.7 0.4 0.8 0.7
0.5
0.9
E 1.0 E
*
C
0.6 0.6
49

0.5 0.5
95% of Emax
Temperature meet
0.4 0.4

ESDU 98005
Configuration Data
See Table 11.12
0.3 Index of Geometries 0.3
See Section 5.4

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·
FIGURE 14 CROSSFLOW, SINGLE-PASS, ONE TUBE ROW, ( M c p ) smaller OUTSIDE TUBES
ESDU 98005
TABLE 11.13
Crossflow CRO-TUBE-SP-3
Single Pass
2 Tube Rows
·c )
(M p smaller inside tubes


Part-mixed/Unmixed

Relationship between E , N TU and C∗
ESDU Copyright material. For current status contact ESDU.

2
 K  – 2K
E = 1 –  1 + ------- exp ---------- ,
 C  ∗ C∗

– N TU C∗
where K = 1 – exp  --------------------- .
 2 
Asymptotic expression

E asymp = 1 –  1 + ------- exp ------- .


1 –2
 C∗ C∗
C∗ E asymp
0 1
0.1 1
0.2 1
0.3 0.99
0.4 0.98
0.5 0.95
0.6 0.90
0.7 0.86
0.8 0.82
0.9 0.77
1 0.73

Algebraic coefficients
0 1 2 3 4
a 1.3424 –1.1815 0.2977
b –3.5727 10.6147 –9.2380 1.2380 1.1198
c 10
d –0.3136 0.0388 –0.4773 –0.4582 0.1650
g 0.4076 0.7360 –0.2346

50
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

CRO-TUBE-SP-3
0.9 0.9

0.8 0. 6 0.8
C* 0 .7
0.0
0.1 0.8
ESDU Copyright material. For current status contact ESDU.

0.2 0.9
0.7 0.3 0.7
0.4 1.0
0.5 C*
E E

0.6 0.6
51

0.5 0.5
95% of Emax
Temperature meet
0.4 0.4

Configuration Data

ESDU 98005
See Table 11.13
Index of Geometries
0.3 0.3
See Section 5.4

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU

·c )
FIGURE 15 CROSSFLOW, SINGLE-PASS, TWO TUBE ROWS, ( M p smaller INSIDE TUBES
ESDU 98005
TABLE 11.14
Crossflow CRO-TUBE-SP-4
Single pass
2 Tube rows
·c )
(M p smaller outside tubes


Part-mixed/unmixed

Relationship between E , N TU and C∗
ESDU Copyright material. For current status contact ESDU.

1 2
E = ------- ( 1 – ( 1 + C∗ K ) exp [ – 2KC∗ ] ) ,
C ∗
– N TU
where K = 1 – exp  -------------- .
 2 
Asymptotic expression
1 – ( 1 + C∗ ) exp [ – 2C∗ ]
E asymp = --------------------------------------------------------------- .
C∗
C∗ E asymp C∗ E asymp
0 1.00 0.6 0.86
0.1 0.99 0.7 0.83
0.2 0.98 0.8 0.80
0.3 0.96 0.9 0.76
0.4 0.93 1 0.73
0.5 0.90

Algebraic coefficients
0 1 2 3 4
a 1.0073 –0.7241 0.1755
b –5.3370 26.1152 –48.2362 40.4877 –12.8809
c 10
d 0.0186 –3.7086 10.4954 –10.7689 3.8756
g 0.4117 0.7023 –0.2146

52
NTU

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10


1.0 1.0

CRO-TUBE-SP-4
0.9 0.9

C*
0.8 0. 6 0.8
0.0
0.1 0 .7
0.2
ESDU Copyright material. For current status contact ESDU.

0.8
0.3
0.4 0. 9
0.7 0.7
0.5 1.0

E C*
E

0.6 0.6
53

0.5 0.5
95% of Emax
Temperature meet
0.4 0.4

ESDU 98005
Configuration Data
See Table 11.14
Index of Geometries
0.3 0.3
See Section 5.4

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 16 CROSSFLOW, SINGLE-PASS, TWO TUBE ROWS, ( M p smaller OUTSIDE TUBES
ESDU 98005
TABLE 11.15
Crossflow CRO-TUBE-SP-5
Single pass
3 Tube rows
·c )
(M p smaller inside tubes


Part-mixed/unmixed

Relationship between E , N TU and C∗
ESDU Copyright material. For current status contact ESDU.

2 4
 K (3 – K) 3K  – 3K
E = 1 –  1 + --------------------------- + ------------- exp ---------- ,
 ∗ C∗
2C∗ 
C 2

– N TU C∗
where K = 1 – exp  --------------------- .
 3 

Asymptotic expression
 1 3  –3
E asymp = 1 –  1 + ------- + ------------- exp ------- .
 C∗ 2C∗  2 C∗

C∗ E asymp C∗ E asymp
0 1 0.6 0.94
0.1 1 0.7 0.90
0.2 1 0.8 0.86
0.3 1 0.9 0.82
0.4 0.99 1 0.78
0.5 0.97

Algebraic coefficients
0 1 2 3 4
a 1.2588 –0.7583 0.0595
b –3.7696 10.0971 –7.3076 –0.5522 1.6290
c 10
d –0.4665 1.0873 –2.6419 3.2634 –1.2845
g 0.4242 0.6931 –0.2135

54
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

CRO-TUBE-SP-5
0.9 0.9
0. 6
0.7

0.8 0.8 0.8


*
C 0.9
0.0
1.0
ESDU Copyright material. For current status contact ESDU.

0.1
0.2 C*
0.7 0.7
0.3
0.4
This page Amendment C

E 0.5
E

0.6 0.6
55

0.5 0.5
95% of Emax
Temperature meet
0.4 0.4

ESDU 98005
Configuration Data
See Table 11.15
0.3 Index of Geometries 0.3
See Section 5.4

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU

·c )
FIGURE 17 CROSSFLOW, SINGLE-PASS, THREE TUBE ROWS, ( M p smaller INSIDE TUBES
ESDU 98005
TABLE 11.16
Crossflow CRO-TUBE-SP-6
Single pass
3 Tube rows
·c )
(M p smaller outside tubes


Part-mixed/unmixed

Relationship between E , N TU and C∗
ESDU Copyright material. For current status contact ESDU.

2 4
1  2 3C∗ K 
E = ------- 1 –  1 + C∗ K ( 3 – K ) + -------------------- exp [ – 3KC∗ ] ,
C∗  2 

– N TU
where K = 1 – exp  -------------- .
 3 
Asymptotic expression
2
1  3C∗ 
E asymp = ------- ( 1 – exp [ – 3C∗ ] )  1 + 2C∗ + ------------- .
C∗  2 

C∗ E asymp C∗ E asymp
0 1 0.6 0.91
0.1 1 0.7 0.88
0.2 0.99 0.8 0.85
0.3 0.98 0.9 0.81
0.4 0.96 1 0.78
0.5 0.94

Algebraic coefficients
0 1 2 3 4
a 1.1055 –0.5967 0.0432
b –3.3972 13.1146 –20.6168 15.9542 –4.9552
c 10
d –0.3394 0.6387 –2.4577 4.2374 –2.1245
g 0.4184 0.6936 –0.2116

56
NTU

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10


1.0 1.0

CRO-TUBE-SP-6
0.9 0.9
0.6
0.7
0.8 *
0.8 0.8
C
0.0 0.9
1.0
ESDU Copyright material. For current status contact ESDU.

0.1
0.2 C*
0.7 0.3 0.7
0.4
0.5
E E

0.6 0.6
57

0.5 0.5
95% of Emax
Temperature meet
0.4 0.4

ESDU 98005
Configuration Data
See Table 11.16
0.3 Index of Geometries 0.3
See Section 5.4

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 18 CROSSFLOW, SINGLE-PASS, THREE TUBE ROWS, ( M p smaller OUTSIDE TUBES
ESDU 98005
TABLE 11.17
Crossflow CRO-TUBE-SP-7
Single pass
4 Tube rows
·c )
(M p smaller inside tubes


Part-mixed/unmixed

Relationship between E , N TU and C∗
ESDU Copyright material. For current status contact ESDU.

2 2 4 6
 K ( 6 – 4 K + K ) 4K ( 2 – K ) 8K  – 4K
E = 1 –  1 + ----------------------------------------- + ------------------------------ + ------------- exp ---------- ,
 ∗ C∗
3C∗ 
2 3
C C∗
– N TU C∗
where K = 1 – exp  --------------------- .
 4 

Asymptotic expression
 3 4 8  –4
E asymp = 1 –  1 + ------- + --------- + ------------- exp ------- .
 ∗ C∗
3C∗ 
2 3
C C∗

C∗ E asymp C∗ E asymp
0.0 1 0.6 0.96
0.1 1 0.7 0.93
0.2 1 0.8 0.89
0.3 1 0.9 0.85
0.4 1 1.0 0.80
0.5 0.99

Algebraic coefficients
0 1 2 3 4
a 1.1014 –0.1440 –0.3480
b –5.0928 23.6681 –46.6196 42.9979 –14.8784
c 10
d –0.6945 2.6625 –4.8442 3.4573 –0.6160
g 0.4204 0.7295 –0.2377

58
NTU

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10


1.0 1.0

CRO-TUBE-SP-7
0.9 0.9

0.6
0. 7
0.8 * 0.8 0.8
C
0.0 0. 9
0.1
ESDU Copyright material. For current status contact ESDU.

0.2 1.0
0.7 0.3 C* 0.7
0.4
0.5
E E

0.6 0.6
59

0.5 0.5
95% of Emax
Temperature meet
0.4 0.4

ESDU 98005
Configuration Data
See Table 11.17
Index of Geometries
0.3 See Section 5.4 0.3

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 19 CROSSFLOW, SINGLE-PASS, FOUR TUBE ROWS, ( M p smaller INSIDE TUBES
ESDU 98005
TABLE 11.18
Crossflow CRO-TUBE-SP-8
Single pass
4 Tube rows
·c )
(M p smaller outside tubes


Part-mixed/unmixed

Relationship between E , N TU and C∗
ESDU Copyright material. For current status contact ESDU.

6 3
1  2 2 2 4 8K C∗ 
E = ------- 1 –  1 + C∗ K ( 6 – 4K + K ) + 4C∗ K ( 2 – K ) + -------------------- exp [ – 4C∗ K ] ,
C∗  3 

– N TU
where K = 1 – exp  -------------- .
 4 
Asymptotic expression
3
1  2 8C∗ 
E asymp = ------- 1 –  1 + 3C∗ + 4C∗ + ------------- exp [ – 4C∗ ] .
C∗  3 

C∗ E asymp C∗ E asymp
0 1 0.6 0.94
0.1 1 0.7 0.91
0.2 1 0.8 0.88
0.3 0.99 0.9 0.84
0.4 0.98 1 0.80
0.5 0.96

Algebraic coefficients
0 1 2 3 4
a 1.1017 –0.3813 –0.1111
b –4.1175 17.9137 –33.5078 30.2323 –10.4447
c 10
d –0.5190 2.2081 –6.0733 6.9594 –2.6102
g 0.4049 0.7506 –0.2474

60
NTU

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10


1.0 1.0

CRO-TUBE-SP-8
0.9 0.9
0. 6
0.7
0. 8
0.8 * 0.8
C 0.9
0.0
0.1 1.0
ESDU Copyright material. For current status contact ESDU.

0.2
C*
0.7 0.3 0.7
0.4
0.5
E E

0.6 0.6
61

0.5 0.5
95% of Emax
Temperature meet
0.4 0.4
Configuration Data

ESDU 98005
See Table 11.18
Index of Geometries
See Section 5.4
0.3 0.3

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 20 CROSSFLOW, SINGLE-PASS, FOUR TUBE ROWS, ( M p smaller OUTSIDE TUBES
ESDU 98005
TABLE 11.19
Crossflow CRO-TUBE-SP-9
Single pass
>4 Tube rows
·c )
(M p smaller in either stream


Unmixed/unmixed
Equivalent to
– CRO-UNMIX/UNMIX

Relationship between E , N TU and C∗


ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5 and Derivation 4.

Asymptotic expression
E asymp = 1 .

Algebraic coefficients
0 1 2 3 4
a 1.0000 0.0000 –0.0000
b –8.0303 41.3607 –85.1420 78.4532 –26.8626
c 100.0000
d –0.7007 1.9395 –2.4416 1.7539 –0.5991
g 0.4233 0.7017 –0.2189

62
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

CRO-TUBE-SP-9
0.9 (Also CRO-UNMIX/UNMIX) 0.9

0. 6
0. 7
0.8 * 0.8 0.8
C
0.0 0. 9
0.1 1.0
ESDU Copyright material. For current status contact ESDU.

0.2
0.3 C*
0.7 0.7
0.4
0.5
E E

0.6 0.6
63

0.5 0.5
95% of Emax
Temperature meet
0.4 0.4

ESDU 98005
Configuration Data
See Table 11.19
0.3 Index of Geometries 0.3
See Section 5.4

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 21 CROSSFLOW, SINGLE-PASS, MORE THAN FOUR TUBE ROWS, ( M p smaller IN EITHER STREAM
ESDU 98005
11.5 Crossflow, Tubular Configurations, Multi-pass – *Counter-current

TABLE 11.20
Crossflow CRO-TUBE-MP-CU-1
2 Passes
2 Tube rows per pass
·c )
(M p smaller inside tubes
All connections
Part-mixed/unmixed

Relationship between E , N TU and C∗ . (See Derivation 8.)


ESDU Copyright material. For current status contact ESDU.

1
E = 1 – --- ,
A
2 3 3 2
K  K K 
exp ------- +  K – ------ + ------  1 – exp -------  + -------  2 – ---- + -------
4K K K 4K
C∗  2 8   C∗  C∗  2 C∗
where A = -------------------------------------------------------------------------------------------------------------------------------------------------------------------- .
2 2
 K 
 1 + -------
 C∗
– N TU C∗
and K = 1 – exp  --------------------- .
 4 
Asymptotic expression
2
1 ( 1 + C∗ )
E asymp = 1 – --------- ----------------------------------------------------------------------------------------------------------- .
C∗
2
3 --- + -------
1
 2 C∗
exp ------- + ---  1 – exp -------  + ------------------------
4 5 4
C∗ 8 C∗  C∗

C∗ E max C∗ Easymp
0 1 0.6 0.976
0.1 1 0.7 0.950
0.2 1 0.8 0.915
0.3 1 0.9 0.874
0.4 1 1 0.831
0.5 0.992

Algebraic coefficients
0 1 2 3 4
a 0.9924 0.6684 –0.9989
b –2.9794 15.3988 –32.4694 30.5203 –10.3523
c 100.0000
d –0.6209 1.6255 –1.4339 0.7541 –0.3819
g 0.0000 0.0000 0.0000

*
A counter-current arrangement is defined as one where the tubeside inlet is located adjacent to the exit of the crossflow stream.

64
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0
*
C
CRO-TUBE-MP-CU-1 0.0
0.1
0.2 0.6
0.9 0.9
0.3 0. 7
0.4
0.5 0.8
0.9
0.8 0.8
1. 0
C*
ESDU Copyright material. For current status contact ESDU.

0.7 0.7

E E
No local temperature meet
0.6 No local temperature meet 0.6
65

0.5 0.5

0.4 0.4

Configuration Data

ESDU 98005
See Table 11.20
Index of Geometries
0.3 See Section 5.5 0.3

95% of Emax

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 22 TWO-PASS COUNTER-CURRENT CROSSFLOW, TWO TUBE ROWS/PASS, ALL PASS CONNECTIONS, ( M p smaller INSIDE TUBES
ESDU 98005
TABLE 11.21
Crossflow CRO-TUBE-MP-CU-2
2 Passes
2 Tube rows per pass
·c )
(M p smaller outside tubes

All connections
Part-mixed/unmixed

Relationship between E , N TU and C∗
ESDU Copyright material. For current status contact ESDU.

E = -------  1 – --- ,
1 1
C∗  A
2 3
exp [ 4C∗ K ] +  K – ------ + ------ ( 1 – exp [ 4C∗ K ] ) + C∗ K  2 – ---- + C∗ K 
K K 3 K 2
 2 8   2 
where A = ---------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- .
2 2
( 1 + C∗ K )
– N TU
and K = 1 – exp  -------------- .
 4 
Asymptotic expression
 2 
1  ( 1 + C∗ ) 
E asymp = -------  1 – ----------------------------------------------------------------------------------------------------------------------- .
C∗  
exp [ 4C∗ ] + --- ( 1 – exp [ 4C∗ ] ) + C∗  --- + C∗
5 3
 8  2  

C∗ E max C∗ Easymp
0 1 0.6 0.958
0.1 1 0.7 0.933
0.2 0.999 0.8 0.903
0.3 0.996 0.9 0.868
0.4 0.989 1 0.831
0.5 0.976

Algebraic coefficients
0 1 2 3 4
a 1.0477 –0.1019 –0.2837
b –1.4186 6.1210 –12.2939 12.7271 –5.0080
c 100
d –0.2034 –0.3194 1.7244 –2.6913 1.4242
g 0.0000 0.0000 0.0000

66
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0
C*
CRO-TUBE-MP-CU-2 0.0
0.1
0.9 0.2 0.6 0.9
0.3 0. 7
0.4
0.5 0.8
0.9
0.8 0.8
1.0
C*
ESDU Copyright material. For current status contact ESDU.

0.7 0.7

E E
No local temperature
No local temperature meet
meet
0.6 0.6
67

0.5 0.5

0.4 0.4

ESDU 98005
Configuration Data
See Table 11.21
0.3
Index of Geometries 0.3
See Section 5.5
95% of Emax

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 23 TWO-PASS COUNTER-CURRENT CROSSFLOW, TWO TUBE ROWS/PASS, ALL PASS CONNECTIONS, ( M p smaller OUTSIDE TUBES
ESDU 98005
TABLE 11.22
Crossflow CRO-TUBE-MP-CU-3
2 Passes
3 Tube rows per pass
·c )
(M p smaller in either stream

All connections
Part-mixed/unmixed

Relationship between E , N TU and C∗
The analytical procedure used to generate the data is described in Part 5.
ESDU Copyright material. For current status contact ESDU.

Asymptotic expression

C∗ E asymp C∗ E asymp
0 1 0.6 1
0.1 1 0.7 1
0.2 1 0.8 1
0.3 1 0.9 0.999
0.4 1 1 0.999
0.5 1

Algebraic coefficients
0 1 2 3 4
a 1 0 0
b –0.9850 1.8183 –0.4777 –1.1933 0.7097
c 1
d –0.25 –0.3625 2.3305 –2.5457 0.8268
g 0 0 0

68
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

CRO-TUBE-MP-CU-3 C*
0.0
0.9 0.1 0.9
0.2
0.3
0.4
0.5
0.8 0.8
0. 6
0.7
0. 8
ESDU Copyright material. For current status contact ESDU.

0. 9
0.7 0.7
1.0
C*
E E

0.6 0.6
69

0.5 0.5

95% of Emax
NoNo
local
localtemperature meet
temperature meet
0.4 0.4

ESDU 98005
Configuration Data
See Table 11.22
0.3 Index of Geometries 0.3
See Section 5.5

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 24 TWO-PASS COUNTER-CURRENT CROSSFLOW, THREE TUBE ROWS/PASS, ALL PASS CONNECTIONS, ( M p smaller IN EITHER
STREAM
ESDU 98005
TABLE 11.23
Crossflow CRO-TUBE-MP-CU-4
2 Passes
>3 tube rows per pass
·c )
(M p smaller in either stream

All connections
Unmixed/unmixed

Relationship between E , N TU and C∗
The analytical procedure used to generate the data is described in Part 5.
ESDU Copyright material. For current status contact ESDU.

Asymptotic expression
E asymp = 1 .

70
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0
C*
CRO-TUBE-MP-CU-4 0.0
0.1 0.6
0.9 0.2 0.9
0.3 0. 7
0.4 0. 8
0.5
0. 9
0.8 1.0 0.8
*
C
ESDU Copyright material. For current status contact ESDU.

0.7 0.7

E E
Nolocal
No local temperature
temperature cross
meet
0.6 0.6
71

0.5 0.5

0.4 0.4

ESDU 98005
Configuration Data
See Table 11.23
0.3 Index of Geometries 0.3
See Section 5.5
95% of Emax

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 25 TWO-PASS COUNTER-CURRENT CROSSFLOW, > THREE TUBE ROWS/PASS, ALL PASS CONNECTIONS, ( M p smaller IN EITHER
STREAM
ESDU 98005
TABLE 11.24
Crossflow CRO-TUBE-MP-CU-5
3 Passes
2 Tube rows per pass
·c )
(M p smaller in either stream

All connections
Part-mixed/unmixed

Relationship between E , N TU and C∗
The analytical procedure used to generate the data is described in Part 5.
ESDU Copyright material. For current status contact ESDU.

Asymptotic expression
E asymp = 1 .

Algebraic coefficients
0 1 2 3 4
a 1.0000 0.0000 0.0000
b –1.1564 4.8910 –8.4500 6.3933 –1.7489
c 1.0000
d –0.4733 0.3629 2.7742 –4.9884 2.3556
g 0.000 0.0000 0.0000

72
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

CRO-TUBE-MP-CU-5
C*
0.0 0 .6
0.9 0.9
0.1 0 .7
0.2
0 .8
0.3
0.4 0 .9
0.8 0.5 0.8
1.0
C*
ESDU Copyright material. For current status contact ESDU.

0.7 0.7

E No local temperature meet E

0.6 0.6
73

0.5 0.5

0.4 95% of Emax 0.4

ESDU 98005
Configuration Data
See Table 11.24
0.3 Index of Geometries 0.3
See Section 5.5

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 26 THREE-PASS COUNTER-CURRENT CROSSFLOW, TWO TUBE ROWS/PASS, ALL PASS CONNECTIONS, ( M p smaller IN EITHER
STREAM
ESDU 98005

TABLE 11.25
Crossflow CRO-TUBE-MP-CU-6
3 Passes
>2 Tube rows per pass
·c )
(M p smaller in either stream

All connections
Unmixed/unmixed

Relationship between E , N TU and C∗
ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5.

Asymptotic expression
E asymp = 1 .

Algebraic coefficients
0 1 2 3 4
a 1 0 0
b –2.0356 9.9306 –19.6277 17.5799 –5.9062
c 10
d –0.6812 1.6827 –1.7804 1.4455 –0.6484
g 0 0 0

74
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

CRO-TUBE-MP-CU-6 C*
0.0
0.9 0.1 0.9
0.2
0.6
0.3
0.4 0. 7
0.5 0.8
0.8 0.8
0. 9
1 .0
C*
ESDU Copyright material. For current status contact ESDU.

0.7 0.7

E E
NoNolocal
localtemperature meet
temperature meet
0.6 0.6
75

0.5 0.5

95% of Emax
0.4 0.4

ESDU 98005
Configuration Data
See Table 11.25
0.3 0.3
Index of Geometries
See Section 5.5

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 27 THREE-PASS COUNTER-CURRENT CROSSFLOW, > TWO TUBE ROWS/PASS, ALL PASS CONNECTIONS, ( M p smaller IN EITHER
STREAM
ESDU 98005
TABLE 11.26
Crossflow CRO-TUBE-MP-CU-7
4 Passes
>1 Tube row per pass
·c )
(M p smaller in either stream

All connections
Unmixed/unmixed

Relationship between E , N TU and C∗
The analytical procedure used to generate the data is described in Part 5.
ESDU Copyright material. For current status contact ESDU.

Asymptotic expression
E asymp = 1 .

Algebraic coefficients
0 1 2 3 4
a 1 0 0
b –0.7754 2.9826 –5.0793 4.2971 –1.4591
c 10
d –0.66 1.1216 –0.1676 –0.2958 0.0287
g 0 0 0

76
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

CRO-TUBE-MP-CU-7 C* 0. 6
0.0 0 .7
0.9 0.1 0.9
0.2 0 .8
0.3 0.9
0.4
0.5 1.0
0.8 0.8
C*
ESDU Copyright material. For current status contact ESDU.

0.7 0.7

E E
This page Amendment A

Notemperature
No local local temperature meet
meet
0.6 0.6
77

0.5 0.5

0.4 0.4

95% of Emax

ESDU 98005
Configuration Data
See Table 11.26
0.3 0.3
Index of Geometries
See Section 5.5

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU

·c )
FIGURE 28 FOUR-PASS COUNTER-CURRENT CROSSFLOW, > ONE TUBE ROW/PASS, ALL PASS CONNECTIONS, ( M p smaller IN EITHER
STREAM
ESDU 98005
11.6 Crossflow, Tubular Exchangers, Multi-pass – *Co-current

TABLE 11.27
Crossflow CRO-TUBE-MP-CO-1
2 Passes
2 Tube rows per pass
·c )
(M p smaller inside tubes

Header
Part-mixed/unmixed

Relationship between E , N TU and C∗
ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5.

Asymptotic expression
1
E asymp = 1 – exp – ------- .
C∗
Since the curves pass through a maximum before reaching the asymptotic value, the following data
are provided to assist their use.
C∗ E maxE for N = 100 ETU asymp
0 1 1 1
0.1 0.885 0.407 0.375
0.2 0.808 0.378 0.375
0.3 0.746 0.375 0.375
0.4 0.694 0.375 0.375
0.5 0.649 0.374 0.374
0.6 0.610 0.373 0.373
0.7 0.576 0.371 0.371
0.8 0.545 0.368 0.368
0.9 0.517 0.364 0.364
1 0.492 0.359 0.359

Algebraic coefficients
0 1 2 3 4
a –0.1590 0.2744 –0.1320
b 6.8700 –30.0408 55.0096 –47.5742 16.1454
c 100
d –1 –0.0300 0 0 –0.7000
g 0.1317 0.9841 0.2780

*
A co-current arrangement is defined as one where the tubeside inlet is located adjacent to the inlet of the crossflow stream.

78
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

CRO-TUBE-MP-CO-1
0.9 0.9

0.8 C* 0.8
0.0

0.1
ESDU Copyright material. For current status contact ESDU.

0.7 0.2 0.7

0.3
E E
0.4 0.6
0.6 0.6
0.5 0.7
0.8
0.9
79

0.5 1.0 0.5


95% of Emax *
C
Temperature meet

0.4 0.4

ESDU 98005
Configuration Data
0.3 See Table 11.27 0.3
Index of Geometries
See Section 5.6

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 29 TWO-PASS CO-CURRENT CROSSFLOW, TWO TUBE ROWS/PASS, MIXED BETWEEN PASSES, ( M p smaller INSIDE TUBES
ESDU 98005
TABLE 11.28
Crossflow CRO-TUBE-MP-CO-2
2 Passes
2 Tube rows per pass
·c )
(M p smaller outside tubes

Header
Part-mixed/unmixed

Relationship between E , N TU and C∗
ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5.

Asymptotic expression
Since the curves pass through a maximum before reaching the asymptotic value, the following data
are provided to assist their use.
C∗ E
max E for N = 100
TU E asymp
0 1 1 1
0.1 0.909 0.901 0.901
0.2 0.832 0.808 0.808
0.3 0.767 0.723 0.723
0.4 0.711 0.647 0.647
0.5 0.662 0.581 0.581
0.6 0.619 0.523 0.523
0.7 0.582 0.473 0.473
0.8 0.548 0.429 0.429
0.9 0.519 0.392 0.392
1 0.492 0.359 0.359

Algebraic coefficients
0 1 2 3 4
a –0.0041 –0.0263 0.0138
b 0.5700 –0.5467 –1.0033 2.3317 –0.7417
c 100
d –0.2700 0.5483 –4.1800 6.5767 –4.3250
g 0.2540 0.5858 –0.1101

80
NTU

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10


1.0 1.0

CRO-TUBE-MP-CO-2
0.9 0.9

C*
0.0

0.8 0.1 0.8

0.2
ESDU Copyright material. For current status contact ESDU.

0.3
0.7 0.7
0.4

E 0.5 E
0.6
0.6 0.6
0.7
0.8
81

0.9
0.5 1.0 0.5
95% of Emax *
C
Temperature meet
0.4 0.4

ESDU 98005
Configuration Data
0.3 See Table 11.28 0.3
Index of Geometries
See Section 5.6

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 30 TWO-PASS CO-CURRENT CROSSFLOW, TWO TUBE ROWS/PASS, MIXED BETWEEN PASSES, ( M p smaller OUTSIDE TUBES
ESDU 98005
TABLE 11.29
Crossflow CRO-TUBE-MP-CO-3
2 Passes
2 Tube rows per pass
·c )
(M p smaller inside tubes

Inverted U-tube
Part-mixed/unmixed

Relationship between E , N TU and C∗
ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5.

Asymptotic expression
Since the curves pass through a maximum before reaching the asymptotic value, the following data
are provided to assist their use.
C∗ E
max E for N = 100
TU E asymp
0 1 1 1
0.1 0.885 0.407 0.375
0.2 0.808 0.378 0.375
0.3 0.745 0.375 0.375
0.4 0.692 0.375 0.375
0.5 0.647 0.373 0.373
0.6 0.607 0.370 0.370
0.7 0.572 0.365 0.365
0.8 0.540 0.358 0.358
0.9 0.512 0.350 0.350
1 0.487 0.341 0.341

Algebraic coefficients
0 1 2 3 4
a –0.1595 0.2537 –0.1210
b 4.9700 –14.6217 12.6742 –0.1783 –2.3142
c 100
d –1 0 0 0 –1.2000
g 0.1062 1.0659 –0.3250

82
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

CRO-TUBE-MP-CO-3
0.9 0.9

C*
0.0
0.8 0.8
0.1

0.2
ESDU Copyright material. For current status contact ESDU.

0.7 0.7
0.3

E 0.4
E
0.5 0.6
0.6 0.6
0.7
0.8
0.9
83

0.5 1.0 0.5


95% of Emax *
C
Temperature meet
0.4 0.4

ESDU 98005
Configuration Data
See Table 11.29
0.3 Index of Geometries 0.3
See Section 5.6

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 31 TWO-PASS CO-CURRENT CROSSFLOW, TWO TUBE ROWS/PASS, INVERTED U-TUBES BETWEEN PASSES, ( M p smaller INSIDE
TUBES
ESDU 98005
TABLE 11.30
Crossflow CRO-TUBE-MP-CO-4
2 Passes
2 Tube rows per pass
·c )
(M p smaller outside tubes

Inverted U-tube
Part-mixed/unmixed

Relationship between E , N TU and C∗
ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5.

Asymptotic expression
Since the curves pass through a maximum before reaching the asymptotic value, the following data
are provided to assist their use.
C∗ E
max E for N = 100
TU E asymp
0 1 1 1
0.1 0.891 0.834 0.834
0.2 0.813 0.718 0.718
0.3 0.750 0.633 0.633
0.4 0.696 0.567 0.567
0.5 0.650 0.513 0.513
0.6 0.609 0.469 0.469
0.7 0.573 0.430 0.430
0.8 0.541 0.397 0.397
0.9 0.513 0.367 0.367
1 0.487 0.341 0.341

Algebraic coefficients
0 1 2 3 4
a –0.1222 0.1806 –0.0852
b 4.9500 –14.6217 12.6842 –0.1583 –2.3642
c 100
d –0.9900 –0.0100 0.0100 0 –1.1000
g 0.2720 0.5485 –0.0949

84
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

CRO-TUBE-MP-CO-4
0.9 0.9

C*
0.8 0.0 0.8

0.1
ESDU Copyright material. For current status contact ESDU.

0.2
0.7 0.7
0.3
E E
0.4
0.6
0.6 0.5 0.6
0.7
0.8
0.9
85

0.5 1.0 0.5


95% of Emax
C*
Temperature meet
0.4 0.4

ESDU 98005
Configuration Data
See Table 11.30
0.3 0.3
Index of Geometries
See Section 5.6

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 32 TWO-PASS CO-CURRENT CROSSFLOW, TWO TUBE ROWS/PASS, INVERTED U-TUBES BETWEEN PASSES, ( M p smaller OUTSIDE
TUBES
ESDU 98005
TABLE 11.31
Crossflow CRO-TUBE-MP-CO-5
2 Passes
2 Tube rows per pass
·c )
(M p smaller inside tubes

Non-inverted U-tube
Part-mixed/unmixed

Relationship between E , N TU and C∗
ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5.

Asymptotic expression
Since the curves pass through a maximum before reaching the asymptotic value, the following data
are provided to assist their use.
C∗ E
max E for N = 100
TU E asymp
0 1 1 1
0.1 0.885 0.407 0.375
0.2 0.809 0.378 0.375
0.3 0.748 0.375 0.375
0.4 0.696 0.376 0.376
0.5 0.652 0.376 0.376
0.6 0.614 0.377 0.377
0.7 0.580 0.377 0.377
0.8 0.549 0.377 0.377
0.9 0.522 0.377 0.377
1 0.498 0.377 0.377

Algebraic coefficients
0 1 2 3 4
a –0.1616 0.2760 –0.1324
b 6.5800 –29.6258 55.6237 –48.8342 16.4762
c 100
d –0.9400 0.0700 0.0500 0.0300 –0.1200
g 0.2222 0.9037 –0.2693

86
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

CRO-TUBE-MP-CO-5
0.9 0.9

C*
0.8 0.0 0.8
0.1

0.2
ESDU Copyright material. For current status contact ESDU.

0.7 0.7
0.3

E 0.4 E
0.6
0.6 0.5 0.6
0.7
0.8
0.9
1.0
87

0.5 0.5
C*
95% of Emax
Temperature meet
0.4 0.4

ESDU 98005
Configuration Data
See Table 11.31
0.3 0.3
Index of Geometries
See Section 5.6

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 33 TWO-PASS CO-CURRENT CROSSFLOW, TWO TUBE ROWS/PASS, NON-INVERTED U-TUBES BETWEEN PASSES, ( M p smaller INSIDE
TUBES
ESDU 98005
TABLE 11.32
Crossflow CRO-TUBE-MP-CO-6
2 Passes
2 Tube rows per pass
·c )
(M p smaller outside tubes

Non-inverted U-tube
Part-mixed/unmixed

Relationship between E , N TU and C∗
ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5.

Asymptotic expression
Since the curves pass through a maximum before reaching the asymptotic value, the following data
are provided to assist their use.
C∗ E
max E for N = 100
TU E asymp
0 1 1 1
0.1 0.968 0.968 0.968
0.2 0.898 0.898 0.898
0.3 0.813 0.813 0.813
0.4 0.733 0.728 0.728
0.5 0.678 0.649 0.649
0.6 0.632 0.571 0.577
0.7 0.592 0.515 0.515
0.8 0.557 0.462 0.462
0.9 0.525 0.416 0.416
1 0.498 0.377 0.377

Algebraic coefficients
0 1 2 3 4
a 0.5945 –1.7167 0.8762
b –2.9584 17.1339 –32.3530 26.6397 –8.1532
c 100
d 0.0137 –2.7687 7.6546 –7.7910 2.5954
g 0.2723 0.6679 –0.1500

88
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

CRO-TUBE-MP-CO-6
0.9 0.9

C*
0.0
0.8 0.8
0.1

0.2
ESDU Copyright material. For current status contact ESDU.

0.7 0.7
0.3

E 0.4 0.6 E
0.5 0.7
0.6 0.6
0.8
0.9
89

0.5 1.0 0.5


C*
95% of Emax
Temperature meet
0.4 0.4

Configuration Data

ESDU 98005
See Table 11.32
0.3 Index of Geometries 0.3
See Section 5.6

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 34 TWO-PASS CO-CURRENT CROSSFLOW, TWO TUBE ROWS/PASS, NON-INVERTED U-TUBES BETWEEN PASSES, ( M p smaller OUTSIDE
TUBES
ESDU 98005
TABLE 11.33
Crossflow CRO-TUBE-MP-CO-7
2 Passes
3 Tube rows per pass
·c )
(M p smaller inside tubes

Header
Part-mixed/unmixed

Relationship between E , N TU and C∗
ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5.

Asymptotic expression
Since the curves pass through a maximum before reaching the asymptotic value, the following data
are provided to assist their use.
C∗ E
max E for N = 100
TU E asymp
0 1 1 1
0.1 0.886 0.313 0.313
0.2 0.809 0.313 0.313
0.3 0.748 0.313 0.313
0.4 0.696 0.313 0.313
0.5 0.651 0.313 0.313
0.6 0.611 0.313 0.313
0.7 0.577 0.313 0.313
0.8 0.546 0.313 0.313
0.9 0.519 0.313 0.313
1 0.494 0.313 0.313

Algebraic coefficients
0 1 2 3 4
a –0.1585 0.2740 –0.1319
b –2.2100 26.4917 –69.9792 71.4683 –25.4908
c 100
d –1.3300 12.8817 –59.6175 86.5483 –40.0725
g 0.0687 1.1333 –0.3543

90
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

CRO-TUBE-MP-CO-7
0.9 0.9

C*
0.0
0.8 0.1 0.8

0.2
ESDU Copyright material. For current status contact ESDU.

0.3
0.7 0.7
0.4
E E
0.5
0.6
0.6 0.6
0.7
0.8
0.9
91

0.5 1.0 0.5


*
95% of Emax C
Temperature meet

0.4 0.4

ESDU 98005
Configuration Data
See Table 11.33
0.3 0.3
Index of Geometries
See Section 5.6

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 35 TWO-PASS CO-CURRENT CROSSFLOW, THREE TUBE ROWS/PASS, MIXED BETWEEN PASSES, ( M p smaller INSIDE TUBES
ESDU 98005
TABLE 11.34
Crossflow CRO-TUBE-MP-CO-8
2 Passes
3 Tube rows per pass
·c )
(M p smaller outside tubes

Header
Part-mixed/unmixed

Relationship between E , N TU and C∗
ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5.

Asymptotic expression
Since the curves pass through a maximum before reaching the asymptotic value, the following data
are provided to assist their use.
C∗ E
max E for N = 100
TU E asymp
0 1 1 1
0.1 0.909 0.900 0.900
0.2 0.832 0.802 0.802
0.3 0.767 0.710 0.710
0.4 0.717 0.625 0.625
0.5 0.662 0.551 0.551
0.6 0.620 0.486 0.486
0.7 0.582 0.431 0.431
0.8 0.549 0.385 0.385
0.9 0.519 0.346 0.346
1 0.492 0.313 0.313

Algebraic coefficients
0 1 2 3 4
a –0.0033 –0.0267 0.0135
b 1.1700 –4.0783 7.1225 –5.3667 1.6225
c 100
d –0.1400 –1.0400 –0.0200 –0.0100 –0.8000
g 0.2426 0.6087 –0.1178

92
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

CRO-TUBE-MP-CO-8
0.9 0.9

C*
0.0

0.8 0.1 0.8

0.2
ESDU Copyright material. For current status contact ESDU.

0.3
0.7 0.7
0.4
E 0.5 E
0.6
0.6 0.7 0.6

0.8
0.9
93

0.5 1.0 0.5


*
95% of Emax C
Temperature meet

0.4 0.4

ESDU 98005
Configuration Data
See Table 11.34
0.3 Index of Geometries 0.3
See Section 5.6

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 36 TWO-PASS CO-CURRENT CROSSFLOW, THREE TUBE ROWS/PASS, MIXED BETWEEN PASSES, ( M p smaller OUTSIDE TUBES
ESDU 98005
TABLE 11.35
Crossflow CRO-TUBE-MP-CO-9
2 Passes
>3 Tube rows per pass
·c )
(M p smaller inside tubes

Header
Unmixed/unmixed

Relationship between E , N TU and C∗
ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5.

Asymptotic expression
Since the curves pass through a maximum before reaching the asymptotic value, the following data
are provided to assist their use.
C∗ E
max E for N = 100
TU E asymp
0 1 1 1
0.1 0.885 0.347 0
0.2 0.808 0.249 0
0.3 0.745 0.204 0
0.4 0.692 0.177 0
0.5 0.649 0.158 0
0.6 0.610 0.145 0
0.7 0.576 0.134 0
0.8 0.544 0.130 0
0.9 0.517 0.128 0
1 0.493 0.127 0

94
NTU

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10


1.0 1.0

CRO-TUBE-MP-CO-9
0.9 0.9

0.8 0.8
*
C
0.0
ESDU Copyright material. For current status contact ESDU.

0.7 0.1 0.7


0.2
E E
0.3 0.6
0.6 0.6
0.4 0.7
0.8
0.5
95

0.9
0.5 1.0 0.5
95% of Emax C*
Temperature meet
0.4 0.4

ESDU 98005
Configuration Data
See Table 11.35
0.3 Index of Geometries 0.3
See Section 5.6

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 37 TWO-PASS CO-CURRENT CROSSFLOW, >THREE TUBE ROWS/PASS, MIXED BETWEEN PASSES, ( M p smaller INSIDE TUBES
ESDU 98005
TABLE 11.36
Crossflow CRO-TUBE-MP-CO-10
2 Passes
>3 Tube rows per pass
·c )
(M p smaller outside tubes

Header
Unmixed/unmixed

Relationship between E , N TU and C∗
ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5.

Asymptotic expression
Since the curves pass through a maximum before reaching the asymptotic value, the following data
are provided to assist their use.
C∗ E
max E for N = 100
TU E asymp
0 1 1 1
0.1 0.909 0.900 0.9
0.2 0.832 0.800 0.8
0.3 0.767 0.700 0.7
0.4 0.712 0.600 0.6
0.5 0.662 0.500 0.5
0.6 0.621 0.401 0.4
0.7 0.582 0.306 0.3
0.8 0.548 0.224 0.2
0.9 0.518 0.164 0.1
1 0.493 0.127 0

96
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

CRO-TUBE-MP-CO-10
0.9 0.9

0.8 0.8
C*
0.0
ESDU Copyright material. For current status contact ESDU.

0.1
0.7 0.7
0.2
E 0.3 E
0.6
0.6 0.4 0.7 0.6

0.5 0.8
0.9
97

0.5 1.0 0.5


95% of Emax *
C
Temperature meet

0.4 0.4

ESDU 98005
Configuration Data
See Table 11.36
0.3 Index of Geometries 0.3
See Section 5.6

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU

·c )
FIGURE 38 TWO-PASS CO-CURRENT CROSSFLOW, > THREE TUBE ROWS/PASS, MIXED BETWEEN PASSES, ( M p smaller OUTSIDE TUBES
ESDU 98005
TABLE 11.37
Crossflow CRO-TUBE-MP-CO-11
3 Passes
2 Tube rows per pass
·c )
(M p smaller inside tubes

Header
Part-mixed/unmixed

Relationship between E , N TU and C∗
ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5.

Asymptotic expression

C∗ E asymp
0 1
0.1 1
0.2 0.998
0.3 0.974
0.4 0.922
0.5 0.857
0.6 0.789
0.7 0.726
0.8 0.670
0.9 0.622
1 0.579

98
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

CRO-TUBE-MP-CO-11
0.9 0.9
C*
0.0
0.1
0.8 0.2 0.8
0.3
0.4
0.5
ESDU Copyright material. For current status contact ESDU.

0.7 0.7

E E
0.6
0.6 95% of Emax 0.6
0.7
Temperature meet 0.8
0.9
99

1.0
0.5 0.5
C*

0.4 0.4

ESDU 98005
Configuration Data
See Table 11.37
0.3 Index of Geometries 0.3
See Section 5.6

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 39 THREE-PASS CO-CURRENT CROSSFLOW, TWO TUBE ROWS/PASS, MIXED BETWEEN PASSES, ( M p smaller INSIDE TUBES
ESDU 98005
TABLE 11.38
Crossflow CRO-TUBE-MP-CO-12
3 Passes
2 Tube rows per pass
·c )
(M p smaller outside tubes

Any connections
Part-mixed/unmixed

Relationship between E , N TU and C∗
ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5.

Asymptotic expression

C∗ E asymp
0 1
0.1 0.910
0.2 0.838
0.3 0.781
0.4 0.735
0.5 0.698
0.6 0.668
0.7 0.642
0.8 0.619
0.9 0.598
1 0.579

Algebraic coefficients
0 1 2 3 4
a –0.0430 0.3577 –0.1567
b 0.2417 –1.5658 1.7850 –0.2242 –0.3607
c 10
d –0.0925 0.8424 –2.8522 3.3591 –1.3490
g 0.0608 0.6221 –0.0992

100
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0
C*
CRO-TUBE-MP-CO-12 0.0

0.1
0.9 0.9
0.2

0.3
0.8 0.4 0.8

0.5
ESDU Copyright material. For current status contact ESDU.

0.7 0.7

E E
0.6
0.6 0.7 0.6
0.8
0.9
101

1.0
0.5 0.5
95% of Emax C*

Temperature meet
0.4 0.4

Configuration Data

ESDU 98005
See Table 11.38
0.3 Index of Geometries 0.3
See Section 5.6

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU

·c )
FIGURE 40 THREE-PASS CO-CURRENT CROSSFLOW, TWO TUBE ROWS/PASS, MIXED BETWEEN PASSES, ( M p smaller OUTSIDE TUBES
ESDU 98005
TABLE 11.39
Crossflow CRO-TUBE-MP-CO-13
3 Passes
2 Tube rows per pass
·c )
(M p smaller inside tubes

Inverted U-tube
Part-mixed/unmixed

Relationship between E , N TU and C∗
ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5.

Asymptotic expression

C∗ E asymp
0 1
0.1 1
0.2 0.998
0.3 0.976
0.4 0.927
0.5 0.866
0.6 0.804
0.7 0.746
0.8 0.695
0.9 0.650
1 0.610

102
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

CRO-TUBE-MP-CO-13
0.9 0.9
C*
0.0
0.1
0.8 0.2 0.8
0.3
0.4
0.5
ESDU Copyright material. For current status contact ESDU.

0.7 0.7

E 0.6 E

0.6 95% of Emax 0.7 0.6


Temperature meet 0.8
0.9
103

1.0
0.5 0.5
C*

0.4 0.4

Configuration Data

ESDU 98005
See Table 11.39
0.3 Index of Geometries 0.3
See Section 5.6

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 41 THREE-PASS CO-CURRENT CROSSFLOW, TWO TUBE ROWS/PASS, INVERTED U-TUBES BETWEEN PASSES, ( M p smaller INSIDE
TUBES
ESDU 98005
TABLE 11.40
Crossflow CRO-TUBE-MP-CO-14
3 Passes
2 Tube rows per pass
·c )
(M p smaller outside tubes

Inverted U-tube
Part-mixed/unmixed

Relationship between E , N TU and C∗
ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5.

Asymptotic expression

C∗ E asymp
0 1
0.1 0.972
0.2 0.918
0.3 0.862
0.4 0.810
0.5 0.765
0.6 0.726
0.7 0.692
0.8 0.661
0.9 0.635
1 0.610

104
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

CRO-TUBE-MP-CO-14

0.9 0.9
C*
0.0
0.1
0.8 0.2 0.8
0.3
0.4
0.5
ESDU Copyright material. For current status contact ESDU.

0.7 0.7

E 0.6 E

0.6 95% of Emax 0.7 0.6


Temperature meet 0.8
0.9
105

1.0
0.5 C* 0.5

0.4 0.4

ESDU 98005
Configuration Data
See Table 11.40
Index of Geometries
0.3 0.3
See Section 5.6

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
TU N
·c )
FIGURE 42 THREE-PASS CO-CURRENT CROSSFLOW, TWO TUBE ROWS/PASS, INVERTED U-TUBES BETWEEN PASSES, ( M p smaller OUTSIDE
TUBES
ESDU 98005
TABLE 11.41
Crossflow CRO-TUBE-MP-CO-15
3 Passes
2 Tube rows per pass
·c )
(M p smaller inside tubes

Non-inverted U-tube
Part-mixed/unmixed

Relationship between E , N TU and C∗


ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5.

Asymptotic expression

C∗ E asymp
0 1
0.1 1
0.2 0.997
0.3 0.973
0.4 0.918
0.5 0.847
0.6 0.774
0.7 0.706
0.8 0.646
0.9 0.593
1 0.548

106
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

CRO-TUBE-MP-CO-15
0.9 0.9
C*
0.0
0.1
0.8 0.2 0.8
0.3
0.4
0.5
ESDU Copyright material. For current status contact ESDU.

0.7 0.7

E 0.6 E

0.6 95% of Emax 0.6


0.7
Temperature meet 0.8
0.9
107

1.0
0.5 0.5
C*

0.4 0.4

ESDU 98005
Configuration Data
See Table 11.41
0.3 Index of Geometries 0.3
See Section 5.6

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 43 THREE-PASS CO-CURRENT CROSSFLOW, TWO TUBE ROWS/PASS, NON-INVERTED U-TUBES BETWEEN PASSES, ( M p smaller IN
TUBES
ESDU 98005
TABLE 11.42
Crossflow CRO-TUBE-MP-CO-16
3 Passes
2 Tube rows per pass
·c )
(M p smaller outside tubes

Non-inverted U-tube
Part-mixed/unmixed

Relationship between E , N TU and C∗


ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5.

Asymptotic expression

C∗ E asymp
0 1
0.1 0.947
0.2 0.854
0.3 0.769
0.4 0.704
0.5 0.656
0.6 0.622
0.7 0.597
0.8 0.578
0.9 0.562
1 0.548

108
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

CRO-TUBE-MP-CO-16

0.9 0.9
C*
0.0
0.1
0.8 0.2 0.8
0.3
0.4
0.5
ESDU Copyright material. For current status contact ESDU.

0.7 0.7

E 0.6 E

0.6 95% of Emax 0.7 0.6


Temperature meet 0.8
109

0.5 0.5
C*
0.9
1.0
0.4 0.4

ESDU 98005
Configuration Data
See Table 11.42
0.3 Index of Geometries 0.3
See Section 5.6

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 44 THREE-PASS CO-CURRENT CROSSFLOW, TWO TUBE ROWS/PASS, NON-INVERTED U-TUBES BETWEEN PASSES, ( M p smaller
OUTSIDE TUBES
ESDU 98005
TABLE 11.43
Crossflow CRO-TUBE-MP-CO-17
3 Passes
>2 Tube rows per pass
·c )
(M p smaller inside tubes

Header
Unmixed/unmixed

Relationship between E , N TU and C∗
ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5.

Asymptotic expression

C∗ E asymp
0 1
0.1 1
0.2 1
0.3 1
0.4 1
0.5 0.998
0.6 0.996
0.7 0.992
0.8 0.986
0.9 0.982
1 1

110
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

CRO-TUBE-MP-CO-17
0.9 0.9
C*
0.0
0.1
0.8 0.2 0.8
0.3
0.4
0.5
ESDU Copyright material. For current status contact ESDU.

0.7 0.7

E 0.6 E

0.6 95% of Emax 0.7 0.6


Temperature meet 0.8
0.9
111

1.0
0.5 0.5
C*

0.4 0.4

ESDU 98005
Configuration Data
See Table 11.43
0.3 Index of Geometries 0.3
See Section 5.6

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 45 THREE-PASS CO-CURRENT CROSSFLOW, > TWO TUBE ROWS/PASS, MIXED BETWEEN PASSES, ( M p smaller INSIDE TUBES
ESDU 98005
TABLE 11.44
Crossflow CRO-TUBE-MP-CO-18
3 Passes
>2 Tube rows per pass
·c )
(M p smaller outside tubes

Header
Unmixed/unmixed

Relationship between E , N TU and C∗
ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5.

Asymptotic expression

C∗ E asymp
0 1
0.1 0.910
0.2 0.840
0.3 0.790
0.4 0.760
0.5 0.750
0.6 0.750
0.7 0.760
0.8 0.840
0.9 0.910
1 1

112
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

CRO-TUBE-MP-CO-18
0.9 0.9
C*
0.0
0.1
0.8 0.2 0.8
0.3
0.4
0.5
ESDU Copyright material. For current status contact ESDU.

0.7 0.7

E 0.6 E

0.6 95% of Emax 0.7 0.6


Temperature meet 0.8
0.9
113

1.0
0.5 0.5
C*

0.4 0.4

ESDU 98005
Configuration Data
See Table 11.44
0.3 Index of Geometries 0.3
See Section 5.6

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 46 THREE-PASS CO-CURRENT CROSSFLOW, > TWO TUBE ROWS/PASS, MIXED BETWEEN PASSES, ( M p smaller OUTSIDE TUBES
ESDU 98005
TABLE 11.45
Crossflow CRO-TUBE-MP-CO-19
4 Passes
2 Tube rows per pass
·c )
(M p smaller inside tubes

Inverted U-tube
Part-mixed/unmixed

Relationship between E , N TU and C∗
ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5.

Asymptotic expression
Since the curves pass through a maximum before reaching the asymptotic value, the following data
are provided to assist their use.
C∗ E
max E for N = 100
TU E asymp
0 1 1 1
0.1 0.903 0.608 0.492
0.2 0.828 0.525 0.492
0.3 0.765 0.501 0.492
0.4 0.711 0.493 0.491
0.5 0.664 0.487 0.486
0.6 0.622 0.478 0.478
0.7 0.586 0.466 0.466
0.8 0.554 0.453 0.453
0.9 0.525 0.438 0.438
1 0.498 0.423 0.423

Algebraic coefficients
0 1 2 3 4
a –0.0250 0.0464 –0.0246
b 0.1403 –0.4672 0.9682 –0.7392 0.2980
c 100
d –0.2100 –0.3000 –0.5000 –0.5000 –1.4000
g –0.3533 1.4294 –0.3765

114
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

CRO-TUBE-MP-CO-19
0.9 0.9

0.8 C* 0.8
0.0

0.1
ESDU Copyright material. For current status contact ESDU.

0.7 0.2 0.7

0.3
E 0.6 E
0.4
0.6 0.7 0.6
0.5
0.8
0.9
115

0.5 1.0 0.5


C*
95% of Emax
Temperature meet
0.4 0.4

ESDU 98005
Configuration Data
See Table 11.45
0.3 Index of Geometries 0.3
See Section 5.6

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 47 FOUR-PASS CO-CURRENT CROSSFLOW, TWO TUBE ROWS/PASS, INVERTED U-TUBES BETWEEN PASSES, ( M p smaller INSIDE
TUBES
ESDU 98005
TABLE 11.46
Crossflow CRO-TUBE-MP-CO-20
4 Passes
2 Tube rows per pass
·c )
(M p smaller outside tubes

Inverted U-tube
Part-mixed/unmixed

Relationship between E , N TU and C∗
ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5.

Asymptotic expression
Since the curves pass through a maximum before reaching the asymptotic value, the following data
are provided to assist their use.
C∗ E max E for N TU = 100 E asymp
0 1 1 1
0.1 0.905 0.857 0.857
0.2 0.829 0.771 0.771
0.3 0.766 0.706 0.706
0.4 0.711 0.651 0.651
0.5 0.664 0.602 0.602
0.6 0.623 0.559 0.599
0.7 0.586 0.520 0.520
0.8 0.554 0.484 0.484
0.9 0.525 0.452 0.452
1 0.498 0.423 0.423

Algebraic coefficients
0 1 2 3 4
a –0.0250 0.0464 –0.0246
b 0.1413 –0.4872 0.9182 –0.7592 0.3280
c 100
d –0.1700 –0.2000 –0.1000 –0.3000 –1.3000
g 0.1565 0.4582 0.0284

116
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

CRO-TUBE-MP-CO-20
0.9 0.9

C*
0.0

0.8 0.1 0.8

0.2
ESDU Copyright material. For current status contact ESDU.

0.3
0.7 0.7
0.4

E 0.5 E
0.6
0.6 0.7 0.6

0.8
0.9
117

0.5 1.0 0.5


C*
95% of Emax
Temperature meet
0.4 0.4

ESDU 98005
Configuration Data
See Table 11.46
0.3 Index of Geometries 0.3
See Section 5.6

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 48 FOUR-PASS CO-CURRENT CROSSFLOW, TWO TUBE ROWS/PASS, INVERTED U-TUBES BETWEEN PASSES, ( M p smaller OUTSIDE
TUBES
ESDU 98005
TABLE 11.47
Crossflow CRO-TUBE-MP-CO-21
4 Passes
Any number of tube rows
(M·c )
p smaller inside tubes
Header
Unmixed/unmixed
– Equivalent to SERP-CO-5

Relationship between E , N TU and C∗


E = 1 – A,
ESDU Copyright material. For current status contact ESDU.

2
K 3
A = ----  1 – ---- + ------ + K  1 – ---- 1 + 2 -------  1 – ---- exp [ –2K / C∗ ] +  1 – ---- exp [ – 4K / C∗ ]
where K K K K K K
2 2 4  2 C∗  2  2
and K = 1 – exp [ – N TU C∗/4 ] .
Asymptotic expression

E asymp = --- – ---  1 + ------- exp [ – 2 / C∗ ] – --- exp [ – 4K / C∗ ] .


5 1 1 1
8 2  C∗  8
Since the curves pass through a maximum before reaching the asymptotic value, the following data
are provided to assist their use.
C∗ E max E for N TU = 100 E asymp
0 1 1 1
0.1 0.903 0.655 0.625
0.2 0.828 0.627 0.625
0.3 0.765 0.622 0.622
0.4 0.711 0.613 0.613
0.5 0.664 0.597 0.597
0.6 0.623 0.577 0.577
0.7 0.586 0.555 0.555
0.8 0.554 0.532 0.532
0.9 0.525 0.509 0.509
1 0.499 0.487 0.487

Algebraic coefficients

0 1 2 3 4
a 0.0007 –0.0036 0.0011
b 0.0120 0.0010 0.0010 0 0.0470
c 100
d –0.1 0 0 –0.2 –1.1
g 0.1178 0.5322 –0.075

118
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

CRO-TUBE-MP-CO-21
(Also SERP-CO-5)
0.9 0.9

0.8 C* 0.8
0.0
0.1
0.2
ESDU Copyright material. For current status contact ESDU.

0.3
0.7 0.4 0.7
0.5

E E
0.6
0.6 0.7 0.6

0.8
0.9
119

0.5 1.0 0.5


95% of Emax C*
Temperature meet

0.4 0.4

ESDU 98005
Configuration Data
See Table 11.47
0.3 0.3
Index of Geometries
See Section 5.6

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 49 FOUR-PASS CO-CURRENT CROSSFLOW, ANY NUMBER OF TUBE ROWS/PASS, MIXED BETWEEN PASSES, ( M p smaller INSIDE
TUBES
ESDU 98005
TABLE 11.48
Crossflow CRO-TUBE-MP-CO-22
4 Passes
Any number of tube rows
·c )
(M p smaller outside tubes
Header
Unmixed/unmixed
– Equivalent to SERP-CO-6

Relationship between E , N TU and C∗

1
E = ------- ( 1 – A ) ,
ESDU Copyright material. For current status contact ESDU.

C∗
2
K 3
A = ----  1 – ---- + ------ + K  1 – ---- 1 + 2C∗ K  1 – ---- exp [ – 2C∗ K ] +  1 – ---- exp [ –4C∗ K ]
K K K K K
where
2  2 4  2  2  2
and K = 1 – exp [ – N TU /4 ] .
Asymptotic expression

E asymp = ------- --- – ---  1 + ------- exp [ – 2C∗ ] – --- exp [ – 4C∗ ] .
1 5 1 1 1
C∗ 8 2  C∗  8
Since the curves pass through a maximum before reaching the asymptotic value, the following data
are provided to assist in their use:

C∗ E max E for N TU = 100 E asymp


0 1 1 1
0.1 0.909 0.909 0.909
0.2 0.833 0.833 0.833
0.3 0.769 0.768 0.768
0.4 0.714 0.713 0.713
0.5 0.666 0.664 0.664
0.6 0.625 0.621 0.621
0.7 0.588 0.583 0.583
0.8 0.555 0.548 0.548
0.9 0.526 0.516 0.516
1 0.499 0.487 0.487

Algebraic coefficients
0 1 2 3 4
a –0.0328 0.0636 –0.0326
b 0.025 0.0210 0.0110 0 0.066
c 100
d –0.13 0 –0.2 –0.3 –1.5
g –0.5554 1.7031 –0.4624

120
NTU

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10


1.0 1.0

CRO-TUBE-MP-CO-22
(Also SERP-CO-6)
0.9 0.9

0.8 C* 0.8
0.0
0.1
ESDU Copyright material. For current status contact ESDU.

0.2
0.3
0.7 0.7
0.4
0.5
E E
0.6
0.6 0.7 0.6

0.8
121

0.9
0.5 1.0 0.5
C*

95% of Emax

0.4 Temperature meet 0.4

ESDU 98005
Configuration Data
See Table 11.48
0.3 Index of Geometries 0.3
See Section 5.6

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 50 FOUR-PASS CO-CURRENT CROSSFLOW, ANY NUMBER OF TUBE ROWS/PASS, MIXED BETWEEN PASSES, ( M p smaller OUTSIDE
TUBES
ESDU 98005
12. DATA FOR SERPENTINE CONFIGURATIONS

12.1 Serpentine, Counter-current

TABLE 12.1
Serpentine SERP-CU-1
2 Passes

·c )
(M p smaller inside tubes


ESDU Copyright material. For current status contact ESDU.

Relationship between E , N TU and C∗ . (See Derivation 8.)

E =  1 – --- ,
1
 A

A = ---- +  1 – ---- exp -------


K K 2K
where
2  2 C∗
– N TU C∗
and K = 1 – exp  ---------------------  .
 2 

Asymptotic expression
2
E asymp = 1 – ---------------------------------- .
2
1 + exp -------
C∗
C∗ E asymp C∗ E asymp
0 1 0.6 0.931
0.1 1 0.7 0.891
0.2 1 0.8 0.848
0.3 0.997 0.9 0.804
0.4 0.987 1 0.762
0.5 0.964

Algebraic coefficients
0 1 2 3 4
a 1.2486 –0.7473 0.0220
b –0.1668 –7.1464 28.2077 –34.0378 13.3857
c 100
d –0.7806 4.9442 –14.9821 17.6124 –6.9183
g 0.4681 0.6639 –0.2150

122
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SERP-CU-1 C*
0.0
0.9 0.1 0.9
0.2
0.3
0.4
0.5
0.8 0.6 0.8
0.7
0.8
0.9
ESDU Copyright material. For current status contact ESDU.

0.7 1.0 0.7


C*

E E

0.6 NoNo
temperature meet
temperature meet 0.6
123

0.5 0.5

0.4 95% of Emax 0.4

ESDU 98005
Configuration Data
See Table 12.1
0.3 Index of Geometries 0.3
See Section 6.1

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 51 TWO-PASS SERPENTINE WITH COUNTER-CURRENT FLOW, ( M p smaller INSIDE TUBES
ESDU 98005
TABLE 12.2

Serpentine SERP-CU-2
2 Passes

·c )
(M p smaller outside tubes



Relationship between E , N TU and C∗ . (See Derivation 8.)
ESDU Copyright material. For current status contact ESDU.

E = -------  1 – --- ,
1 1
C∗  A

A = ---- +  1 – ---- exp [ 2KC∗ ]


K K
where
2  2
– N TU
and K = 1 – exp  --------------  .
 2 

Asymptotic expression

E asymp = -------  1 – ------------------------------------ .


1 2
C ∗  1 + exp [ 2C∗ ]
C∗ E asymp C∗ E asymp
0 1 0.6 0.895
0.1 0.997 0.7 0.863
0.2 0.987 0.8 0.830
0.3 0.971 0.9 0.796
0.4 0.950 1 0.762
0.5 0.924

Algebraic coefficients
0 1 2 3 4
a 1.0577 –0.6139 0.0802
b –0.1531 –3.0922 15.5566 –20.8543 8.7865
c 100
d –0.3825 2.9001 –10.7301 13.8630 –5.7806
g 0.4620 0.6638 –0.2147

124
NTU

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10


1.0 1.0

SERP-CU-2 C*
0.0
0.9 0.1 0.9
0.2 0. 6
0.3 0.7
0.4
0.5 0. 8
0.8 0.8
0.9
1.0
ESDU Copyright material. For current status contact ESDU.

C*
0.7 0.7

E E
No local temperature cross
0.6 No temperature meet 0.6
125

0.5 0.5
95% of Emax

0.4 0.4

ESDU 98005
Configuration Data
See Table 12.2
0.3 Index of Geometries 0.3
See Section 6.1

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 52 TWO-PASS SERPENTINE WITH COUNTER-CURRENT FLOW, ( M p smaller OUTSIDE TUBES
ESDU 98005
TABLE 12.3
Serpentine SERP-CU-3
3 Passes

·c )
(M p smaller inside tubes

Relationship between E , N TU and C∗ . (See Derivation 8.)


ESDU Copyright material. For current status contact ESDU.

E =  1 – --- ,
1
 A
K 2
A = K 1 – ---- – -------  1 – ---- exp ------- +  1 – ---- exp -------
K K K K 3K
where
4 C∗  2 C ∗  2  C∗
– N TU C∗
and K = 1 – exp  ---------------------  .
 3 

Asymptotic expression
1
E asymp = 1 – -------------------------------------------------------------------------------------- .
3 --- – ---------- exp ------- + --- exp -------
1 1 1 3
 4 2C∗ C∗ 4 C∗
C∗ E asymp C∗ E asymp
0 1 0.6 0.975
0.1 1 0.7 0.950
0.2 1 0.8 0.916
0.3 1 0.9 0.874
0.4 0.999 1 0.825
0.5 0.990

Algebraic coefficients
0 1 2 3 4
a 1.0132 0.1551 –0.5191
b –1.2460 4.4523 –6.6881 5.2792 –1.5984
c 100
d –1.1472 6.7976 –17.8128 19.8344 –7.7682
g 0.4877 0.6265 –0.1914

126
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SERP-CU-3 C*

0.9 0.0 0.9


0.1 0.6
0.2 0.7
0.3
0.4 0.8
0.8 0.5 0.8
0.9
1.0
ESDU Copyright material. For current status contact ESDU.

C*
0.7 0.7

E E
No temperature meet
0.6 0.6
127

0.5 0.5

0.4 95% of Emax 0.4

Configuration Data

ESDU 98005
See Table 12.3
Index of Geometries
0.3 0.3
See Section 6.1

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU

·c )
FIGURE 53 THREE-PASS SERPENTINE WITH COUNTER-CURRENT FLOW, ( M p smaller INSIDE TUBES
ESDU 98005
TABLE 12.4
Serpentine SERP-CU-4
3 Passes

·c )
(M p smaller outside tubes


Relationship between E , N TU and C∗ . (See Derivation 8.)


ESDU Copyright material. For current status contact ESDU.

E = -------  1 – --- ,
1 1
C ∗  A 

K 2
A = K 1 – ---- – C∗ K  1 – ---- exp [ KC∗ ] +  1 – ---- exp [ 3KC∗ ]
K K
where
4  2  2
– N TU
and K = 1 – exp  --------------  .
 3 

Asymptotic expression
 
1  1 
E asymp = -------  1 – ------------------------------------------------------------------------------------ .
C∗  C∗
3 --- – ------- exp [ C∗ ] + --- exp [ 3C∗ ]
1
 4 2  4
C∗ E asymp C∗ E asymp
0 1 0.6 0.952
0.1 1 0.7 0.927
0.2 0.998 0.8 0.896
0.3 0.994 0.9 0.861
0.4 0.985 1 0.825
0.5 0.975

Algebraic coefficients
0 1 2 3 4
a 1.0448 –0.1369 –0.2588
b –0.5248 1.0240 1.5834 –3.6385 1.7569
c 100
d –0.6617 5.5230 –19.5002 25.2611 –10.7188
g 0.5000 0.6254 –0.2061

128
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SERP-CU-4 C*
0.0
0.9 0.1 0.9
0.6
0.2
0.3 0.7
0.4 0.8
0.5
0.8 0.9 0.8
1.0
C*
ESDU Copyright material. For current status contact ESDU.

0.7 0.7

E E
No
Notemperature meet
local temperature meet
0.6 0.6
129

0.5 0.5

95% of Emax
0.4 0.4
Configuration Data

ESDU 98005
See Table 12.4
Index of Geometries
0.3 See Section 6.1 0.3

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 54 THREE-PASS SERPENTINE WITH COUNTER-CURRENT FLOW, ( M p smaller OUTSIDE TUBES
ESDU 98005
TABLE 12.5
Serpentine SERP-CU-5
4 Passes

·c )
(M p smaller inside tubes

Relationship between E , N TU and C∗ . (See Derivation 8.)


ESDU Copyright material. For current status contact ESDU.

E =  1 – --- ,
1
 A
2
K 3
A = ----  1 – ---- + ------ + K  1 – ---- 1 – -------  1 – ---- exp ------- +  1 – ---- exp -------
K K K K 2K K 2K 4K
where
2 2 4  2 C∗  2 C∗  2 C∗
– N TU C∗
and K = 1 – exp  ---------------------  .
 4 

Asymptotic expression
1
E asymp = 1 – ------------------------------------------------------------------------------------------------------- .
3 --- + ---  1 – ------- exp ------- + --- exp ------- 
1 1 2 1 4
8 2 C ∗  C ∗ 8 C∗ 
C∗ E asymp C∗ E asymp
0 1 0.6 0.989
0.1 1 0.7 0.971
0.2 1 0.8 0.943
0.3 1 0.9 0.905
0.4 1 1 0.861
0.5 0.997

Algebraic coefficients
0 1 2 3 4
a 0.8752 0.6164 –0.7694
b 0.0357 1.4025 –8.6351 14.0365 –6.6669
c 100
d –0.1780 1.2071 –3.3154 2.4458 –0.2386
g 0.4875 0.6365 –0.2053

130
NTU

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10


1.0 1.0

SERP-CU-5
C*
0.9 0.6 0.9
0.0
0.1 0.7
0.2 0.8
0.3
0.4 0.9
0.8 0.8
0.5
1.0
C*
ESDU Copyright material. For current status contact ESDU.

0.7 0.7

E E
No
Nolocal temperaturemeet
temperature cross
0.6 0.6
131

0.5 0.5

0.4 0.4

ESDU 98005
95% of Emax Configuration Data
See Table 12.5
Index of Geometries
0.3 0.3
See Section 6.1

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 55 FOUR-PASS SERPENTINE WITH COUNTER-CURRENT FLOW, ( M p smaller INSIDE TUBES
ESDU 98005
TABLE 12.6
Serpentine SERP-CU-6
4 Passes

·c )
(M p smaller outside tubes

Relationship between E , N TU and C∗ . (See Derivation 8.)


ESDU Copyright material. For current status contact ESDU.

E = -------  1 – --- ,
1 1
C ∗  A 
2
K 3
A = ----  1 – ---- + ------ + K  1 – ---- 1 – 2KC∗  1 – ---- exp [ 2KC∗ ] +  1 – ---- exp [ 4KC∗ ]
K K K K K
where
2 2 4  2  2  2
– N TU
and K = 1 – exp  --------------  .
 4 

Asymptotic expression

1 1
E asymp = ------- 1 – ------------------------------------------------------------------------------------------------------ .
C ∗ 3 1 1
--- + --- ( 1 – C∗ ) exp [ 2C∗ ] + --- exp [ 4C∗ ]
8 2 8
C∗ E asymp C∗ E asymp
0 1 0.6 0.977
0.1 1 0.7 0.958
0.2 1 0.8 0.932
0.3 0.999 0.9 0.900
0.4 0.996 1 0.861
0.5 0.989

Algebraic coefficients
0 1 2 3 4
a 0.9562 0.2742 –0.5082
b 0.4135 –3.7205 8.5532 –7.0115 1.9323
c 100
d –0.3713 3.3240 –13.0859 17.6198 –7.5629
g 0.5000 0.6022 –0.1819

132
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SERP-CU-6
0.6
0.9 C* 0.9
0.7
0.0 0.8
0.1
0.2 0.9
0.8 0.3 1.0 0.8
0.4
0.5 C*
ESDU Copyright material. For current status contact ESDU.

0.7 0.7

E E
Nolocal
No temperature
temperaturemeet
cross
0.6 0.6
133

0.5 0.5

0.4 0.4

ESDU 98005
Configuration Data
95% of Emax See Table 12.6
Index of Geometries
0.3 0.3
See Section 6.1

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 56 FOUR-PASS SERPENTINE WITH COUNTER-CURRENT FLOW, ( M p smaller OUTSIDE TUBES
ESDU 98005
TABLE 12.7
Serpentine SERP-CU-7
6 Passes

·c )
(M p smaller in either stream

Relationship between E , N TU and C∗


ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5.

Asymptotic expression
.
C∗ E asymp
0 1
0.1 1
0.2 1
0.3 1
0.4 1
0.5 0.998
0.6 0.995
0.7 0.986
0.8 0.969
0.9 0.941
1 0.902

Algebraic coefficients
0 1 2 3 4
a 1.2351 –0.2756 –0.1556
b –0.9102 6.8629 –19.6552 23.4640 –9.6433
c 100
d –0.9363 4.6876 –9.5921 8.1334 –2.3421
g 0.0000 0.0000 0.0000

134
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SERP-CU-7
0.9 0.9
0.6
0. 7
C* 0. 8
0.0 0.9
0.8 0.1 0.8
1 .0
0.2
0.3 C*
0.4
ESDU Copyright material. For current status contact ESDU.

0.5
0.7 0.7

E E
Nolocal
No temperature
temperaturemeet
meet
0.6 0.6
135

0.5 0.5

95% of Emax

0.4 0.4

ESDU 98005
Configuration Data
See Table 12.7
0.3 Index of Geometries 0.3
See Section 6.1

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU

·c )
FIGURE 57 SIX-PASS SERPENTINE WITH COUNTER-CURRENT FLOW, ( M p smaller IN EITHER STREAM
ESDU 98005
TABLE 12.8

Serpentine SERP-CU-8
9 Passes

·c )
(M p smaller in either stream



Relationship between E , N TU and C∗
ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5.

Asymptotic expression
.
C∗ E asymp
0 1
0.1 1
0.2 1
0.3 1
0.4 1
0.5 1
0.6 0.999
0.7 0.997
0.8 0.989
0.9 0.969
1 0.932

Algebraic coefficients
0 1 2 3 4
a 1.0884 0.1978 –0.4222
b –0.1316 0.4347 –0.3110 –0.4997 0.5967
c 100
d –0.4722 0.6473 1.8862 –3.9303 1.8361
g 0.0000 0.0000 0.0000

136
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SERP-CU-8 C*
0.0
0.9 0.1 0.9
0.2
0.3
0.4 0. 6
0.5 0. 7
0.8 0.8
0. 8
0. 9
1. 0
ESDU Copyright material. For current status contact ESDU.

C*
0.7 0.7

E E
NoNotemperature meet
local temperature meet
0.6 0.6
137

0.5 0.5

0.4 0.4

ESDU 98005
95% of Emax Configuration Data
See Table 12.8
0.3 Index of Geometries 0.3
See Section 6.1

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU

·c )
FIGURE 58 NINE-PASS SERPENTINE WITH COUNTER-CURRENT FLOW, ( M p smaller IN EITHER STREAM
ESDU 98005
12.2 Serpentine, Co-current

TABLE 12.9
Serpentine
SERP-CO-1
2 Passes

·c )
(M p smaller inside tubes



ESDU Copyright material. For current status contact ESDU.

Relationship between E , N TU and C∗

2C∗ – N TU C∗
E = 1 – ---- –  1 – ---- exp – ---------- where K = 1 – exp  ---------------------  .
K K
2  2 K  2 

Asymptotic expression

E asymp = ---  1 – exp -------  .


1 –2
2 C∗ 
Since the curves pass through a maximum before reaching the asymptotic value, the following data
are provided to assist their use.
C∗ E E for N TU = 100 E
max asymp
0 1 1 1
0.1 0.885 0.503 0.500
0.2 0.808 0.500 0.500
0.3 0.746 0.499 0.499
0.4 0.694 0.497 0.497
0.5 0.649 0.491 0.491
0.6 0.609 0.482 0.482
0.7 0.575 0.471 0.471
0.8 0.544 0.459 0.459
0.9 0.516 0.446 0.466
1 0.491 0.432 0.432

Algebraic coefficients
0 1 2 3 4
a –0.1616 0.2760 –0.1324
b 6.580 –29.6358 55.6137 –48.8342 16.6562
c 100
d –0.9800 0.0000 –0.0200 0.0000 –0.8000
g 0.0628 1.1118 –0.3325

138
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SERP-CO-1
0.9 0.9

0.8 C* 0.8
0.0
0.1
ESDU Copyright material. For current status contact ESDU.

0.2
0.3
0.7 0.4 0.7
0.5
E E
0.6
0.6 0.6
0.7
0.8
139

0.9
0.5 1.0 0.5
C*

0.4 0.4
95% of Emax

ESDU 98005
Temperature meet
Configuration Data
0.3 See Table 12.9 0.3
Index of Geometries
See Section 6.2

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·
FIGURE 59 TWO-PASS SERPENTINE WITH CO-CURRENT FLOW, ( M c p ) smaller INSIDE TUBES
ESDU 98005
TABLE 12.10
Serpentine SERP-CO-2
2 Passes

·c )
(M p smaller outside tubes


Relationship between E , N TU and C∗


ESDU Copyright material. For current status contact ESDU.

E = ------- + 1 – ---- –  1 – ---- exp [ – 2C∗ K ] ,


1 K K
C∗ 2  2
– N TU
where K = 1 – exp  -------------- .
 2 

Asymptotic expression
1
E asymp = ---------- ( 1 – exp [ – 2 C∗ ] ) .
2C∗
Since the curves pass through a maximum before reaching the asymptotic value, the following data
are provided to assist their use.
C∗ E E for NTU = 100 E
max asymp
0 1 1 1
0.1 0.908 0.906 0.906
0.2 0.832 0.824 0.824
0.3 0.766 0.752 0.752
0.4 0.710 0.688 0.688
0.5 0.661 0.632 0.632
0.6 0.618 0.582 0.582
0.7 0.581 0.538 0.538
0.8 0.547 0.499 0.499
0.9 0.518 0.464 0.464
1 0.491 0.432 0.432

Algebraic coefficients
0 1 2 3 4
a –0.0119 –0.0180 0.0118
b 1.1109 –4.0654 7.1311 –5.6782 2.0526
c 100
d –0.3100 0.5483 –4.8500 6.6667 –4.3250
g 0.2300 0.6271 –0.1291

140
NTU

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10


1.0 1.0

SERP-CO-2 C*
0.9 0.0 0.9
0.1
0.2
0.3

0.8 0.8
ESDU Copyright material. For current status contact ESDU.

0.4
0.7 0.7
0.5
E E
0.6
0.6 0.6
0.7
0.8
141

0.9
0.5 1.0 0.5
C*

95% of Emax
0.4 0.4

ESDU 98005
Temperature meet
Configuration Data
See Table 12.10
0.3 Index of Geometries 0.3
See Section 6.2

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·
FIGURE 60 TWO-PASS SERPENTINE WITH CO-CURRENT FLOW, ( M c p ) smaller OUTSIDE TUBES
ESDU 98005
TABLE 12.11

Serpentine SERP-CO-3
3 Passes

·c )
(M p smaller inside tubes



Relationship between E , N TU and C∗
ESDU Copyright material. For current status contact ESDU.

E = 1 – A,
K 2
A = K 1 – ---- + -------  1 – ---- exp – ------- +  1 – ---- exp ----------
K K K K –3K
where
4 C∗  2 C ∗  2  C∗

– N TU C∗
and K = 1 – exp  --------------------- .
 3 

Asymptotic expression

E asymp = 1 –  --- + ---------- exp ------- – --- exp ---------- .


3 1 –1 1 –3
 4 2C∗ C∗ 8 – C∗
C∗ E asymp
0 1
0.1 1
0.2 0.978
0.3 0.914
0.4 0.836
0.5 0.762
0.6 0.699
0.7 0.646
0.8 0.600
0.9 0.561
1 0.528

142
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SERP-CO-3
0.9 0.9

C*
0.0
0.1
0.8 0.2 0.8
0.3
0.4
ESDU Copyright material. For current status contact ESDU.

0.5

0.7 0.7

E E
0.6
0.6 0.6
0.7
0.8
143

0.9
0.5 1.0 0.5
C*

95% of Emax
0.4 Temperature meet 0.4

ESDU 98005
Configuration Data
See Table 12.11
0.3 Index of Geometries 0.3
See Section 6.2

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·
FIGURE 61 THREE-PASS SERPENTINE WITH CO-CURRENT FLOW, ( M c p ) smaller INSIDE TUBES
ESDU 98005
TABLE 12.12
Serpentine SERP-CO-4
3 Passes

·c )
(M p smaller outside tubes

Relationship between E , N TU and C∗


ESDU Copyright material. For current status contact ESDU.

1
E = ------- ( 1 – A ) ,
C∗
where K 2
1 – ---- + C∗ K  1 – ---- exp [ – C∗ K ] +  1 – ---- exp [ – 3C∗ K ]
K K
A=K
4  2 2
– N TU
and K = 1 – exp  -------------- .
 3 

Asymptotic expression
3 C∗
E asymp = ------- 1 –  --- + ------- exp [ – C∗ ] – --- exp [ – 3 C∗ ] .
1 1
C ∗  4 2  8
C∗ E asymp
0 1
0.1 0.909
0.2 0.834
0.3 0.772
0.4 0.720
0.5 0.675
0.6 0.637
0.7 0.604
0.8 0.576
0.9 0.550
1 0.528

Algebraic coefficients
0 1 2 3 4
a –0.0053 0.0644 –0.0032
b 1.2620 –8.5717 20.1061 –19.9773 7.1039
c 1
d –0.2412 –0.4887 4.2139 –6.8074 3.0534
g 0.0665 0.5928 –0.0868

144
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SERP-CO-4
0.9 0.9
C*
0.0
0.1
0.8 0.2 0.8
0.3
0.4
0.5
ESDU Copyright material. For current status contact ESDU.

0.7 0.7

E E
0.6
0.6 0.7 0.6
0.8
0.9
145

1.0
0.5 0.5
C*
95% of Emax
Temperature meet

0.4 0.4

ESDU 98005
Configuration Data
See Table 12.12
0.3 Index of Geometries 0.3
See Section 6.2

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU

·
FIGURE 62 THREE-PASS SERPENTINE WITH CO-CURRENT FLOW, ( M c p ) smaller OUTSIDE TUBES
ESDU 98005
TABLE 12.13
Serpentine SERP-CO-5
4 Passes

·c )
(M p smaller inside tubes

– Equivalent to
CRO-TUBE-MP-CO-21

Relationship between E , N TU and C∗


ESDU Copyright material. For current status contact ESDU.

E = 1 – A,
2
K 3
A = ----  1 – ---- + ------ + K  1 – ---- 1 + 2 -------  1 – ---- exp ---------- +  1 – ---- exp ----------
K K K K K K –2 K –4 K
where
2  2 4  2  C∗  2  C∗  2  C∗
– N TU C∗
and K = 1 – exp  ---------------------  .
 4 

Asymptotic expression

E asymp = --- – ---  1 + ------- exp ------- – --- exp ------- .


5 1 1 –2 1 –4
8 2  C∗  C∗ 8 C∗
Since the curves pass through a maximum before reaching the asymptotic value, the following data
are provided to assist their use.
C∗ Emax E for NTU = 100 E asymp
0 1 1 1
0.1 0.903 0.655 0.625
0.2 0.828 0.627 0.625
0.3 0.765 0.622 0.622
0.4 0.711 0.613 0.613
0.5 0.664 0.597 0.597
0.6 0.623 0.577 0.577
0.7 0.586 0.555 0.555
0.8 0.554 0.532 0.532
0.9 0.525 0.509 0.509
1 0.499 0.487 0.487

Algebraic coefficients
0 1 2 3 4
a –0.0328 0.0636 –0.0326
b 0.0250 0.0210 0.0110 0.0000 0.0660
c 100
d –0.1300 0.0000 –0.2000 –0.3000 –1.5000
g –0.5554 1.7031 –0.4624

146
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SERP-CO-5
(Also CRO-TUBE-MP-CO-21)
0.9 0.9

0.8 C* 0.8
0.0
0.1
0.2
ESDU Copyright material. For current status contact ESDU.

0.3
0.7 0.4 0.7
0.5

E E
0.6
0.6 0.7 0.6

0.8
147

0.9
0.5 1.0 0.5
95% of Emax C*
Temperature meet

0.4 0.4

ESDU 98005
Configuration Data
See Table 12.13
0.3 Index of Geometries 0.3
See Section 6.2

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·
FIGURE 63 FOUR-PASS SERPENTINE WITH CO-CURRENT FLOW, ( M c p ) smaller INSIDE TUBES
ESDU 98005
TABLE 12.14
Serpentine SERP-CO-6
4 Passes

·c )
(M p smaller outside tubes


Equivalent to
– CRO-TUBE-MP-CO-22

Relationship between E , N TU and C∗


ESDU Copyright material. For current status contact ESDU.

1
E = ------- ( 1 – A ) , where
C∗
2
K 3
A = ----  1 – ---- + ------ + K  1 – ---- 1 + 2C∗ K  1 – ---- exp [ – 2 C∗ K ] +  1 – ---- exp [ – 4 C∗ K ]
K K K K K
2 2 4  2  2  2
– N TU
and K = 1 – exp  --------------  .
 4 

Asymptotic expression
1 5 1 1
E asymp = ------- --- – --- ( 1 + C∗ ) exp [ – 2C∗ ] – --- exp [ – 4C∗ ] .
C∗ 8 2 8
Since the curves pass through a maximum before reaching the asymptotic value, the following data
are provided to assist their use.
C∗ E max E for NTU = 100 E asymp
0 1 1 1
0.1 0.909 0.909 0.909
0.2 0.833 0.833 0.833
0.3 0.769 0.768 0.768
0.4 0.714 0.713 0.713
0.5 0.666 0.664 0.664
0.6 0.625 0.621 0.621
0.7 0.588 0.583 0.583
0.8 0.555 0.548 0.548
0.9 0.526 0.516 0.516
1 0.499 0.487 0.487

Algebraic coefficients
0 1 2 3 4
a 0.0007 –0.0036 0.0011
b 0.0120 0.0010 0.0010 0 0.0470
c 100
d –0.1 0 0 –0.2000 –1.1000
g 0.1178 0.5322 –0.0750

148
NTU

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10


1.0 1.0

SERP-CO-6
0.9 (Also CRO-TUBE-MP-CO-22) 0.9

0.8 C* 0.8
0.0
0.1
ESDU Copyright material. For current status contact ESDU.

0.2
0.3
0.7 0.7
0.4
0.5
E E
0.6
0.6 0.7 0.6

0.8
149

0.9
0.5 1.0 0.5
C*

95% of Emax

0.4 Temperature meet 0.4

ESDU 98005
Configuration Data
See Table 12.14
0.3 Index of Geometries 0.3
See Section 6.2

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·
FIGURE 64 FOUR-PASS SERPENTINE WITH CO-CURRENT FLOW, ( M c p ) smaller OUTSIDE TUBES
ESDU 98005
13. DATA FOR SHELL-AND-TUBE CONFIGURATIONS

13.1 Single E-shell

TABLE 13.1
Shell-and-tube SAT-E-SS-1
1 E-Shell
Any even number of tube
passes
·c )
(M p smaller in either stream
– Two tube passes Large even number of tube passes
ESDU Copyright material. For current status contact ESDU.

> 5 Baffles

Relationship between E , N TU and C * . (See Derivation 1.)

2 – E ( 1 + C∗ – η )
log -----------------------------------------
2 ( exp [ NTU η ] – 1 ) e
2 – E ( 1 + C∗ + η )
E = -------------------------------------------------------------------------------------------- , NTU = ---------------------------------------------------- ,
( 1 + C∗ + η ) exp [ NTU η ] – ( 1 + C∗ – η ) η

2 ½
where η = ( C∗ + 1 ) .

Asymptotic expression
2
Easymp = ------------------------ .
1 + C∗ + η
C∗ E asymp C∗ E asymp
0 1 0.6 0.72
0.1 0.95 0.7 0.68
0.2 0.90 0.8 0.65
0.3 0.85 0.9 0.62
0.4 0.81 1 0.59
0.5 0.76

Algebraic coefficients
0 1 2 3 4
a 0.4925 –0.4799 0.1590
b –0.3470 6.6333 –17.0208 16.6687 –5.7242
c 100
d 0.1672 –4.5412 10.1234 –8.4520 2.4446
g 0.3481 0.7264 –0.2039

150
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SAT-E-SS-1
0.9 0.9

C*
0.8 0.8
0.0
0.1
0.2
ESDU Copyright material. For current status contact ESDU.

0.3 0.6
0.7 0.4 0.7
0.5 0.7
0.8
E E
0.9
0.6 1.0 0.6
*
C
151

0.5 0.5

95% of Emax
0.4 0.4
Temperature meet

ESDU 98005
Configuration Data
See Table 13.1
0.3 Index of Geometries 0.3
See Section 7.1

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 65 E-SHELL WITH EVEN NUMBER OF TUBE PASSES, MORE THAN FIVE BAFFLES, ( M p smaller IN EITHER STREAM
ESDU 98005
TABLE 13.2

Shell-and-tube SAT-E-SS-2
1 E-Shell
3 Tube passes
·c )
(M p smaller on tubeside

> 5 Baffles

Relationship between E , N TU and C∗ . (See Derivation 3.)
ESDU Copyright material. For current status contact ESDU.

x–1
E = -------------- ,
x – C∗

3  ------- – 1 φ 1 exp ( η1 ) + φ2 λ exp ( η 1 ) + 2λ exp ( –3D 1 )


2
 C∗ 
where x = ----------------------------------------------------------------------------------------------------------------------------- ,
6φ 1
λφ 2 + 2λ exp ( η1 ) exp ( 3D1 ) –  --------- + 3φ 1
 C∗ 

C∗ λN TU C∗ λN TU
φ 1 = 2 sinh  ---------------------- , φ 2 = 2 cosh  --------------------- ,
 6   6 
1⁄ 2 N TU C∗ NTU
 1 
λ =  9 – -------  1 – ------- 
4
, η 1 = ----------- and D1 = ----------------- .
 C∗  C∗  3 6

Asymptotic expression
Easymp = 1 .

Algebraic coefficients
0 1 2 3 4
a 1 0 0
b –6.3760 26.1970 –49.7060 44.3240 –15.0130
c 1
d –0.1900 0.3790 –0.4900 0.5210 –0.2570
g 0.3765 0.7149 –0.2045

152
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SAT-E-SS-2
0.9 0.9

0.8 0.8
*
C
0.0
ESDU Copyright material. For current status contact ESDU.

0.1
0.7 0.2 0. 6 0.7
0.3
0.4 0.7
E 0.5 0.8 E
0.9
0.6 0.6
1.0
C*
153

0.5 0.5
95% of Emax
Temperature meet
0.4 0.4

ESDU 98005
Configuration Data
See Table 13.2
0.3 0.3
Index of Geometries
See Section 7.1

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 66 E-SHELL WITH THREE TUBE PASSES, MORE THAN FIVE BAFFLES, ( M p smaller ON TUBESIDE
ESDU 98005
TABLE 13.3

Shell-and-tube SAT-E-SS-3
1 E-Shell
3 Tube passes
·c )
(M p smaller on shellside

> 5 Baffles

Relationship between E , N TU and C∗ . (See Derivation 3.)
ESDU Copyright material. For current status contact ESDU.

x–1
E = ------------------ ,
C∗ x – 1
3 ( 2C∗ – 1 )φ 1 exp ( η 1 ) + λ exp ( η 1 )φ 2 + 2λ exp ( – 3D1 )
where x = -------------------------------------------------------------------------------------------------------------------------------- ,
λφ2 + 2λ exp ( η 1 ) exp ( 3D1 ) – 6φ 1 C∗ + 3φ 1

λN TU NTU
φ 1 = 2 sinh  -------------- , φ 2 = 2 cosh  ---------- ,
 6   6 

1⁄ 2 C∗ N TU NTU
λ = { 9 – 4C∗ ( 1 – C∗ ) } , η 1 = ------------------ and D1 = ---------- .
3 6

Asymptotic expression
Easymp = 1 .

Algebraic coefficients
0 1 2 3 4
a 1 0 0
b –4.8170 20.3290 –40.6850 37.3920 –12.7830
c 1
d –0.0160 0.1460 –0.4510 0.4440 –0.1570
g 0.3805 0.6907 –0.1925

154
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SAT-E-SS-3
0.9 0.9

0.8 C* 0.8
0.0
0.1
0.2
ESDU Copyright material. For current status contact ESDU.

0.3
0.7 0.4 0. 6 0.7
0.5
0. 7
E 0.8 E
0.9
0.6 0.6
1.0
C*
155

0.5 0.5

95% of Emax
Temperature meet
0.4 0.4
Configuration Data

ESDU 98005
See Table 13.3
Index of Geometries
0.3 See Section 7.1 0.3

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 67 E-SHELL WITH THREE TUBE PASSES, MORE THAN FIVE BAFFLES, ( M p smaller ON SHELLSIDE
ESDU 98005
TABLE 13.4

Shell-and-tube SAT-E-SS-4
1 E-Shell
2 Tube Passes
·c )
(M p smaller in either stream

1 Baffle
*
Co-current
Relationship between E , N TU and C*
ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5. See Derivation 9.

Asymptotic expression
Since the curves pass through a maximum before reaching the asymptotic value, the following data are
provided to assist their use.

C∗ E max E for N TU = 100 E asymp


0 1 1 1
0.1 0.919 0.477 0
0.2 0.854 0.347 0
0.3 0.798 0.286 0
0.4 0.748 0.249 0
0.5 0.703 0.223 0
0.6 0.662 0.202 0
0.7 0.625 0.183 0
0.8 0.592 0.164 0
0.9 0.561 0.145 0
1 0.533 0.132 0

Algebraic coefficients
0 1 2 3 4
a 0.1657 –0.1275 0.0274
b 5.8903 –25.0230 48.5548 –44.4357 15.2967
c 100.000
d –1.0537 3.6272 –12.1106 15.3467 –6.3161
g –1.6000 3.3076 –1.0669

*
A co-current configuration is defined as one where the tubeside inlet is located adjacent to the shellside inlet.

156
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SAT-E-SS-4
0.9 0.9
C*
0.0

0.1
0.8 0.8
0.2

0.3
ESDU Copyright material. For current status contact ESDU.

0.7 0.4 0.7


0.6
0.5
E 0.7 E

0.6 0.8 0.6


0.9
1.0
157

0.5 C* 0.5
95% of Emax
Temperature meet
0.4 0.4
Configuration Data
See Table 13.4

ESDU 98005
Index of Geometries
0.3 See Section 7.1 0.3

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 68 E-SHELL WITH TWO TUBE PASSES, ONE BAFFLE, CO-CURRENT FLOW IN FIRST TUBESIDE PASS, ( M p smaller IN EITHER STREAM
ESDU 98005
TABLE 13.5

Shell-and-tube SAT-E-SS-5
1 E-Shell
2 Tube passes
·c )
(M p smaller in either stream

1 Baffle
*
Counter-current
Relationship between E , N TU and C*
ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5. See Derivation 9.

Asymptotic expression
Easymp = 1 .

Algebraic coefficients
0 1 2 3 4
a 1 0 0
b –5.3900 20.3390 –35.1400 28.8510 –9.1150
c 1
d –0.2200 0.2270 0.1820 –0.3650 0.1220
g 0.4493 –0.6088 0.6607

*
A counter-current configuration is defined as one where the tubeside outlet is located adjacent to the shellside inlet.

158
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SAT-E-SS-5
0.9 0.9

0.8 0.8
*
C
0.0
ESDU Copyright material. For current status contact ESDU.

0.1
0.7 0.2 0.7
0.3 0. 6
0.4 0.7
E 0.5 0.8 E
0.9
0.6 0.6
1.0
C*
159

0.5 0.5
95% of Emax
Temperature meet

0.4 0.4

ESDU 98005
Configuration Data
0.3 See Table 13.5 0.3
Index of Geometries
See Section 7.1

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 69 E-SHELL WITH TWO TUBE PASSES, ONE BAFFLE, COUNTER-CURRENT FLOW, ( M p smaller IN EITHER STREAM
ESDU 98005
TABLE 13.6

Shell-and-tube SAT-E-SS-6
1 E-Shell
2 Tube passes
·c )
(M p smaller in either stream

2 Baffles
*
Co-current
Relationship between E , N TU and C*
ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5. See Derivation 9.

Asymptotic expression
Since the curves pass through a maximum before reaching the asymptotic value, the following data
are provided to assist their use.

C∗ E max E for N TU = 100 E asymp


0 1 1 1
0.1 0.931 0.665 0
0.2 0.873 0.546 0
0.3 0.820 0.475 0
0.4 0.771 0.423 0
0.5 0.726 0.377 0
0.6 0.685 0.331 0
0.7 0.648 0.284 0
0.8 0.613 0.237 0
0.9 0.582 0.199 0
1 0.553 0.172 0

Algebraic coefficients
0 1 2 3 4
a 0.2939 –0.2702 0.0819
b 1.8560 1.5240 –21.0960 –35.7650 –14.7980
c 100
d –0.5810 –10.8560 32.9960 –38.4420 15.3470
g –2.3779 4.1457 –1.2846

*
A co-current arrangement is defined as one where the tubeside inlet is located adjacent to the shellside inlet.

160
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SAT-E-SS-6
0.9 0.9

0.8 0.8
*
C
0.0
ESDU Copyright material. For current status contact ESDU.

0.1
0.7 0.2 0.7
0.6
0.3
0.4 0.7
E 0.5 E
0.8
0.6 0.9 0.6

1.0

C*
161

0.5 0.5
95% of Emax
Temperature meet

0.4 0.4

ESDU 98005
Configuration Data
See Table 13.6
0.3 0.3
Index of Geometries
See Section 7.1

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 70 E-SHELL WITH TWO TUBE PASSES, TWO BAFFLES, CO-CURRENT FLOW, ( M p smaller IN EITHER STREAM
ESDU 98005
TABLE 13.7

Shell-and-tube SAT-E-SS-7
1 E-Shell
2 Tube passes
·c )
(M p smaller in either stream

2 Baffles
*
Counter-current
Relationship between E , N TU and C*
ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5. See Derivation 9.

Asymptotic expression
Easymp = 1 .

Algebraic coefficients
0 1 2 3 4
a 1 0 0
b –7.1600 31.7230 –62.8470 57.4930 –19.7760
c 1
d –0.2200 0.5460 –0.8650 0.7290 –0.2640
g –3.1144 4.3606 –1.1615

*
A counter-current configuration is defined as one where the tubeside outlet is located adjacent to the shellside inlet.

162
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SAT-E-SS-7
0.9 0.9

0.8 0.8
*
C
0.0
ESDU Copyright material. For current status contact ESDU.

0.1
0.2
0.7
0.3 0 .6 0.7
0.4 0. 7
E 0.5
0.8 E
0.9
0.6 0.6
1.0
C*
163

0.5 0.5
95% of Emax
Temperature meet

0.4 0.4

ESDU 98005
Configuration Data
See Table 13.7
0.3 Index of Geometries 0.3
See Section 7.1

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 71 E-SHELL WITH TWO TUBE PASSES, TWO BAFFLES, COUNTER-CURRENT FLOW, ( M p smaller IN EITHER STREAM
ESDU 98005
TABLE 13.8

Shell-and-tube SAT-E-SS-8
1 E-Shell
2 Tube passes
·c )
(M p smaller in either stream

3 Baffles
*
Co-current
Relationship between E , N TU and C*
ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5. See Derivation 9.

Asymptotic expression
Since the curves pass through a maximum before reaching the asymptotic value, the following data
are provided to assist their use.

C∗ E max E for NTU = 100 E asymp


0 1 1 1
0.1 0.937 0.711 0
0.2 0.882 0.596 0
0.3 0.830 0.552 0
0.4 0.782 0.463 0
0.5 0.738 0.409 0
0.6 0.697 0.357 0
0.7 0.659 0.306 0
0.8 0.624 0.261 0
0.9 0.592 0.226 0
1 0.563 0.202 0

Algebraic coefficients
0 1 2 3 4
a 0.3584 –0.3487 0.1157
b 1.1090 5.6610 –30.3560 42.1080 –18.2900
c 100
d 0.6540 –11.4160 35.0760 –41.2540 16.6220
g –6.8712 9.7051 –3.0088

*
A co-current configuration is defined as one where the tubeside inlet is located adjacent to the shellside inlet.

164
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SAT-E-SS-8 C*
0.0
0.9 0.9
0.1

0.2

0.8 0.3 0.8

0.4
ESDU Copyright material. For current status contact ESDU.

0.5
0.7 0.6 0.7
0.7
E 0.8 E

0.6 0.9 0.6


1.0
C*
165

0.5 0.5
95% of Emax
Temperature meet
0.4 0.4

ESDU 98005
Configuration Data
See Table 13.8
0.3 Index of Geometries 0.3
See Section 7.1

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 72 E-SHELL WITH TWO TUBE PASSES, THREE BAFFLES, CO-CURRENT FLOW, ( M p smaller IN EITHER STREAM
ESDU 98005
TABLE 13.9

Shell-and-tube SAT-E-SS-9
1 E-Shell
2 Tube passes
·c )
(M p smaller in either stream

3 Baffles
*
Counter-current
Relationship between E , N TU and C*
ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5. See Derivation 9.

Asymptotic expression
Easymp = 1 .

Algebraic coefficients
0 1 2 3 4
a 1 0 0
b –5.5249 20.9132 –37.0698 30.9965 –9.8864
c 1
d –0.0650 –0.1723 0.7969 –0.9896 0.3906
g –3.6755 4.9267 –1.3063

*
A counter-current configuration is defined as one where the tubeside outlet is located adjacent to the shellside inlet.

166
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SAT-E-SS-9
0.9 0.9

C*
0.0
0.1
0.8 0.2 0.8
0.3
0.4
0.5
ESDU Copyright material. For current status contact ESDU.

0.7 0.6 0.7


0. 7
E 0. 8 E
0. 9
0.6 0.6
1. 0
*
C
167

0.5 0.5
95% of Emax
Temperature meet

0.4 0.4

ESDU 98005
Configuration Data
0.3 See Table 13.9 0.3
Index of Geometries
See Section 7.1

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 73 E-SHELL WITH TWO TUBE PASSES, THREE BAFFLES, COUNTER-CURRENT FLOW, ( M p smaller IN EITHER STREAM
ESDU 98005
TABLE 13.10

Shell-and-tube SAT-E-SS-10
1 E-Shell
2 Tube passes
·c )
(M p smaller in either stream

4 Baffles
*
Co-current
Relationship between E , N TU and C*
ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5. See Derivation 9.

Asymptotic expression
Since the curves pass through a maximum before reaching the asymptotic value, the following data
are provided to assist their use.

C∗ E max E for N TU = 100 E asymp


0 1 1 1
0.1 0.941 0.782 0
0.2 0.886 0.684 0
0.3 0.836 0.604 0
0.4 0.789 0.529 0
0.5 0.744 0.458 0
0.6 0.703 0.391 0
0.7 0.666 0.332 0
0.8 0.630 0.283 0
0.9 0.598 0.246 0
1 0.569 0.220 0

Algebraic coefficients
0 1 2 3 4
a 0.3890 –0.3706 0.1189
b 0.8118 5.6410 –24.0789 30.2466 –12.3755
c 100
d –0.2342 –2.6371 6.5706 –5.8350 1.7966
g –9.1837 12.3459 –3.7575

*
A co-current configuration is defined as one where the tubeside inlet is located adjacent to the shellside inlet.

168
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SAT-E-SS-10
0.9 C* 0.9
0.0
0.1
0.2
0.3
0.8 0.4 0.8
0.5
ESDU Copyright material. For current status contact ESDU.

0.6
0.7 0.7
0.7
E 0.8 E
0.9
0.6 0.6
1.0
C*
169

0.5 0.5
95% of Emax
Temperature meet
0.4 0.4

ESDU 98005
Configuration Data
0.3 See Table 13.10 0.3
Index of Geometries
See Section 7.1

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 74 E-SHELL WITH TWO TUBE PASSES, FOUR BAFFLES, CO-CURRENT FLOW, ( M p smaller IN EITHER STREAM
ESDU 98005
TABLE 13.11

Shell-and-tube SAT-E-SS-11
1 E-Shell
2 Tube passes
·c )
(M p smaller in either stream

4 Baffles
*
Counter-current
Relationship between E , N TU and C*
ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5. See Derivation 9.

Asymptotic expression
Easymp = 1 .

Algebraic coefficients
0 1 2 3 4
a 1 0 0
b –5.6458 22.4366 –41.9078 36.7585 –12.2119
c 1
d –0.0800 0.1125 –0.0625 0 0
g –2.8624 3.8189 –0.9479

*
A counter-current configuration is defined as one where the tubeside outlet is located adjacent to the shellside inlet.

170
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SAT-E-SS-11
0.9 0.9
*
C
0.0
0.1
0.8 0.2 0.8
0.3
0.4
0.5
ESDU Copyright material. For current status contact ESDU.

0.7 0.7
0 .6
E 0.7 E
0. 8
0.6 0. 9 0.6
1.0
C*
171

0.5 0.5
95% of Emax
Temperature meet

0.4 0.4

ESDU 98005
Configuration Data
0.3
See Table 13.11 0.3
Index of Geometries
See Section 7.1

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 75 E-SHELL WITH TWO TUBE PASSES, FOUR BAFFLES, COUNTER-CURRENT FLOW, ( M p smaller IN EITHER STREAM
ESDU 98005
13.2 Multiple E-shells

TABLE 13.12
Shell-and-tube SAT-E-MS-1
2 E-shells
Any even number of tube
passes
·
( M c p ) smaller in either stream
Series/series

Overall counter-current
Relationship between E , N TU and C∗ . (See Derivation 2.)
ESDU Copyright material. For current status contact ESDU.

2 – α ( 1 + C∗ – η )
– loge -----------------------------------------
2 – α ( 1 + C∗ + η ) δ∗
NTU = -------------------------------------------------------------- . ------- ,
η δ
2 ½
where η = ( C∗ + 1 ) ,
( 1⁄ S )
1–X E EC∗ – 1
α = ------------------------- = ---------------------------- , X = --------------------- ,
C∗ – X
( 1⁄ S )
C∗ ≠ 1 S – E ( S – 1 ) C∗ = 1 E–1

C∗ – 1 1–α C∗ – 1 1–E
δ∗ = ------------------------------------ = ------------ , δ = ------------------------------------ = ----------- , S = 2.
1–α α 1–E E
loge ------------------- C∗ ≠ 1 C∗ = 1 loge ------------------- C∗ = 1 C∗ = 1
1 – αC∗ 1 – EC∗

Asymptotic expression
S
Z –1 2S
Easymp = ------------------ = ------------------ ,
Z – C∗ C∗ ≠ 1 2S + 2 C∗ = 1
S

η – C∗ + 1
where Z = ------------------------ .
η + C∗ – 1
C∗ E max C∗ E max
0 1 0.6 0.89
0.1 1 0.7 0.85
0.2 0.99 0.8 0.81
0.3 0.97 0.9 0.78
0.4 0.95 1 0.74
0.5 0.92

Algebraic coefficients
0 1 2 3 4
a 1.1022 –0.7416 0.1177
b –1.8040 8.5229 –12.9323 8.8021 –2.3157
c 100
d –0.0949 –0.4409 –0.9005 2.6621 –1.3703
g –0.2946 1.3929 –0.3773

172
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

C*
0.0
SAT-E-MS-1 0.1
0.9 0.2 0.9
0.3
0.6
0.4
0.5 0.7

0.8 0.8 0.8


0.9

1.0
ESDU Copyright material. For current status contact ESDU.

0.7 C* 0.7

E E

0.6 0.6
173

0.5 0.5
95% of Emax
Temperature meet
0.4 0.4

ESDU 98005
Configuration Data
0.3
See Table 13.12 0.3
Index of Geometries
See Section 7.2

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 76 TWO E-SHELLS IN SERIES, ANY EVEN NUMBER OF TUBE PASSES, ( M p smaller IN EITHER STREAM
ESDU 98005
TABLE 13.13
Shell-and-tube SAT-E-MS-2
3 E-shells
Any even number of tube
passes
·
( M c p ) smaller in either stream
Series/series

Overall counter-current
Relationship between E , N TU and C∗ . (See Derivation 2.)
2 – α ( 1 + C∗ – η )
ESDU Copyright material. For current status contact ESDU.

– loge -----------------------------------------
2 – α ( 1 + C∗ + η ) δ∗
NTU = -------------------------------------------------------------- . ------- ,
η δ
2 ½
where η = ( C∗ + 1 ) ,
( 1⁄ S )
1–X E EC∗ – 1
α = ------------------------- = ---------------------------- , X = --------------------- ,
C∗ – X
( 1⁄ S )
C∗ ≠ 1 S – E ( S – 1 ) C∗ = 1 E–1

C∗ – 1 1–α C∗ – 1 1–E
δ∗ = ------------------------------------ = ------------ , δ = ------------------------------------ = ----------- , S = 3.
1–α α 1–E E
loge ------------------- C∗ ≠ 1 C∗ = 1 loge ------------------- C∗ = 1 C∗ = 1
1 – αC∗ 1 – EC∗
Asymptotic expression
S
Z –1 2S
Easymp = ------------------ = ------------------ ,
Z – C∗ C∗ ≠ 1 2S + 2 C∗ = 1
S

η – C∗ + 1
where Z = ------------------------ .
η + C∗ – 1
C∗ E max C∗ E max
0 1 0.6 0.95
0.1 1 0.7 0.92
0.2 1 0.8 0.89
0.3 1 0.9 0.85
0.4 0.99 1 0.81
0.5 0.97

Algebraic coefficients
0 1 2 3 4
a 1.0689 –0.1906 –0.2590
b –0.6690 0.9210 3.2600 –6.1460 2.8670
c 100
d –0.0870 –0.6360 0.9710 –0.4290 0.0780
g –0.8504 1.7842 –0.4287

174
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SAT-E-MS-2
0.9 0.9
C*
0.0
0.1 0.6
0.2 0. 7
0.8 0.3 0.8
0.8
0.4
0.5 0.9
1.0*
ESDU Copyright material. For current status contact ESDU.

C
0.7 0.7

E E

0.6 0.6
175

0.5 0.5
95% of Emax
Temperature meet
0.4 0.4

ESDU 98005
Configuration Data
See Table 13.13
0.3 Index of Geometries 0.3
See Section 7.2

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 77 THREE E-SHELLS IN SERIES, ANY EVEN NUMBER OF TUBE PASSES, ( M p smaller IN EITHER STREAM
ESDU 98005
TABLE 13.14
Shell-and-tube SAT-E-MS-3
4 E-shells
Any even number of tube
passes
·
( M c p ) smaller in either stream
Series/series

Overall counter-current
Relationship between E , N TU and C∗ . (See Derivation 2.)
2 – α ( 1 + C∗ – η )
ESDU Copyright material. For current status contact ESDU.

– loge -----------------------------------------
2 – α ( 1 + C∗ + η ) δ∗
NTU = -------------------------------------------------------------- . ------- ,
η δ
2 ½
where η = ( C∗ + 1 ) ,
( 1⁄ S )
1–X E EC∗ – 1
α = ------------------------- = ---------------------------- , X = --------------------- ,
C∗ – X
( 1⁄ S )
C∗ ≠ 1 S – E ( S – 1 ) C∗ = 1 E–1

C∗ – 1 1–α C∗ – 1 1–E
δ∗ = ------------------------------------ = ------------ , δ = ------------------------------------ = ----------- , S = 4.
1–α α 1–E E
loge ------------------- C∗ ≠ 1 C∗ = 1 log ------------------- ∗ C∗ = 1
1 – αC∗ e
1 – EC∗ C = 1
Asymptotic expression
S
Z –1 2S
Easymp = ------------------ = ------------------ ,
Z – C∗ C∗ ≠ 1 2S + 2 C∗ = 1
S

η – C∗ + 1
where Z = ------------------------ .
η + C∗ – 1
C∗ E max C∗ E max
0 1 0.6 0.98
0.1 1 0.7 0.96
0.2 1 0.8 0.93
0.3 1 0.9 0.89
0.4 1 1 0.85
0.5 0.99

Algebraic coefficients
0 1 2 3 4
a 0.9606 0.2802 –0.5404
b 0.3910 –4.4280 12.1980 –12.3960 4.4340
c 100
d –0.2800 0.2210 –0.4990 0.7300 –0.2570
g –2.0691 2.8393 –0.6565

176
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SAT-E-MS-3
0.9 0.9
C*
0.0 0. 6
0.1 0.7
0.2
0.3 0.8
0.8 0 .9 0.8
0.4
0.5
1 .0
C*
ESDU Copyright material. For current status contact ESDU.

0.7 0.7

E E

0.6 0.6
177

0.5 0.5
95% of Emax
Temperature meet
0.4 0.4

ESDU 98005
Configuration Data
0.3
See Table 13.14 0.3
Index of Geometries
See Section 7.2

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU

·c )
FIGURE 78 FOUR E-SHELLS IN SERIES, ANY EVEN NUMBER OF TUBE PASSES, ( M p smaller IN EITHER STREAM
ESDU 98005
TABLE 13.15
Shell-and-tube SAT-E-MS-4
5 E-shells
Even number of tube passes
·c )
(M p smaller in either stream
Series/series

Overall counter-current
Relationship between E , N TU and C∗ . (See Derivation 2.)
2 – α ( 1 + C∗ – η )
– loge -----------------------------------------
ESDU Copyright material. For current status contact ESDU.

2 – α ( 1 + C∗ + η ) δ∗
NTU = -------------------------------------------------------------- . ------- ,
η δ
2 ½
where η = ( C∗ + 1 ) ,
( 1⁄ S )
1–X E EC∗ – 1
α = ------------------------- = ---------------------------- , X = --------------------- ,
C∗ – X
( 1⁄ S )
C∗ ≠ 1 S – E ( S – 1 ) C∗ = 1 E–1

C∗ – 1 1–α C∗ – 1 1–E
δ∗ = ------------------------------------ = ------------ , δ = ------------------------------------ = ----------- , S = 5.
1–α α 1–E E
------------------- ∗ -------------------
loge
1 – αC∗ C ≠ 1 C∗ = 1 loge
1 – EC∗ C = 1
∗ C∗ = 1
Asymptotic expression
S
Z –1 2S
Easymp = ------------------ = ------------------ ,
Z – C∗ C∗ ≠ 1 2S + 2 C∗ = 1
S

η – C∗ + 1
where Z = ------------------------ .
η + C∗ – 1
C∗ E max C∗ E max
0 1 0.6 0.99
0.1 1 0.7 0.97
0.2 1 0.8 0.95
0.3 1 0.9 0.92
0.4 1 1 0.88
0.5 1

Algebraic coefficients
0 1 2 3 4
a 0.8800 0.5684 –0.6953
b 0.7090 –4.0290 6.9690 –4.2710 0.7780
c 100
d –0.1600 0.0170 –0.1250 0.2080 0.0000
g –3.0005 3.5326 –0.7806

178
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SAT-E-MS-4
0.9 C* 0.9
0.0
0.1 0. 6
0.2 0. 7
0.3
0.8 0.4 0.8 0.8
0.5 0. 9
1.0
C*
ESDU Copyright material. For current status contact ESDU.

0.7 0.7

E E

0.6 0.6
179

0.5 0.5
95% of Emax
Temperature meet
0.4 0.4

ESDU 98005
Configuration Data
See Table 13.15
0.3 Index of Geometries 0.3
See Section 7.2

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 79 FIVE E-SHELLS IN SERIES, ANY EVEN NUMBER OF TUBE PASSES, ( M p smaller IN EITHER STREAM
ESDU 98005
TABLE 13.16
Shell-and-tube SAT-E-MS-5
6 E-shells
Even number of tube passes
·c )
(M p smaller in either stream
Series/series

Overall counter-current
Relationship between E , N TU and C∗ . (See Derivation 2.)
2 – α ( 1 + C∗ – η )
– loge -----------------------------------------
2 – α ( 1 + C∗ + η ) δ∗
ESDU Copyright material. For current status contact ESDU.

NTU = -------------------------------------------------------------- . ------- ,


η δ
2 ½
where η = ( C∗ + 1 ) ,
( 1⁄ S )
1–X E EC∗ – 1
α = ------------------------- = ---------------------------- , X = --------------------- ,
C∗ – X
( 1⁄ S )
C∗ ≠ 1 S – E ( S – 1 ) C∗ = 1 E–1

C∗ – 1 1–α C∗ – 1 1–E
δ∗ = ------------------------------------ = ------------ , δ = ------------------------------------ = ----------- , S = 6.
1–α α 1–E E
loge ------------------- C∗ ≠ 1 C∗ = 1 loge ------------------- C∗ = 1 C∗ = 1
1 – αC∗ 1 – EC∗
Asymptotic expression
S
Z –1 2S
Easymp = ------------------ = ------------------ ,
Z – C∗ C∗ ≠ 1 2S + 2 C∗ = 1
S

η – C∗ + 1
where Z = ------------------------ .
η + C∗ – 1
C∗ E max C∗ E max
0 1 0.6 1
0.1 1 0.7 0.99
0.2 1 0.8 0.97
0.3 1 0.9 0.94
0.4 1 1 0.90
0.5 1

Algebraic coefficients
0 1 2 3 4
a 0.8342 0.7155 –0.7597
b 1.0290 –6.4630 13.9470 –12.8130 4.4360
c 100
d –0.0500 0.0000 0.0000 0.0000 –0.0010
g –3.4632 3.71210 –0.7722

180
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0
C*
0.0
SAT-E-MS-5 0.1
0. 6
0.9 0.2 0.9
0.3 0. 7
0.4 0. 8
0.5
0.9
0.8 1.0 0.8
C*
ESDU Copyright material. For current status contact ESDU.

0.7 0.7

E E

0.6 0.6
181

0.5 0.5
95% of Emax
Temperature meet
0.4 0.4

ESDU 98005
Configuration Data
See Table 13.16
0.3 Index of Geometries 0.3
See Section 7.2

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU

·c )
FIGURE 80 SIX E-SHELLS IN SERIES, ANY EVEN NUMBER OF TUBE PASSES, ( M p smaller IN EITHER STREAM
ESDU 98005
TABLE 13.17
Shell-and-tube SAT-E-MS-6
2 E-shells
Any even number of tube
passes
·
( M c p ) smaller on parallel side
Series/parallel


Relationship between E , N TU and C∗ . (See Derivation 2.)
ESDU Copyright material. For current status contact ESDU.

2
C∗ E 1
E = E 1 – -------------- ,
4
ηN TU
2  1 – exp  --------------- 
  2 
where E 1 = --------------------------------------------------------------------------------------------------------------
∗ C∗ ηN TU
1 + C ------- – η –  1 + ------- + η exp  -------------- -
 2   2   2 

2
C∗
and η = 1 + --------- .
4
Asymptotic expression
2
C∗ E ′1
E asymp = E ′1 – --------------- ,
4
2
where E′1 = ------------------------------ .
1 + C ∗
------- + η
 2 
C∗ E asymp C∗ E asymp
0 1 0.6 0.744
0.1 0.951 0.7 0.709
0.2 0.905 0.8 0.677
0.3 0.861 0.9 0.647
0.4 0.820 1 0.618
0.5 0.781

Algebraic coefficients
0 1 2 3 4
a 0.4945 –0.3498 0.0913
b 0.6360 –2.5793 5.6236 –5.7121 1.8317
c 100
d –0.5900 2.3814 –5.7905 5.988 –2.2235
g 0.0856 1.0344 –0.3082

182
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SAT-E-MS-6
0.9 0.9
*
C
0.0
0.1
0.8 0.2 0.8
0.3
0.4
0.6
0.5
ESDU Copyright material. For current status contact ESDU.

0.7
0.7 0.7
0.8

E 0.9
E
1.0
0.6 C* 0.6
183

0.5 0.5
95% of Emax
Temperature meet

0.4 0.4

ESDU 98005
Configuration Data
0.3 See Table 13.17 0.3
Index of Geometries
See Section 7.2

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 81 TWO E-SHELLS IN SERIES/PARALLEL, ANY EVEN NUMBER OF TUBE PASSES, ( M p smaller ON PARALLEL SIDE
ESDU 98005
TABLE 13.18
Shell-and-tube SAT-E-MS-7
2 E-shells
Any even number of tube
passes
·c )
(M p smaller on series side
Series/parallel


Relationship between E , N TU and C∗ . (See Derivation 2.)
ESDU Copyright material. For current status contact ESDU.

2
E = 2E 1 – E 1 ,
ηN TU
2  1 – exp  --------------- 
  2 
where E 1 = -------------------------------------------------------------------------------------------------------------------
ηN TU
( 1 + 2C∗ – η ) – ( 1 + 2C∗ + η ) exp  ---------------
 2 
2
and η = 1 + 4C∗ .

Asymptotic expression
′2
E asymp = 2E 1′ – E 1 ,
2
where E′1 = -------------------------------- .
( 1 + 2C∗ + η )
C∗ E asymp C∗ E asymp
0 1 0.6 0.781
0.1 0.990 0.7 0.735
0.2 0.963 0.8 0.693
0.3 0.923 0.9 0.654
0.4 0.877 1 0.618
0.5 0.828

Algebraic coefficients
0 1 2 3 4
a 0.9953 –1.2689 0.5096
b –3.9750 24.2700 –53.1230 51.3190 –18.2770
c 100
d –0.3150 0.1070 –0.0020 –0.0020 –0.0070
g 0.0895 0.9842 –0.2692

184
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SAT-E-MS-7
0.9 0.9

C*
0.0
0.1
0.8 0.2 0.8
0.3 0.6
0.4
0.5 0.7
ESDU Copyright material. For current status contact ESDU.

0.7 0.8 0.7

0.9
E E
1.0
0.6 C* 0.6
185

0.5 0.5
95% of Emax
Temperature meet

0.4 0.4

ESDU 98005
Configuration Data
0.3 See Table 13.18 0.3
Index of Geometries
See Section 7.2

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU

·c )
FIGURE 82 TWO E-SHELLS IN SERIES/PARALLEL, ANY EVEN NUMBER OF TUBE PASSES, ( M p smaller ON SERIES SIDE
ESDU 98005
TABLE 13.19
Shell-and-tube SAT-E-MS-8
3 E-shells
Any even number of tube
passes
·c )
(M p smaller on parallel side
Series/parallel


Relationship between E , N TU and C∗ . (See Derivation 2.)
ESDU Copyright material. For current status contact ESDU.

2 3
C∗ 2 C∗ E 1
E = E 1 – ------- E 1 + ---------------- ,
3 27
ηN TU
 1 – exp  -------------- - 
  3 
where E 1 = --------------------------------------------------------------------------------------------------------------
∗ C∗ ηN TU
1 + C ------- – η –  1 + ------- + η exp ---------------
 3   3  3
2
and C∗
η = 1 + --------- .
9
Asymptotic expression
2 3 2
C∗ E ′1 C∗ E ′1
E asymp = E ′1 – --------------- + ------------------ ,
3 27
2
where E′1 = ------------------------------ .
1 + C ∗
------- + η
 3 
C∗ E asymp C∗ E asymp
0 1 0.6 0.748
0.1 0.951 0.7 0.715
0.2 0.906 0.8 0.683
0.3 0.863 0.9 0.653
0.4 0.822 1 0.626
0.5 0.784

Algebraic coefficients
0 1 2 3 4
a 0.4943 –0.3234 0.0802
b 0.2252 –0.0419 –0.4942 1.0654 –0.5137
c 100
d –0.1990 0.0561 0.1793 –0.2614 0.1122
g –0.0566 1.0758 –0.2760

186
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SAT-E-MS-8 C*
0.9 0.9
0.0
0.1
0.2
0.3
0.8 0.4 0.8
0.5
0.6
ESDU Copyright material. For current status contact ESDU.

0.7
0.7 0.7
0.8
0.9
E E
1.0
0.6 C* 0.6
187

0.5 0.5
95% of Emax
Temperature meet
0.4 0.4

ESDU 98005
Configuration Data
See Table 13.19
0.3 Index of Geometries 0.3
See Section 7.2

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 83 THREE E-SHELLS IN SERIES/PARALLEL, ANY EVEN NUMBER OF TUBE PASSES, ( M p smaller ON PARALLEL SIDE
ESDU 98005
TABLE 13.20
Shell-and-tube SAT-E-MS-9
3 E-shells
Any even number of tube
passes
·c )
(M p smaller on series side
Series/parallel


Relationship between E , N TU and C∗ . (See Derivation 2.)
ESDU Copyright material. For current status contact ESDU.

2 3
E = 3E1 – 3E1 + E1 ,
ηN TU
2  1 – exp  --------------- 
  3 
where E 1 = -------------------------------------------------------------------------------------------------------------------
ηN TU
( 1 + 3C∗ – η ) – ( 1 + 3C∗ + η ) exp  ---------------
 3 

1 + 9C∗ .
2
and η =
Asymptotic expression
2 3
E asymp = 3E ′1 – 3E ′1 + E ′1 ,
2
where E′1 = -------------------------------- .
( 1 + 3C∗ + η )
C∗ E asymp C∗ E asymp
0 1 0.6 0.796
0.1 0.997 0.7 0.748
0.2 0.979 0.8 0.704
0.3 0.943 0.9 0.663
0.4 0.897 1 0.626
0.5 0.847

Algebraic coefficients
0 1 2 3 4
a 1.1535 –1.5365 0.6341
b –3.8510 23.1050 –50.8970 49.7780 –17.9200
c 100
d –0.2000 0.0000 –0.0020 –0.0010 –0.0060
g –0.0272 1.0337 –0.2616

188
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SAT-E-MS-9 C*
0.0
0.9 0.9
0.1
0.2
0.3
0.4
0.5
0.8 0.6 0.8

0.7
ESDU Copyright material. For current status contact ESDU.

0.7 0.8 0.7


0.9
E E
1.0
0.6 C* 0.6
189

0.5 0.5
95% of Emax
Temperature meet
0.4 0.4

ESDU 98005
Configuration Data
0.3 See Table 13.20 0.3
Index of Geometries
See Section 7.2

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU

·c )
FIGURE 84 THREE E-SHELLS IN SERIES/PARALLEL, ANY EVEN NUMBER OF TUBE PASSES, ( M p smaller ON SERIES SIDE
ESDU 98005
TABLE 13.21
Shell-and-tube SAT-E-MS-10
4 E-shells
Even number of tube passes
·c )
(M p smaller on parallel side
Series/parallel


Relationship between E , N TU and C∗ . (See Derivation 2.)
3 2 1 3 2 1 4 3
E = E 1 – --- E 1 C∗ + ------ E 1 C∗ – --------- E 1 C∗ ,
ESDU Copyright material. For current status contact ESDU.

8 16 256
ηN TU
2  1 – exp  --------------- 
  4 
where E 1 = --------------------------------------------------------------------------------------------------------------
∗ C∗ ηN TU
1 + C ------- – η –  1 + ------- + η exp  ---------------
 4   4   4 

2
and C∗
η =
1 + --------- .
16
Asymptotic expression
3 2 1 3 2 1 4 3
E asymp = E ′1 – --- E ′1 C∗ + ------ E ′1 C∗ – --------- E ′1 C∗ ,
8 16 256
2
where E′1 = --------------------------------- .
1 + C ∗
------- + C∗
 4 

C∗ E asymp C∗ E asymp
0 1 0.6 0.750
0.1 0.952 0.7 0.717
0.2 0.906 0.8 0.685
0.3 0.863 0.9 0.655
0.4 0.823 1 0.628
0.5 0.785

Algebraic coefficients
0 1 2 3 4
a 0.4941 –0.3139 0.0766
b –0.2175 5.2367 –16.9873 21.2218 –9.0325
c 100
d 0.2410 –5.3697 16.8948 –20.8343 8.8632
g –0.4142 1.5796 –0.4490

190
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SAT-E-MS-10
0.9 C* 0.9
0.0
0.1
0.2
0.8 0.3 0.8
0.4
0.5
0.6
ESDU Copyright material. For current status contact ESDU.

0.7
0.7 0.7
0.8
0.9
E E
1.0
0.6 C* 0.6
191

0.5 0.5

95% of Emax
Temperature meet
0.4 0.4

ESDU 98005
Configuration Data
See Table 13.21
0.3 0.3
Index of Geometries
See Section 7.2

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 85 FOUR E-SHELLS IN SERIES/PARALLEL, ANY EVEN NUMBER OF TUBE PASSES, ( M p smaller ON PARALLEL SIDE
ESDU 98005
TABLE 13.22
Shell-and-tube SAT-E-MS-11
4 E-shells
Any even number of tube
passes
·c )
(M p smaller on series side
Series/parallel


Relationship between E , N TU and C∗ . (See Derivation 2.)
ESDU Copyright material. For current status contact ESDU.

2 3 4
E = 4E1 – 6E1 + 4E1 – E1 ,
ηN TU
2  1 – exp  --------------- 
  4 
where E 1 = -------------------------------------------------------------------------------------------------------------------
ηN TU
( 1 + 4C∗ – η ) – ( 1 + 4C∗ + η ) exp  ---------------
 4 

2
and η = 1 + 6C∗ .
Asymptotic expression
2 3 ′4
E asymp = 4E ′1 – 6E ′1 + 4E ′1 – E 1 ,
2
where E′1 = -------------------------------- .
( 1 + 4C∗ + η )
C∗ E asymp C∗ E asymp
0 1 0.6 0.802
0.1 0.999 0.7 0.753
0.2 0.985 0.8 0.708
0.3 0.952 0.9 0.666
0.4 0.906 1 0.628
0.5 0.854

Algebraic coefficients
0 1 2 3 4
a 1.2216 –1.6561 0.6913
b –3.3410 15.8830 –27.1560 20.9190 –6.0730
c 100
d –0.2050 –0.0040 –0.0020 –0.0010 –0.0000
g –0.1117 1.0790 –0.2636

192
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SAT-E-MS-11 C*
0.9 0.9
0.0
0.1
0.2
0.3
0.8 0.4 0.6 0.8
0.5
0.7
ESDU Copyright material. For current status contact ESDU.

0.8
0.7 0.7
0.9
E 1.0 E

0.6 C* 0.6
193

0.5 0.5
95% of Emax
Temperature meet
0.4 0.4

ESDU 98005
Configuration Data
0.3 See Table 13.22 0.3
Index of Geometries
See Section 7.2

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 86 FOUR E-SHELLS IN SERIES/PARALLEL, ANY EVEN NUMBER OF TUBE PASSES, ( M p smaller ON SERIES SIDE
ESDU 98005
13.3 Single F-shells

TABLE 13.23

Shell-and-tube SAT-F-SS-1
1 F-shell

·c )
(M p smaller on tubeside

Y = 0.02
ESDU Copyright material. For current status contact ESDU.


Relationship between E , N TU and C∗ . (See Derivation 7.)

2X
E = --------------------------------- ,
1 + X + C∗ X
exp ( ZN TU ) – 1
where X = -------------------------------------------------- ,
Z [ exp ( ZN TU ) + 1 ]

2
Z = 4C∗ 2 Y + ( 1 – C∗ )
and Y = 0.2 .

Asymptotic expression
2X′
E asymp = ------------------------------------- ,
1 + X′ + C∗ X′
1
where X′ = --- .
Z
C∗ E asymp C∗ E asymp
0 1 0.6 0.983
0.1 1 0.7 0.971
0.2 0.999 0.8 0.951
0.3 0.997 0.9 0.920
0.4 0.995 1 0.876
0.5 0.990

194
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SAT-F-SS-1
C* 0. 6
0.9 0.9
0. 7
0.0
0.1 0. 8
0.2
0. 9
0.3
0.8 0.4 1.0 0.8
0.5 C*
ESDU Copyright material. For current status contact ESDU.

0.7 0.7

E
No temperature meet
E

0.6 0.6
195

0.5 Configuration Data 0.5


See Table 13.23
Index of Geometries
See Section 7.3
0.4 0.4

ESDU 98005
95% of Emax

0.3 0.3

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 87 F-SHELL, Y = 0.02, ( M p smaller ON TUBESIDE
ESDU 98005
TABLE 13.24

Shell-and-tube SAT-F-SS-2
1 F-shell

·c )
(M p smaller on shellside

Y = 0.02

Relationship between E , N TU and C∗ . (See Derivation 7.)
ESDU Copyright material. For current status contact ESDU.

2X
E = ----------------------------- ,
X
1 + X + -------
C∗
exp ( ZN TU ) – 1
where X = -------------------------------------------------- ,
Z [ exp ( ZN TU ) + 1 ]

1 2
--------- +  1 – -------
4Y
Z =
 C∗
C∗ 2
and Y = 0.2 .

Asymptotic expression
2X′
E asymp = ------------------------------------- ,
 1 + X′ + ------ X′ 
-
 C∗
1
where X′ = --- .
Z
C∗ E asymp C∗ E asymp
0 0.981 0.6 0.957
0.1 0.979 0.7 0.947
0.2 0.976 0.8 0.932
0.3 0.973 0.9 0.909
0.4 0.969 1 0.876
0.5 0.964

196
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SAT-F-SS-2
0.9 C* 0.9
0.0
0.1 0. 6
0.2 0.7
0.3 0.8
0.8 0.4 0.8
0. 9
0.5
1. 0
C*
ESDU Copyright material. For current status contact ESDU.

0.7 0.7

E No temperature meet
E

0.6 0.6
197

0.5 Configuration Data 0.5


See Table 13.24
Index of Geometries
See Section 7.3
0.4 0.4

ESDU 98005
95% of Emax

0.3 0.3

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 88 F-SHELL, Y = 0.02, ( M p smaller ON SHELLSIDE
ESDU 98005
TABLE 13.25

Shell-and-tube SAT-F-SS-3
1 F-shell

·c )
(M p smaller on tubeside

Y = 0.04

Relationship between E , N TU and C∗ . (See Derivation 7.)
ESDU Copyright material. For current status contact ESDU.

2X
E = --------------------------------- ,
1 + X + C∗ X
exp ( ZN TU ) – 1
where X = -------------------------------------------------- ,
Z [ exp ( ZN TU ) + 1 ]

2
Z = 4C∗ 2 Y + ( 1 – C∗ )
and Y = 0.04 .

Asymptotic expression
2X′
E asymp = ------------------------------------------ ,
( 1 + X′ + C∗ X′ )
1
where X′ = --- .
Z
C∗ E asymp C∗ E asymp
0 1.000 0.6 0.968
0.1 1.000 0.7 0.948
0.2 0.998 0.8 0.919
0.3 0.995 0.9 0.880
0.4 0.990 1 0.833
0.5 0.981

198
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

C*
SAT-F-SS-3 0.0
0.9 0.1 0.6 0.9
0.2 0. 7
0.3 0. 8
0.4
0.5 0. 9
0.8 0.8
1.0
C*
ESDU Copyright material. For current status contact ESDU.

0.7 0.7
No temperature meet
E E

0.6 0.6
199

0.5 Configuration Data 0.5


See Table 13.25
Index of Geometries
See Section 7.3
0.4 0.4

ESDU 98005
95% of Emax

0.3 0.3

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 89 F-SHELL, Y = 0.04, ( M p smaller ON TUBESIDE
ESDU 98005
TABLE 13.26

Shell-and-tube SAT-F-SS-4
1 F-shell

·c )
(M p smaller on shellside

Y = 0.04

Relationship between E , N TU and C∗ . (See Derivation 7.)
ESDU Copyright material. For current status contact ESDU.

2X
E = ----------------------------- ,
X
1 + X + -------
C∗
exp ( ZN TU ) – 1
where X = -------------------------------------------------- ,
Z [ exp ( ZN TU ) + 1 ]

1 2
--------- +  1 – -------
4Y
Z =
 C∗
C∗ 2
and Y = 0.04 .

Asymptotic expression
2X′
E asymp = ------------------------------- ,
X′
1 + X′ + -------
C∗
1
where X′ = --- .
Z
C∗ E asymp C∗ E asymp
0 0.963 0.6 0.923
0.1 0.959 0.7 0.909
0.2 0.955 0.8 0.890
0.3 0.950 0.9 0.865
0.4 0.943 1 0.833
0.5 0.934

200
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

C*
SAT-F-SS-4 0.0
0.9 0.1 0.9
0.2
0.3
0.4 0.6
0.5 0 .7
0.8 0. 8 0.8
0.9
1.0
ESDU Copyright material. For current status contact ESDU.

C*
0.7 0.7

E E
No temperature meet
0.6 0.6
201

0.5 Configuration Data 0.5


See Table 13.26
Index of Geometries
See Section 7.3
0.4 0.4

ESDU 98005
95% of Emax

0.3 0.3

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU

·c )
FIGURE 90 F-SHELL, Y = 0.04, ( M p smaller ON SHELLSIDE
ESDU 98005
13.4 Single G-shells

TABLE 13.27
Shell-and-tube SAT-G-SS-1
1 G-shell
2 Tube passes
·c )
(M p smaller on tubeside



Relationship between E , N TU and C∗ . (See Derivation 5.)
ESDU Copyright material. For current status contact ESDU.

J–1
E = ---------------------------------------- ,
J + 2C∗ exp [ a ]
1
where J = -------------- { ( 1 + G + 2C∗ G ) exp [ a ] + 2C∗ D } ,
1–D
1 – exp [ – b ] N TU
G = -------------------------------- = ----------- ,
2C∗ – 1 C∗ ≠ 0.5 2 C∗ = 0.5
( 1 – exp [ – a ] )
D = ------------------------------------- ,
2C∗ + 1
( 2C∗ + 1 ) ( 2C∗ – 1 )
a = -------------------------- N TU and b = -------------------------- N TU .
4 2
Asymptotic expression
2C∗ + 1
E asymp = 1 = --------------------------------------- .

C ≤ 0.5 ∗ 2
2C + C + 1 C = 0.5 ∗ ∗
C ∗ E asymp C∗ E asymp
0 1 0.6 0.95
0.1 1 0.7 0.90
0.2 1 0.8 0.85
0.3 1 0.9 0.80
0.4 1 1 0.75
0.5 1

Algebraic coefficients
0 1 2 3 4
a 1.3499 –0.8914 0.0415
b –1.4460 7.0226 –17.7751 22.8000 –10.3501
c 100
d –0.8973 5.7701 –13.9255 12.5809 –3.6678
g 0.4679 0.6678 –0.2141

202
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SAT-G-SS-1 C*
0.0
0.9 0.1 0.9
0.2
0.3
0.4 0 .6
0.5
0.8 0.7 0.8
0.8
0. 9
ESDU Copyright material. For current status contact ESDU.

1. 0
0.7 0.7
C*

E E

0.6 0.6
203

0.5 0.5
95% of Emax
Temperature meet
0.4 0.4

ESDU 98005
Configuration Data
See Table 13.27
0.3 Index of Geometries 0.3
See Section 7.4

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU

·c )
FIGURE 91 G-SHELL WITH TWO TUBE PASSES, ( M p smaller ON TUBESIDE
ESDU 98005
TABLE 13.28
Shell-and-tube SAT-G-SS-2
1 G-shell
2 Tube passes
·
( M c p ) smaller on shellside



Relationship between E , N TU and C∗ . (See Derivation 5).
J–1
E = ---------------------------------------- ,
ESDU Copyright material. For current status contact ESDU.

JC∗ + 2 exp [ a ]
1
where J = --------------------------- { ( C∗ + GC∗ + 2G ) exp [ a ] + 2D } ,
( 1 – D )C∗
C∗ ( 1 – exp [ – b ] )
G = --------------------------------------------- = N TU ,
2 – C∗ C∗ ≠ 2 C∗ = 2
C∗ ( 1 – exp [ – a ] )
D = --------------------------------------------- ‘
2 + C∗
( 2 + C∗ ) ( 2 – C∗ )
a = ----------------------- N TU and b = ---------------------- N TU .
4 2
Asymptotic expression
2 + C∗
E asymp = ----------------------------------- .
C∗ 2 + C∗ + 2
C∗ E asymp C∗ E asymp
0 1 0.6 0.88
0.1 1 0.7 0.85
0.2 0.98 0.8 0.81
0.3 0.96 0.9 0.78
0.4 0.94 1 0.75
0.5 0.91

Algebraic coefficients
0 1 2 3 4
a 1.0295 –0.6813 0.1518
b –1.5692 10.7877 –22.5836 20.4970 –6.8786
c 100
d –0.4158 –0.3840 1.9482 –2.0668 0.7850
g 0.4694 0.6362 –0.1934

204
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

C*
SAT-G-SS-2
0.0
0.9 0.1 0.9
0.2
0.3
0.4
0.5 0. 6
0.8 0.8
0.7
0 .8
0.9
ESDU Copyright material. For current status contact ESDU.

0.7 1.0 0.7


C*
E E

0.6 0.6
205

0.5 0.5
95% of Emax
Temperature meet
0.4 0.4

ESDU 98005
Configuration Data
0.3 See Table 13.28 0.3
Index of Geometries
See Section 7.4

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 92 G-SHELL WITH TWO TUBE PASSES, ( M p smaller ON SHELLSIDE
ESDU 98005
13.5 Single J-shells

TABLE 13.29
Shell-and-tube SAT-J-SS-1
1 J-shell
1 Tube pass
·c )
(M p smaller on tubeside

>9 Baffles

ESDU Copyright material. For current status contact ESDU.

Relationship between E , N TU and C∗ . (See Derivation 6.)



– ( C + 0.5 )
2C∗ – 1  2C∗ + φ 
E = 1 –  ---------------------  -----------------------------------------------
 2C∗ + 1  – ( C∗ – 0.5 ) 
2C∗ – φ C∗ ≠ 0.5
1
1 + ---
or φ
E = 1 – ------------------------ ,
2 + log e φ ∗
C = 0.5

where φ = exp [ N TU ] .
Asymptotic expression
2
E asymp = 1.0 = --------------------- .
C∗ ≤ 0.5 ∗
2C + 1 C∗ > 0.5
C∗ E asymp C∗ E asymp
0 1 0.6 0.91
0.1 1 0.7 0.83
0.2 1 0.8 0.77
0.3 1 0.9 0.71
0.4 1 1.0 0.67
0.5 1

Algebraic coefficients
0 1 2 3 4
a 1.7619 –2.2222 0.7937
b –3.7036 11.3170 –12.5946 6.3827 –1.2436
c 10
d –0.6724 3.4658 –7.7369 7.1540 –2.3475
g 0.3715 0.7450 –0.2195

206
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SAT-J-SS-1
0.9 0.9

0.8 0.8
C*
0.0
0.1 0. 6
ESDU Copyright material. For current status contact ESDU.

0.2
0.7 0.3 0.7 0.7
0.4 0. 8
0.5
E 0.9 E
1.0
0.6 0.6
C*
207

0.5 0.5
95% of Emax
Temperature meet
0.4 0.4

ESDU 98005
Configuration Data
See Table 13.29
0.3 Index of Geometries 0.3
See Section 7.5

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 93 J-SHELL WITH ONE TUBE PASS, MORE THAN NINE BAFFLES, ( M p smaller ON TUBESIDE
ESDU 98005
TABLE 13.30

Shell-and-tube SAT-J-SS-2
1 J-shell
1 Tube pass
·c )
(M p smaller on shellside

>9 Baffles

Relationship between E , N TU and C∗ . (See Derivation 6.)
ESDU Copyright material. For current status contact ESDU.

1/C ∗ – 0.5
 2 – C∗  2φ + C∗ φ  1
E =  1 –  -----------------  --------------------------------------------  ------∗- ,
 2 + C∗  1/C∗
 – C∗ φ  C
0.5

where φ = exp [ N TU C∗ ] .
Asymptotic expression
2
E asymp = ----------------- .
2 + C∗
C∗ E asymp C∗ E asymp
0 1 0.6 0.77
0.1 0.95 0.7 0.74
0.2 0.91 0.8 0.71
0.3 0.87 0.9 0.69
0.4 0.83 1 0.67
0.5 0.80

Algebraic coefficients
0 1 2 3 4
a 0.4928 –0.2109 0.0514
b 0.2410 –0.1000 0 0 0
c 10
d –0.4710 1.0990 –2.9390 3.7500 –1.5660
g 0.3765 0.7149 –0.2045

208
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SAT-J-SS-2
0.9 0.9

0.8 C* 0.8
0.0
0.1
0.2
0.3
ESDU Copyright material. For current status contact ESDU.

0.7 0.4 0 .6 0.7


0.5
0.7
E 0.8
E
0. 9
0.6 1.0 0.6
*
C
209

0.5 0.5
95% of Emax
Temperature meet
0.4 0.4

ESDU 98005
Configuration Data
0.3 See Table 13.30 0.3
Index of Geometries
See Section 7.5

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU

·c )
FIGURE 94 J-SHELL WITH ONE TUBE PASS, MORE THAN NINE BAFFLES, ( M p smaller ON SHELLSIDE
ESDU 98005
TABLE 13.31
Shell-and-tube SAT-J-SS-3
1 J-shell
2 Tube passes
·
( M c p ) smaller on tubeside

>9 Baffles
*
Counter-current
Relationship between E , N TU and C∗ . (See Derivation 6.)
2
E = --------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- ,
 C∗ ( 1 + λ )/2 
ESDU Copyright material. For current status contact ESDU.

 φ 
-----------------------------
 C∗ λ C∗ λ C∗ ( λ – 1 )/2 
 φ + 1 φ –1 λφ 
1 + 2C∗  1 + λ  ----------------------- – 2λ -------------------------------------------- 1 + --------------------------------- 
∗λ ∗λ ∗λ
 φ C
– 1 φ C
+ 1 φ
C
–1 
 1 + λ  ----------------------- 
  φ C∗ λ – 1 
 

1 + 4C∗ 2
where φ = exp [ N TU ] and λ = ------------------------ .
2C∗
Asymptotic expression
2 Since the curves pass through a maximum before
E asymp = ---------------------------------------------------------- reaching the asymptotic value, the following data
1 + 2C∗ + 1 + 4C∗ 2 are provided to assist their use.
C∗ E max NTU for E max E asymp

0 1 ∞ 1
0.1 0.934 5.20 0.901
0.2 0.878 4.56 0.807
0.3 0.827 4.17 0.723
0.4 0.779 3.89 0.649
0.5 0.735 3.67 0.586
0.6 0.695 3.48 0.532
0.7 0.658 3.31 0.485
0.8 0.624 3.16 0.446
0.9 0.593 3.02 0.412
1 0.564 2.90 0.382

Algebraic coefficients
0 1 2 3 4
a 0.3274 –0.2852 0.0857
b 0.7552 8.2817 –32.7394 40.5133 –16.5337
c 100
d –0.1180 –2.6577 4.8881 –2.9625 0.4531
g 0.3414 0.7081 –0.1859

*
A counter-current configuration is defined as one where the tubeside inlet is located adjacent to a shellside outlet port.

210
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SAT-J-SS-3

0.9 0.9

C*
0.8 0.8
0.0
0.1
0.2
ESDU Copyright material. For current status contact ESDU.

0.3
0.7 0.4 0.6 0.7
0.5
0.7
E E
0.8
0.6 0.9 0.6
1.0
C*
211

0.5 0.5
95% of Emax
Temperature meet
0.4 0.4
Configuration Data

ESDU 98005
See Table 13.31
Index of Geometries
0.3 See Section 7.5 0.3

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 95 J-SHELL WITH TWO TUBE PASSES, MORE THAN NINE BAFFLES, COUNTER-CURRENT, ( M p smaller ON TUBESIDE
ESDU 98005
TABLE 13.32
Shell-and-tube SAT-J-SS-4
1 J-shell
2 Tube passes
·
( M c p ) smaller on shellside

>9 Baffles
*Counter-current

Relationship between E , N TU and C∗ . (See Derivation 6.)


2
E = ------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------ ,
 ( 1 + λ )/2C∗ 
ESDU Copyright material. For current status contact ESDU.

 φ 
-----------------------------
 C∗ λ λC∗ ( λ – 1 )/ ( 2C∗ ) 
 φ + 1 φ –1 λφ 
C∗ + 2  1 + λ  ----------------------- – 2λ ---------------------------------------------- 1 + -------------------------------------- 
∗λ λ/C ∗ λ/C ∗
 φ C
– 1 φ + 1 φ –1 
 1 + λ  ------------------------- 

  φ λ/C – 1 
 

C∗ 2 + 4
where -------------------- and φ = exp [ N TU C∗ ] .
λ =
2
Asymptotic expression

2 Since the curves pass through a maximum before


E asymp = --------------------------------------------------- reaching the asymptotic value, the following data
C∗ + 2 + C∗ 2 + 4 are provided to assist their use.
C∗ E max NTU for E max E asymp
0 1 ∞ 1
0.1 0.947 7.40 0.488
0.2 0.893 6.00 0.475
0.3 0.842 5.19 0.463
0.4 0.791 4.62 0.450
0.5 0.745 4.19 0.438
0.6 0.702 3.83 0.427
0.7 0.663 3.54 0.415
0.8 0.627 3.30 0.404
0.9 0.594 3.09 0.393
1 0.569 2.90 0.382
Algebraic coefficients
0 1 2 3 4
a 0.4382 –0.5049 0.1945
b –0.5931 12.8107 –36.3825 38.6704 –14.2325
c 100
d –0.0215 –2.5991 4.4663 –2.6159 0.4093
g 0.3296 0.7334 –0.2036

*
A counter-current configuration is defined as one where the tubeside inlet is located adjacent to a shellside outlet port.

212
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SAT-J-SS-4

0.9 0.9

C*
0.8 0.0 0.8
0.1
0.2
0.3
ESDU Copyright material. For current status contact ESDU.

0.4
0.7 0.5 0.6 0.7
0.7
E 0.8 E

0.6 0.9 0.6


1.0
C*
213

0.5 0.5
95% of Emax
Temperature meet
0.4 0.4

Configuration Data

ESDU 98005
See Table 13.32
0.3 Index of Geometries 0.3
See Section 7.5

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU

·c )
FIGURE 96 J-SHELL WITH TWO TUBE PASSES, MORE THAN NINE BAFFLES, COUNTER-CURRENT, ( M p smaller ON SHELLSIDE
ESDU 98005
TABLE 13.33
Shell-and-tube SAT-J-SS-5
1 J-shell
>2 Tube passes
·c )
(M p smaller in either stream

>9 Baffles
*Counter-current

Relationship between E , N TU and C∗ . (See Derivation 6.)


ESDU Copyright material. For current status contact ESDU.

1
E = ----------------------------------------------------------------------- ,

 C∗ φ C φ 1 
 --------------------- + ------------- – -------------
 φC∗ – 1 φ – 1 log e φ
where φ = exp [ N TU ] .
Asymptotic expression
1 Since the curves pass through a maximum before
E asymp = -----------------
1 + C∗ reaching the asymptotic value, the following data
are provided to assist their use.
C∗ E asymp E max N TU for E max
0 1 1 ∞
0.1 0.91 0.946 7.12
0.2 0.83 0.891 5.78
0.3 0.77 0.838 5.02
0.4 0.71 0.789 4.50
0.5 0.67 0.742 4.10
0.6 0.63 0.700 3.79
0.7 0.59 0.662 3.54
0.8 0.56 0.626 3.32
0.9 0.53 0.594 3.14
1 0.50 0.565 2.98

Algebraic coefficients
0 1 2 3 4
a 0.4219 –0.4810 0.1880
b 1.3350 –1.6590 –0.8430 2.1900 –0.7320
c 100
d 0.0000 –4.1440 11.6760 –12.5030 4.6080
g 0.3514 0.7089 –0.1937

*
A counter-current configuration is defined as one where the tubeside inlet is located adjacent to a shellside outlet port.

214
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SAT-J-SS-5
0.9 0.9

0.8 C* 0.8
0.0
0.1
0.2
ESDU Copyright material. For current status contact ESDU.

0.3
0.7 0.4 0.6 0.7
0.5
0.7
E E
0.8
0.6 0.9 0.6
1.0
C*
215

0.5 0.5
95% of Emax
Temperature meet
0.4 0.4

ESDU 98005
Configuration Data
0.3 See Table 13.33 0.3
Index of Geometries
See Section 7.5

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 97 J-SHELL WITH MORE THAN TWO TUBE PASSES, MORE THAN NINE BAFFLES, COUNTER-CURRENT, ( M p smaller IN EITHER
STREAM
ESDU 98005
TABLE 13.34

Shell-and-tube SAT-J-SS-6
1 J-shell
>2 Tube passes
·c )
(M Note:
p smaller on tubeside
– The number of baffles is the
total number, including the
5 Baffles central dividing baffle.

*
Counter-current
Relationship between E , N TU and C∗
ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5. See Derivation 9.

Asymptotic expression

E asymp = 1

Algebraic coefficients
0 1 2 3 4
a 1 0 0
b –7.2600 30.4520 –57.9666 51.3914 –17.2228
c 0.8000
d –0.1769 0.3590 –0.3471 0.2071 –0.0709
g 0.1334 0.8950 –0.2337

*
A counter-current configuration is defined as one where the tubeside inlet is located adjacent to a shellside outlet port.

216
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SAT-J-SS-6
0.9 C* 0.9
0.0
0.1
0.2
0.3
0.8 0.4 0.8
0.5
0.6
ESDU Copyright material. For current status contact ESDU.

0.7
0.7 0.7
0.8

E 0.9
E
1.0
0.6 0.6
C*
217

0.5 0.5
95% of Emax
Temperature meet
0.4 0.4

ESDU 98005
Configuration Data
0.3 See Table 13.34 0.3
Index of Geometries
See Section 7.5

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 98 J-SHELL WITH TWO TUBE PASSES, FIVE BAFFLES, COUNTER-CURRENT, ( M p smaller ON TUBE SIDE
ESDU 98005
TABLE 13.35

Shell-and-tube SAT-J-SS-7
1 J-shell
2 Tube passes
·c )
(M Note:
p smaller on shellside
The number of baffles is the

total number, including the
5 Baffles central dividing baffle.

*
Counter-current
Relationship between E , N TU and C∗
ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5. See Derivation 9.

Asymptotic expression

C∗ E max E asymp
0 1 1 Inspection of Figure 99 shows that
0.1 0.944 1 two maxima are present in the curves
0.2 0.894 1 for C∗ < 0.4 . Values of the first
0.3 0.846 1 maximum are given in this table and
0.4 0.802 1 are used to identify the design limit
0.5 0.762 1 (95% line). This line is extended
0.6 – 1 beyond C∗ = 0.5 to follow the trends
0.7 – 1 shown in other figures for similar
0.8 – 1 geometries.
0.9 – 1
1 – 1

Algebraic coefficients
0 1 2 3 4
a 1 0 0
b –5.6365 24.0150 –48.4541 45.2191 –15.7535
c 0.8000
d –0.0040 0.0847 –0.4039 0.5008 –0.2064
g 0.0757 1.0606 –0.3143

*
A counter-current configuration is defined as one where the tubeside inlet is located adjacent to a shellside outlet port.

218
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SAT-J-SS-7
0.9 C* 0.9
0.0
0.1
0.2
0.3
0.8 0.4 0.8
0.5
ESDU Copyright material. For current status contact ESDU.

0.6
0.7 0.7 0.7

0.8
E E
0.9
0.6 1.0 0.6
*
C
219

0.5 0.5
95% of Emax
Temperature meet
0.4 0.4

ESDU 98005
Configuration Data
0.3 See Table 13.35 0.3
Index of Geometries
See Section 7.5

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 99 J-SHELL WITH TWO TUBE PASSES, FIVE BAFFLES, COUNTER-CURRENT, ( M p smaller ON SHELLSIDE
ESDU 98005
TABLE 13.36

Shell-and-tube SAT-J-SS-8
1 J-shell
2 Tube passes
·c ) Note:
(M p smaller on tubeside
The number of baffles is the
– total number, including the
central dividing baffle.
5 Baffles
*
Co-current
Relationship between E , N TU and C∗
ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5. See Derivation 9.

Asymptotic expression
Since the curves pass through a maximum before reaching the asymptotic value, the following data
are provided to assist their use.
C∗ E max E for N TU = 100 E asymp
0 1 1 1
0.1 0.930 0.663 0
0.2 0.871 0.547 0
0.3 0.817 0.477 0
0.4 0.767 0.426 0
0.5 0.722 0.384 0
0.6 0.681 0.346 0
0.7 0.643 0.313 0
0.8 0.609 0.285 0
0.9 0.577 0.255 0
1 0.548 0.230 0

Algebraic coefficients
0 1 2 3 4
a 0.2856 –0.2888 0.0996
b 3.8346 –17.1344 36.2090 –36.1580 13.4848
c 100
d –0.9300 4.2065 –13.8229 17.8035 –7.6141
g 0.3483 0.7011 –0.1953

*
A co-current configuration is defined as one where the tubeside outlet is located adjacent to a shellside outlet port.

220
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SAT-J-SS-8
0.9 0.9

0.8 0.8
C*
0.0
ESDU Copyright material. For current status contact ESDU.

0.1
0.2
0.7 0.6 0.7
0.3
0.4
0.5 0.7
E E
0.8
0.6 0.6
0.9
1.0
221

C*
0.5 0.5
95% of Emax
Temperature meet
0.4 0.4

ESDU 98005
Configuration Data
See Table 13.36
0.3 0.3
Index of Geometries
See Section 7.5

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 100 J-SHELL WITH TWO TUBE PASSES, FIVE BAFFLES, CO-CURRENT, ( M p smaller ON TUBESIDE
ESDU 98005
TABLE 13.37

Shell-and-tube SAT-J-SS-9
1 J-shell
2 Tube passes
·c )
(M Note:
p smaller on shellside
– The number of baffles is the
total number, including the
5 Baffles central dividing baffle.

*
Co-current
Relationship between E , N TU and C∗
ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5. See Derivation 9.

Asymptotic expression
Since the curves pass through a maximum before reaching the asymptotic value, the following data
are provided to assist their use.
C∗ E max E for N TU = 100 E asymp
0 1 1 1
0.1 0.926 0.562 0
0.2 0.866 0.413 0
0.3 0.813 0.327 0
0.4 0.763 0.268 0
0.5 0.719 0.245 0
0.6 0.679 0.239 0
0.7 0.642 0.236 0
0.8 0.608 0.234 0
0.9 0.576 0.232 0
1 0.548 0.230 0

Algebraic coefficients
0 1 2 3 4
a 0.2426 –0.1965 0.0503
b 2.9366 –5.8863 0.0986 7.1620 –4.0709
c 100
d –0.0350 –4.1062 10.3546 –9.8958 3.3154
g 0.3386 0.7495 –0.2171

*
A co-current configuration is defined as one where the tubeside outlet is located adjacent to a shellside outlet port.

222
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SAT-J-SS-9
0.9 0.9

0.8 C* 0.8
0.0
0.1
0.2
ESDU Copyright material. For current status contact ESDU.

0.3
0.7 0.4 0.7
0.5 0.6
E 0.7 E
0.8
0.6 0.6
0.9
1.0
C*
223

0.5 0.5
95% of Emax
Temperature meet
0.4 0.4

ESDU 98005
Configuration Data
See Table 13.37
0.3 Index of Geometries 0.3
See Section 7.5

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 101 J-SHELL WITH TWO TUBE PASSES, FIVE BAFFLES, CO-CURRENT, ( M p smaller ON SHELLSIDE
ESDU 98005
TABLE 13.38

Shell-and-tube SAT-J-SS-10
1 J-shell
2 Tube passes
·c )
(M Note:
p smaller on tubeside
– The number of baffles is the
total number, including the
9 Baffles central dividing baffle.

*
Counter-current
Relationship between E , N TU and C∗
ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5. See Derivation 9.

Asymptotic expression

E asymp = 1 .

Algebraic coefficients
0 1 2 3 4
a 1 0 0
b –5.7597 23.1082 –43.0118 37.2147 –12.1385
c 1
d –0.0811 0.2146 –0.2480 0.1532 –0.0415
g 0.2696 0.7619 –0.2008

*
A counter-current configuration is defined as one where the tubeside inlet is located adjacent to a shellside outlet port.

224
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SAT-J-SS-10
0.9 0.9

0.8 C* 0.8
0.0
0.1
0.2
ESDU Copyright material. For current status contact ESDU.

0.3 0.6
0.7 0.4 0.7
0.5 0.7

E 0.8 E
0.9
0.6 0.6
1.0
C*
225

0.5 0.5
95% of Emax
Temperature meet
0.4 0.4

ESDU 98005
Configuration Data
See Table 13.38
0.3 Index of Geometries 0.3
See Section 7.5

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU

·c )
FIGURE 102 J-SHELL WITH TWO TUBE PASSES, NINE BAFFLES, COUNTER-CURRENT, ( M p smaller ON TUBESIDE
ESDU 98005
TABLE 13.39

Shell-and-tube SAT-J-SS-11
1 J-shell
2 Tube passes
·c )
(M Note:
p smaller on shellside
– The number of baffles is the
total number, including the
9 Baffles central dividing baffle.

*
Counter-current
Relationship between E , N TU and C∗
ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5. See Derivation 9.

Asymptotic expression
Since the curves pass through a maximum before reaching the asymptotic value, the following data
are provided to assist their use.
C∗ E max E asymp
0 1 1
0.1 0.936 1
0.2 0.882 1
0.3 0.832 1
0.4 0.786 1
0.5 0.743 1
0.6 0.704 1
0.7 0.666 1
0.8 0.629 1
0.9 0.602 1
1 0.574 1

Algebraic coefficients
0 1 2 3 4
a 1 0 0
b –4.7636 18.1544 –34.2670 30.2670 –10.0774
c 0.8000
d 0.0570 –0.1942 0.2919 –0.2440 0.0772
g 0.2473 0.8524 –0.2517

*
A counter-current configuration is defined as one where the tubeside inlet is located adjacent to a shellside outlet port.

226
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SAT-J-SS-11

0.9 0.9

0.8 0.8
*
C
0.0
ESDU Copyright material. For current status contact ESDU.

0.1 0.6
0.7 0.2 0.7
0.3 0.7
0.4
E 0.5 0.8 E
0.9
0.6 0.6
1.0
C*
227

0.5 0.5
95% of Emax
Temperature meet
0.4 0.4

ESDU 98005
Configuration Data
See Table 13.39
0.3 0.3
Index of Geometries
See Section 7.5

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 103 J-SHELL WITH TWO TUBE PASSES, NINE BAFFLES, COUNTER-CURRENT, ( M p smaller ON SHELLSIDE
ESDU 98005
TABLE 13.40

Shell-and-tube SAT-J-SS-12
1 J-shell
2 Tube passes
·c )
(M Note:
p smaller on tubeside
– The number of baffles is the
total number, including the
9 Baffles central dividing baffle.

*
Co-current
Relationship between E , N TU and C∗
ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5. See Derivation 9.

Asymptotic expression
Since the curves pass through a maximum before reaching the asymptotic value, the following data
are provided to assist their use.
C∗ E max E for N TU = 100 E asymp
0 1 1 1
0.1 0.939 0.778 0
0.2 0.883 0.682 0
0.3 0.830 0.612 0
0.4 0.781 0.546 0
0.5 0.735 0.487 0
0.6 0.693 0.433 0
0.7 0.655 0.384 0
0.8 0.619 0.342 0
0.9 0.587 0.305 0
1 0.558 0.273 0

Algebraic coefficients
0 1 2 3 4
a 0.3636 –0.3825 0.1339
b 2.9459 –11.0033 19.7424 –18.1637 6.8777
c 100
d –0.7530 2.4087 –7.9058 11.4563 –5.7392
g 0.3642 0.6962 –0.1939

*
A co-current configuration is defined as one where the tubeside outlet is located adjacent to a shellside outlet port.

228
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SAT-J-SS-12
0.9 0.9

0.8 0.8
*
C
0.0
ESDU Copyright material. For current status contact ESDU.

0.1
0.7 0.2 0.6 0.7
0.3
0.4 0.7
E 0.5 E
0.8
0.6 0.9 0.6
1.0
C*
229

0.5 0.5
95% of Emax
Temperature meet
0.4 0.4

ESDU 98005
Configuration Data
0.3 See Table 13.40 0.3
Index of Geometries
See Section 7.5

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU

·c )
FIGURE 104 J-SHELL WITH TWO TUBE PASSES, NINE BAFFLES, CO-CURRENT, ( M p smaller ON TUBESIDE
ESDU 98005
TABLE 13.41

Shell-and-tube SAT-J-SS-13
1 J-shell
2 Tube passes
·c )
(M Note:
p smaller on shellside
– The number of baffles is the
total number, including the
9 Baffles central dividing baffle.

*
Co-current
Relationship between E , N TU and C∗
ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5. See Derivation 9.

Asymptotic expression
Since the curves pass through a maximum before reaching the asymptotic value, the following data
are provided to assist their use.
C∗ E max E for N TU = 100 E asymp
0 1 1 1
0.1 0.931 0.669 0
0.2 0.873 0.507 0
0.3 0.821 0.405 0
0.4 0.773 0.336 0
0.5 0.729 0.295 0
0.6 0.689 0.290 0
0.7 0.652 0.285 0
0.8 0.617 0.281 0
0.9 0.586 0.277 0
1 0.557 0.273 0

Algebraic coefficients
0 1 2 3 4
a 0.2996 –0.2641 0.0794
b 2.8408 –19.0238 56.4265 –67.4398 27.5023
c 100
d –0.9542 7.2201 –25.7699 32.5044 –13.4192
g 0.3494 0.7492 –0.2214

*
A co-current configuration is defined as one where the tubeside outlet is located adjacent to a shellside outlet port.

230
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SAT-J-SS-13
0.9 0.9

0.8 0.8
*
C
0.0
ESDU Copyright material. For current status contact ESDU.

0.1
0.7 0.2 0.6 0.7
0.3
0.4 0.7
E 0.5 E
0.8
0.6 0.9 0.6
1.0
C*
231

0.5 0.5
95% of Emax
Temperature meet
0.4 0.4

ESDU 98005
Configuration Data
0.3 See Table 13.41 0.3
Index of Geometries
See Section 7.5

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU

·c )
FIGURE 105 J-SHELL WITH TWO TUBE PASSES, NINE BAFFLES, CO-CURRENT, ( M p smaller ON SHELLSIDE
ESDU 98005
13.6 Multiple J-shells

TABLE 13.42
Shell-and-tube SAT-J-MS-1
2 J-shells
1 Tube pass
·c )
(M p smaller on shellside
Cross connections

Overall counter-current
Relationship between E , N TU and C∗
ESDU Copyright material. For current status contact ESDU.

2E 1 –  1 + ------- E 12 + ∆
1
 C∗
E = ------------------------------------------------------------ ,
 E 12 
C∗  1 – ------- + ∆
 C∗ 
2
( EA + EB ) ( EA – EB )
where E 1 = --------------------------- , ∆ = ----------------------------- ,
2 4

( 1 – b )  1 – ----------
1
1–a  2C∗
E A = --------------------- , E B = ------------------------------------------------------- ,
a  1 – --------- a 
- 1 + ----------
1
1 – ----------
2C∗  2C∗  2C∗

a = exp –  1 – ---------- N TU
1
b = exp –  1 + ---------- N TU .
and 1
 2C∗  2C∗
Asymptotic expression

C∗ E asymp C∗ E asymp
0 1 0.6 0.953
0.1 0.999 0.7 0.929
0.2 0.998 0.8 0.901
0.3 0.994 0.9 0.868
0.4 0.985 1 0.833
0.5 0.971

Algebraic coefficients
0 1 2 3 4
a 1.0426 –0.1453 –0.2313
b –1.6146 6.1212 –9.2907 7.2061 –2.2830
c 100
d –0.5068 2.8807 –9.6165 12.3405 –5.1693
g 0.0 0.0 0.0

232
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SAT-J-MS-1 C*
0.0
0.9 0.1 0.9
0.2
0.3 0.6
0.4 0 .7
0.5
0.8 0.8 0.8
0. 9
1.0
ESDU Copyright material. For current status contact ESDU.

C*
0.7 0.7

E E

0.6 0.6
233

0.5 0.5
No temperature meet

0.4 0.4

ESDU 98005
95% of Emax
Configuration Data
0.3 See Table 13.42 0.3
Index of Geometries
See Section 7.6

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
FIGURE 106 TWO J-SHELLS IN SERIES, ONE TUBE PASS, CROSS-CONNECTIONS BETWEEN SHELLSIDE PASSES WITH OVERALL
COUNTER-CURRENT FLOW, ( M ·c )
p smaller ON SHELLSIDE
ESDU 98005
TABLE 13.43
Shell-and-tube SAT-J-MS-2
2 J-shells
1 Tube pass
·c )
(M p smaller on tubeside
Cross connections

Overall counter-current
Relationship between E , N TU and C∗
ESDU Copyright material. For current status contact ESDU.

2E 1 – ( 1 + C∗ )E 12 + ∆
E = ----------------------------------------------------------- ,
1 – C∗ E 12 + ∆
2
( EA + EB ) ( EA – EB )
where E 1 = --------------------------- , ∆ = ----------------------------- ,
2 4
C∗
( 1 – b )  1 – -------
1–a  2
E A = --------------------- , E B = --------------------------------------------------- ,
aC∗  1 – aC ∗ C∗
1 – ---------- ----------  1 + -------
2  2  2
C∗ C∗
a = exp –  1 – ------- N TU and b = exp –  1 + ------- N TU .
 2  2
Asymptotic expression

C∗ E asymp C∗ E asymp
0 1 0.6 0.990
0.1 1 0.7 0.964
0.2 1 0.8 0.925
0.3 1 0.9 0.880
0.4 1 1 0.833
0.5 1

Algebraic coefficients
0 1 2 3 4
a 1.2578 –0.2629 –0.3289
b –1.9530 9.7594 –20.9534 20.7046 –7.4147
c 100
d –0.0165 –3.5501 15.0034 –20.8309 9.3257
g 0.0000 0.0000 0.0000

234
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SAT-J-MS-2 C*
0.0
0.9 0.1 0.9
0.2
0.3
0.4 0. 6
0.5 0. 7
0.8 0.8
0.8
0. 9
1 .0
ESDU Copyright material. For current status contact ESDU.

0.7 C* 0.7

E E

0.6 0.6
235

0.5 0.5
No temperature meet

0.4 0.4

95% of Emax

ESDU 98005
Configuration Data
0.3 See Table 13.43 0.3
Index of Geometries
See Section 7.6

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
FIGURE 107 TWO J-SHELLS IN SERIES, SINGLE TUBE PASSES ARRANGED IN SERIES WITH OVERALL COUNTER-CURRENT FLOW,
CROSS-CONNECTIONS BETWEEN SHELLSIDE PASSES, ( M ·c )
p smaller ON TUBESIDE
ESDU 98005
TABLE 13.44
Shell-and-tube SAT-J-MS-3
2 J-shells
1 Tube pass
·c )
(M p smaller on shellside
Mixed connections

Overall counter-current
Relationship between E , N TU and C∗

2E 1 –  1 + ------- E 12
1
ESDU Copyright material. For current status contact ESDU.

 C∗
E = ------------------------------------------------- ,
 E 12
C∗  1 – -------
 C∗
( EA + EB )
where E 1 = --------------------------- ,
2

( 1 – b )  1 – ----------
1
1–a  2C∗
E A = --------------------- , E B = ------------------------------------------------------- ,
a  1 – --------- a 
- 1 + ----------
1
1 – ----------
2C∗  2C∗   2C∗

a = exp –  1 – ---------- N TU b = exp –  1 + ---------- N TU .


1 1
and
 2C∗  2C∗
Asymptotic expression

C∗ E asymp C∗ E asymp
0 1 0.6 0.917
0.1 0.998 0.7 0.891
0.2 0.990 0.8 0.862
0.3 0.978 0.9 0.832
0.4 0.962 1 0.800
0.5 0.941

Algebraic coefficients
0 1 2 3 4
a 1.0371 –0.4172 –0.0198
b –1.4357 7.6971 –15.7067 15.2747 –5.6560
c 100
d –0.1034 –0.7515 2.5243 –3.7668 2.0029
g 0.0000 0.0000 0.0000

236
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SAT-J-MS-3 C*
0.0
0.9 0.1 0.9
0.2
0.3
0.4 0.6
0.5
0.8 0. 7 0.8
0.8
0. 9
ESDU Copyright material. For current status contact ESDU.

1.0
0.7 0.7
C*

E E

0.6 0.6
237

0.5 0.5
No temperature meet

0.4 0.4

ESDU 98005
95% of Emax
Configuration Data
0.3 See Table 13.44 0.3
Index of Geometries
See Section 7.6

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
FIGURE 108 TWO J-SHELLS IN SERIES, SINGLE TUBE PASSES ARRANGED IN SERIES WITH OVERALL COUNTER-CURRENT FLOW, MIXED
CONNECTIONS BETWEEN SHELLSIDE PASSES, ( M ·c )
p smaller ON SHELLSIDE
ESDU 98005
TABLE 13.45
Shell-and-tube SAT-J-MS-4
2 J-shells
1 Tube pass
·c )
(M p smaller on tubeside
Mixed connections

Overall counter-current
Relationship between E , N TU and C∗
ESDU Copyright material. For current status contact ESDU.

2E 1 – ( 1 + C∗ )E 12
E = ------------------------------------------------ ,
1 – C∗ E 12
( EA + EB )
where E 1 = --------------------------- ,
2
C∗
( 1 – b )  1 – -------
1–a  2
E A = --------------------- , E B = --------------------------------------------------- ,
aC∗  1 – aC ∗ C∗
1 – ---------- ----------  1 + -------
2  2   2
C∗ C∗
a = exp –  1 – ------- N TU and b = exp –  1 + ------- N TU .
 2  2
Asymptotic expression

C∗ E asymp C∗ E asymp
0 1 0.6 0.984
0.1 1 0.7 0.946
0.2 1 0.8 0.899
0.3 1 0.9 0.849
0.4 1 1 0.800
0.5 1

Algebraic coefficients
0 1 2 3 4
a 1.3493 –0.5393 –0.2100
b –0.9694 8.9560 –17.5339 16.1236 –5.3774
c 100
d –0.0541 –3.1882 14.0181 –19.5625 8.6688
g 0.0000 0.0000 0.0000

238
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SAT-J-MS-4 C*
0.0
0.9 0.1 0.9
0.2
0.3
0.4 0. 6
0.5
0.8 0. 7 0.8
0.8
0.9
ESDU Copyright material. For current status contact ESDU.

1. 0
0.7 0.7
C*

E E

0.6 0.6
239

0.5 0.5
No temperature meet

0.4 0.4

ESDU 98005
95% of Emax
Configuration Data
0.3 See Table 13.45 0.3
Index of Geometries
See Section 7.6

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
FIGURE 109 TWO J-SHELLS IN SERIES, SINGLE TUBE PASSES ARRANGED IN SERIES WITH OVERALL COUNTER-CURRENT FLOW, MIXED
CONNECTIONS BETWEEN SHELLSIDE PASSES, ( M·c )
p smaller ON TUBESIDE
ESDU 98005
TABLE 13.46
Shell-and-tube SAT-J-MS-5
2 J-shells
1 Tube pass
·
( M c p ) smaller on shellside
Direct connections

Overall counter-current
Relationship between E , N TU and C∗

2E 1 –  1 + ------- E 12 – ∆
1
 C∗
ESDU Copyright material. For current status contact ESDU.

E = ------------------------------------------------------------ ,
 E 12 
C∗  1 – ------- – ∆
 C∗ 
2
( EA + EB ) ( EA – EB )
where E 1 = --------------------------- , ∆ = ----------------------------- ,
2 4

( 1 – b )  1 – ----------
1
1–a  2C∗
E A = --------------------- , E B = ------------------------------------------------------- ,
a  1 – --------- a 
- 1 + ----------
1
1 – ----------
2C∗  2C∗   2C∗

a = exp –  1 – ---------- N TU b = exp –  1 + ---------- N TU .


1 1
and
 2C∗  2C∗
Asymptotic expression

C∗ E asymp C∗ E asymp
0 1 0.6 0.878
0.1 0.995 0.7 0.846
0.2 0.982 0.8 0.814
0.3 0.962 0.9 0.782
0.4 0.938 1 0.750
0.5 0.909

Algebraic coefficients
0 1 2 3 4
a 1.0406 –0.7128 0.1722
b –0.2563 –0.5874 7.1734 –10.5097 4.4359
c 100
d –0.4093 2.4336 –8.0284 9.5516 –3.6835
g 0.0000 0.0000 0.0000

240
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SAT-J-MS-5 C*
0.0
0.9 0.1 0.9
0.2
0.3
0.4
0.5 0.6
0.8 0.8
0 .7
0.8
0. 9
ESDU Copyright material. For current status contact ESDU.

0.7 1.0 0.7


C*
E E

0.6 0.6
241

0.5 0.5
No temperature meet

0.4 0.4

ESDU 98005
95% of Emax
Configuration Data
0.3 See Table 13.46 0.3
Index of Geometries
See Section 7.6

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
FIGURE 110 TWO J-SHELLS IN SERIES, SINGLE TUBE PASSES ARRANGED IN SERIES WITH OVERALL COUNTER-CURRENT FLOW, DIRECT
CONNECTIONS BETWEEN SHELLSIDE PASSES, ( M·c )
p smaller ON SHELLSIDE
ESDU 98005
TABLE 13.47
Shell-and-tube SAT-J-MS-6
2 J-Shells
1 Tube pass
·c )
(M p smaller on tubeside
Direct connections

Overall counter-current
Relationship between E , N TU and C∗

2E 1 – ( 1 + C∗ )E 12 – ∆
ESDU Copyright material. For current status contact ESDU.

E = ----------------------------------------------------------- ,
( 1 – C∗ E 12 – ∆ )
2
( EA + EB ) ( EA – EB )
where E 1 = --------------------------- , ∆ = ----------------------------- ,
2 4
C∗
( 1 – b )  1 – -------
1–a  2
E A = --------------------- , E B = --------------------------------------------------- ,
aC∗  1 – aC ∗ C∗
1 – ---------- ----------  1 + -------
2  2  2
C∗ C∗
a = exp –  1 – ------- N TU and b = exp –  1 + ------- N TU .
 2  2
Asymptotic expression

C∗ E asymp C∗ E asymp
0 1 0.6 0.948
0.1 1 0.7 0.896
0.2 1 0.8 0.844
0.3 1 0.9 0.796
0.4 1 1 0.750
0.5 1

Algebraic coefficients
0 1 2 3 4
a 1.3448 –0.8733 0.0286
b –1.3052 5.4301 –12.2264 15.2796 –6.9191
c 100
d –1.2400 9.1367 –24.8146 26.4565 –9.6886
g 0 0 0

242
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SAT-J-MS-6
0.9 C* 0.9
0.0
0.1
0.2
0.3 0. 6
0.8 0.4 0. 7 0.8
0.5
0. 8
0 .9
ESDU Copyright material. For current status contact ESDU.

0.7 1.0 0.7


*
C
E E

0.6 0.6
243

0.5 0.5
No temperature meet

0.4 0.4

95% of Emax

ESDU 98005
Configuration Data
0.3 See Table 13.47 0.3
Index of Geometries
See Section 7.6

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
FIGURE 111 TWO J-SHELLS IN SERIES, SINGLE TUBE PASSES ARRANGED IN SERIES WITH OVERALL COUNTER-CURRENT FLOW, DIRECT
CONNECTIONS BETWEEN SHELLSIDE PASSES, ( M ·c )
p smaller ON TUBESIDE
ESDU 98005
TABLE 13.48
Shell-and-tube SAT-J-MS-7
2 J-shells
2 Tube passes
·c )
(M p smaller on shellside
Mixed connections

Overall counter-current
Relationship between E , N TU and C∗

2E 1 –  1 + ------- E 12
1
 C∗
ESDU Copyright material. For current status contact ESDU.

E = ------------------------------------------------- ,
 E 12
C∗  1 – -------
 C∗
2a ( a + β )
where E 1 = -------------------------- ,
D
yN TU
sinh  --------------
 2  N TU N TU yN TU
a = ------------------------------- exp  – ----------- , β = exp – ----------- cosh  -------------- ,
γ  2  2  2 
2
β + a  1 + ---------- + 2a ( a + β – 1 ) .
1 1
y = 1 + ------------- and D =
 2C∗
4C∗ 2
Asymptotic expression
C∗ E max E for NTU = 100 E asymp
0 1 1 1
0.1 0.996 0.989 0.731
0.2 0.986 0.933 0.711
0.3 0.968 0.845 0.692
0.4 0.942 0.762 0.671
0.5 0.910 0.699 0.651
0.6 0.874 0.654 0.631
0.7 0.836 0.621 0.611
0.8 0.797 0.595 0.591
0.9 0.758 0.573 0.572
1 0.721 0.553 0.553

Algebraic coefficients
0 1 2 3 4
a 1.1127 –0.8747 0.2043
b –2.5678 15.8668 –33.6845 32.3382 –11.6110
c 100
d 0.3560 –5.5500 15.8333 –18.1250 7.3057
g –0.2946 1.3930 –0.3773

244
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SAT-J-MS-7
0.9 C* 0.9
0.0
0.1 0.6
0.2
0.3 0. 7
0.8 0.4 0.8
0.5 0.8
0. 9
ESDU Copyright material. For current status contact ESDU.

1. 0
0.7 0.7
C*

E E

0.6 0.6
245

0.5 0.5

0.4 0.4
95% of Emax
Configuration Data

ESDU 98005
Temperature meet See Table 13.48
0.3 Index of Geometries 0.3
See Section 7.6

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
FIGURE 112 TWO J-SHELLS IN SERIES, TWO TUBE PASSES ARRANGED IN SERIES WITH OVERALL COUNTER-CURRENT FLOW, MIXED
CONNECTIONS BETWEEN SHELLSIDE PASSES, ( M·c )
p smaller ON SHELLSIDE
ESDU 98005
TABLE 13.49
Shell-and-tube SAT-J-MS-8
2 J-Shells
2 Tube passes
·c )
(M p smaller on tubeside
Mixed connections

Overall counter-current
Relationship between E , N TU and C∗
2E 1 – ( 1 + C∗ )E 12 2a ( a + β )
ESDU Copyright material. For current status contact ESDU.

E = ------------------------------------------------ where E 1 = -------------------------- ,


1 – C∗ E 1 2 D

yN TU N TU yN TU
 sinh  ------------- -  β = exp – ----------- cosh  -------------- ,
  2  2  2 
a =  ------------------------------- exp ( – N TU ) ,
 γ 
 
∗ 2
C∗ 2 D = β + a 1 + C
------
- + 2a ( a + β – 1 ) .
y = 1 + --------- ,  2
4
Asymptotic expression
Since the curves pass through a maximum before reaching the asymptotic value, the following data
are provided to assist their use.
C∗ E E for NTU = 100 max
E asymp
0 1 1 1
0.1 1 0.989 0.989
0.2 0.982 0.957 0.957
0.3 0.962 0.909 0.909
0.4 0.936 0.852 0.852
0.5 0.904 0.793 0.793
0.6 0.869 0.736 0.736
0.7 0.832 0.683 0.683
0.8 0.795 0.635 0.635
0.9 0.757 0.592 0.592
1 0.721 0.553 0.553

Algebraic coefficients
0 1 2 3 4
a 1.0661 –0.7992 0.1754
b –0.9889 3.4745 1.0629 –7.9008 4.6913
c 100
d –1.2410 8.7573 –25.5218 29.7917 –11.9752
g –0.2153 1.2612 –0.3280

246
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SAT-J-MS-8
0.9 C* 0.9
0.0
0.1 0.6
0.2
0.3 0.7
0.8 0.4 0.8
0.8
0.5
0.9
ESDU Copyright material. For current status contact ESDU.

1.0
0.7 C* 0.7

E E

0.6 0.6
247

0.5 0.5

0.4 95% of Emax 0.4

Temperature meet

ESDU 98005
Configuration Data
See Table 13.49
0.3 Index of Geometries 0.3
See Section 7.6

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
FIGURE 113 TWO J-SHELLS IN SERIES, TWO TUBE PASSES ARRANGED IN SERIES WITH OVERALL COUNTER-CURRENT FLOW, MIXED
CONNECTIONS BETWEEN SHELLSIDE PASSES,( M ·c )
p smaller ON TUBESIDE
ESDU 98005
13.7 Single X-shells

TABLE 13.50

Shell-and-tube SAT-X-SS-CU
1 X-Shell
2 Tube Passes
·c )
(M p smaller in either stream
U-tube

ESDU Copyright material. For current status contact ESDU.

Overall counter-current
Relationship between E , N TU and C*

The analytical procedure used to generate the data is described in Part 5. See Derivation 9.

Asymptotic expression

E asymp = 1 .

Algebraic coefficients
0 1 2 3 4
a 1 0 0
b –2 6.7040 –9.8020 6.7710 –1.8240
c 1
d –0.1850 –1.4440 5.4740 –6.0940 2.2160
g –1.2105 2.0985 –0.4983

248
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SAT-X-SS-CU C*
0.0
0.9 0.1 0.9
0.2
0.3
0.4
0.5
0.8 0.8
0.6
0. 7
0.8
ESDU Copyright material. For current status contact ESDU.

0.7 0.9 0.7


1.0
C*
E E

0.6 0.6
249

0.5 0.5
95% of Emax
Temperature meet
0.4 0.4

ESDU 98005
Configuration Data
See Table 13.50
0.3 Index of Geometries 0.3
See Section 7.7

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·c )
FIGURE 114 X-SHELL, TWO TUBE PASSES WITH U-TUBE CONNECTIONS, OVERALL COUNTER-CURRENT, ( M p smaller IN EITHER STREAM
ESDU 98005
TABLE 13.51

Shell-and-tube SAT-X-SS-CO
1 X-shell
2 Tube passes
·c )
(M p smaller in either stream
U-tube

Overall co-current
Relationship between E , N TU and C*
ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5. See Derivation 9.

Asymptotic expression

Since the curves pass through a maximum before reaching the asymptotic value, the following data
are provided to assist their use.

C∗ E max E at N TU = 100 E asymp


0 1 1 1
0.1 0.885 0.347 0
0.2 0.807 0.249 0
0.3 0.744 0.204 0
0.4 0.692 0.177 0
0.5 0.646 0.158 0
0.6 0.606 0.145 0
0.7 0.570 0.134 0
0.8 0.539 0.125 0
0.9 0.510 0.117 0
1 0.485 0.109 0

Algebraic coefficients
0 1 2 3 4
a –0.1590 0.2744 –0.1320
b 6.8600 –30.0608 55.0096 –47.5942 16.4654
c 100
d –1.0100 –0.0300 –0.2000 –0.2000 –1.4000
g 0.3203 0.5431 –0.0141

250
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

SAT-X-SS-CO
0.9 0.9

0.8 0.8
C*
0.0
0.1
ESDU Copyright material. For current status contact ESDU.

0.2
0.7 0.7
0.3
0.4
E 0.5
E
0.6
0.6 0.6
0.7
0.8
251

0.9
0.5 1.0 0.5
95% of Emax C*
Temperature meet
0.4 0.4

ESDU 98005
Configuration Data
0.3 See Table 13.51 0.3
Index of Geometries
See Section 7.7

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU

·c )
FIGURE 115 X-SHELL, TWO TUBE PASSES WITH U-TUBE CONNECTIONS, OVERALL CO-CURRENT FLOW, ( M p smaller IN EITHER STREAM
ESDU 98005
14. DATA FOR PLATE-TYPE CONFIGURATIONS

14.1 One Pass/One Pass, Counter-current

TABLE 14.1
Plate-type PLATE-1:1-CU-1
One pass/one pass
1, 2 or ≥ 14 thermal plates
·c )
(M p smaller in either stream

-
-
ESDU Copyright material. For current status contact ESDU.

Relationship between E , N TU and C∗

The analytical procedure used to generate the data is described in Part 5.

Asymptotic expression

E asymp = 1 .

252
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

PLATE-1:1-CU-1
0.9 0.9

0. 6 . 7
0
C* 0. 8
0.8
0.0 0.9 0.8
0.1 1.0
0.2 C*
ESDU Copyright material. For current status contact ESDU.

0.3
0.4
0.7 0.7
0.5

E E

0.6 0.6
253

0.5 0.5
95% of Emax
No temperature meet

0.4 0.4

ESDU 98005
Configuration Data
See Table 14.1
0.3 Index of Geometries 0.3
See Section 8.1

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·
FIGURE 116 PLATE-TYPE, ONE PASS/ONE PASS, COUNTER-CURRENT, 1, 2 OR ≥ 14 THERMAL PLATES, ( M c p ) smaller IN EITHER STREAM
ESDU 98005
TABLE 14.2
Plate-type PLATE-1:1-CU-2
One pass/one pass
4, 6 to 13 thermal plates
·c )
(M p smaller in either stream

-
-

Relationship between E , N TU and C∗


ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5.

Asymptotic expression

E asymp = 1 .

254
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

PLATE-1:1-CU-2
0.9 0.9

C* 0.6.7
0 8
0.8
0.0 0. 9 0.8
0.
0.1
1. 0
0.2
C*
ESDU Copyright material. For current status contact ESDU.

0.3
0.4
0.7 0.7
0.5

E E

0.6 0.6
255

0.5 0.5
95% of Emax
No temperature meet

0.4 0.4

ESDU 98005
Configuration Data
0.3 See Table 14.2 0.3
Index of Geometries
See Section 8.1

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·
FIGURE 117 PLATE-TYPE, ONE PASS/ONE PASS, COUNTER-CURRENT, 4 OR 6 TO 13 THERMAL PLATES, ( M c p ) smaller IN EITHER STREAM
ESDU 98005
TABLE 14.3
Plate-type PLATE-1:1-CU-3
One pass/one pass
3 or 5 thermal plates
·c )
(M p smaller in either stream

-
-
-
Relationship between E , N TU and C∗
ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5.

Asymptotic expression

E asymp = 1 .

256
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

PLATE-1:1-CU-3
0.9 0.9

C* 0. 6 7
0.8 0. 0.8
0.0
0.1 0.8
0.2 0. 9 0
1.
0.3
ESDU Copyright material. For current status contact ESDU.

C*
0.4
0.7 0.7
0.5

E E

0.6 0.6
257

0.5 0.5
No temperature meet
95% of Emax

0.4 0.4

ESDU 98005
Configuration Data
See Table 14.3
0.3 0.3
Index of Geometries
See Section 8.1

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU

·
FIGURE 118 PLATE-TYPE, ONE PASS/ONE PASS, COUNTER-CURRENT, 3 OR 5 THERMAL PLATES, ( M c p ) smaller IN EITHER STREAM
ESDU 98005
14.2 One Pass/One Pass, Co-current

TABLE 14.4
Plate-type PLATE-1:1-CO-1
One pass/one pass
1, 2, 4, 6, 8, 10 or ≥ 12
thermal plates
·c )
(M p smaller in either stream

-
-

ESDU Copyright material. For current status contact ESDU.

Relationship between E , N TU and C∗

The analytical procedure used to generate the data is described in Part 5.

Asymptotic expression

C∗ E asymp
1 0.50
0.9 0.525
0.8 0.55
0.7 0.59
0.6 0.625
0.5 0.67
0.4 0.715
0.3 0.77
0.2 0.832
0.1 0.91
0 1

258
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

PLATE-1:1-CO-1
0.9 0.9

C*
0.8 0.8
0.0
0.1
0.2
ESDU Copyright material. For current status contact ESDU.

0.3
0.4
0.7 0.7
0.5

E E
0.6

0.6 0.7 0.6


0.8
0.9
259

1.0
0.5 0.5
C*
95% of Emax

No temperature meet
0.4 0.4

ESDU 98005
Configuration Data
See Table 14.4
0.3 Index of Geometries 0.3
See Section 8.2

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·
FIGURE 119 PLATE-TYPE, ONE PASS/ONE PASS, CO-CURRENT, 1, 2, 4, 6, 8, 10 OR ≥ 12 THERMAL PLATES, ( M c p ) smaller IN EITHER STREAM
ESDU 98005
TABLE 14.5
Plate-type PLATE-1:1-CO-2
One pass/one pass
5, 7, 9 or 11 thermal plates
·c )
(M p smaller in either stream

-
-

Relationship between E , N TU and C∗


ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5.

Asymptotic expression

C∗ E asymp
1 0.50
0.9 0.526
0.8 0.556
0.7 0.588
0.6 0.625
0.5 0.67
0.4 0.715
0.3 0.77
0.2 0.832
0.1 0.91
0 1

260
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

PLATE-1:1-CO-2
0.9 0.9

C*
0.8 0.8
0.0
0.1
0.2
ESDU Copyright material. For current status contact ESDU.

0.3
0.4
0.7 0.7
0.5

E E
0.6

0.6 0.7 0.6


0.8
0.9
261

1.0
0.5 0.5
C*
95% of Emax

No temperature meet
0.4 0.4

ESDU 98005
Configuration Data
See Table 14.5
0.3 Index of Geometries 0.3
See Section 8.2

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·
FIGURE 120 PLATE-TYPE, ONE PASS/ONE PASS, CO-CURRENT, 5, 7, 9 OR 11 THERMAL PLATES, ( M c p ) smaller IN EITHER STREAM
ESDU 98005
TABLE 14.6
Plate-type PLATE-1:1-CO-3
One pass/one pass
3 thermal plates
·c )
(M p smaller in either stream

-
-
-
Relationship between E , N TU and C∗
ESDU Copyright material. For current status contact ESDU.

The analytical procedure used to generate the data is described in Part 5.

Asymptotic expression

C∗ E asymp
1 0.47
0.9 0.54
0.8 0.57
0.7 0.60
0.6 0.63
0.5 0.67
0.4 0.71
0.3 0.76
0.2 0.82
0.1 0.90
0 1

262
NTU
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
1.0 1.0

PLATE-1:1-CO-3
0.9 0.9

C*
0.8 0.8
0.0
0.1
0.2
ESDU Copyright material. For current status contact ESDU.

0.3
0.4
0.7 0.7
0.5

E E
0.6
0.6 0.7 0.6

0.8
0.9
263

0.5 1.0 0.5


*
95% of Emax C

No temperature meet
0.4 0.4

ESDU 98005
Configuration Data
See Table 14.6
0.3 0.3
Index of Geometries
See Section 8.2

0.2 0.2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10
NTU
·
FIGURE 121 PLATE-TYPE, ONE PASS/ONE PASS, CO-CURRENT, 3 THERMAL PLATES, ( M c p ) smaller IN EITHER STREAM
ESDU 98005
KEEPING UP TO DATE

Whenever Items are revised, subscribers to the service automatically receive the material required to update
the appropriate Volumes. If you are in any doubt as to whether or not your ESDU holding is up to date, please
contact us.

Please address all technical engineering enquiries and suggestions to:

ESDU International plc Tel: 020 7490 5151 (from the UK)
+44 20 7490 5151 (from outside the UK)
Fax: 020 7490 2701 (from the UK)
+44 20 7490 2701 (from outside the UK)
E-Mail: esdu@ihs.com
Website: www.ihsesdu.com
ESDU Copyright material. For current status contact ESDU.

For users in the USA, please address all Customer Service and Support enquiries and suggestions to:

IHS Engineering Products Tel: 1 800 447 3352 (toll free number)
and Fax: 1 303 397 2599
Global Engineering Documents Website: www.ihs.com
global.ihs.com
ESDU 98005
The evaluation of vapour-pressure data
ESDU 98005

ISBN 978 1 86246 042 3, ISSN 0141-402X

Available as part of the ESDU Series on Heat Transfer. For information


on all ESDU validated engineering data contact ESDU International plc,
27 Corsham Street, London N1 6UA.

ESDU 98005 provides graphical and tabular effectiveness - NTU data for
a wide range of practical heat exchanger configurations. The data are
presented in "family groups" based on exchanger types, and for each
family group there is an Index of Geometries, within which each particular
configuration (which may cover a range of practical heat exchangers) is
identified by a concise description and a unique acronym.

A data sheet is given for each configuration including graphical


ESDU Copyright material. For current status contact ESDU.

information and a detailed description. The description includes where


available the mathematical relationship between E, NTU and C* (the
stream thermal capacity ratio) and its source, notes on the derivation of
the data, maximum and asymptotic effectiveness data and expressions,
a curve for the temperature meet, and the coefficients of an algebraic
expression for effectiveness that has been fitted to the data for most
configurations. Data are provided for a wide range of single- and
multi-pass crossflow configurations (including serpentine), single- and
multi-pass E- and J-shells, trains of E- and J-shells, single F-, G- and
X-shells, and single- and multi-pass plate-type configurations.

ESDU 98003 describes the method and introduces the data presented
here and in ESDU 98004 where the data are in a convenient form for
selection purposes. The use of the method is illustrated in design studies
in ESDU 98006. Analytical techniques used to derive the data are
described in ESDU 98007.

© ESDU International plc, 2007

All rights are reserved. No part of any Data Item may be reprinted, reproduced, or
transmitted in any form or by any means, optical, electronic or mechanical including
photocopying, recording or by any information storage and retrieval system without
permission from ESDU International plc in writing. Save for such permission all
copyright and other intellectual property rights belong to ESDU International plc.