ANNEX A~ KEY DATA FOR INSULATION SYSTEMS.
[fusulation insulation Jacket [Other Comments 7
lclass (Materials Material Build-up
Jctass 1 (Cellular glass, [Non-metallic weather
Heat ‘Mineral wool at temp. \proofing membrane.
[Conservation higher then 420°C _[or Stainless Steel / Al
Jctass 2 (Cellular glass "Non-metallic weathes~ | Vapour barrier
[Cold Service [proofing membrane,
Hinsulation lor Stainless Steel / Al
Jctass 3 Either linaccordance with [Perforated guards to be of
[Personnel (Class 1-9 lclasses 1-9 as stainless steel.
Protection lor applicable If insulation is used, it shall be
Perforated sheet metal designed so that the jacket
ards itenaperature do not exceed 70°C.
[Glass 4, (Celfular elas 'Non-metallic weather | Vapour barrier
[Frost Proofing [ptoofing membrane.,
lor Stainless Steel / Al
[Glass 5, (Cellular elass + Stainless steel Iinsilation materials are dependani
JFire proofing (Ceramic fibre [on protection requirements, and
lor Imust be accepted in writing by
Inxineral wool client for each case
when necessary
ass 6 (Cellular glass \Non-metallic weather- [30mm Cellular glass ~ 25mm
Acoustic (Ceramic fibre or proofing membrane., | fibres” + metallic jacketing (or
insulation ~ 10dB|Mineral wool lor Stainless Steel / Al aluminium foil + non-metallic
Heavy synthetic shoet jacketing)
ass 7, (Cellular glass \Nou-metallic weaihes- [30mm Cellular glass + 38mm
Acoustic (Ceramic fibre or proofing membrane., fibres” + heavy synthetic sheets
insulation ~ 20d8|Mineral wool lor Stainless Stoel /Al_ |+ metallic jacketing (or
Heavy synthetic sheet altuninium foil + non-metallic
jacketing)
[class 8, (Cellular alas \Nou-metallic weather [30mm Cellular glass + 38mm
Acoustic (Ceramic fibre or proofing membrane., |Mfibres” ,~2 x heavy synthetic
finsulation ~30dB [Mineral wool (or Stainless Steel /Al_|sheets ~ 25mm fibres +2 x
Heavy synthetic sheet Iheavy synthetic sheets + metallic
jacketing (or aluminium foil +
non-metallic jacketing)
[class 9, (Cellular glass [Non-metallic weather | Vapour barrier
JExtemal [proofing membrane,
[Condensation lor Stainless Steel /AL
These key data are not applicable for pre insulated pipe systems.