1 General Description
2.1 Loads
The 14 Bus System consists of 14 buses
(nodes), 5 generators, 11 loads, 16 lines, 5 The loads are not voltage-dependent, but
transformers and one shunt. 3 of these 5 have constant active and reactive power de-
transformers are used to represent one sin- mand. Please note that this is achieved by
gle 3-winding transformer. Figure 1 shows disabling the load option “Consider Voltage
the single line diagram. It is a simplified Dependency of Loads” in the PowerFactory
model of the transmission system in the Mid- load flow calculation command. Load data
west United States. (active power P and reactive power Q) have
been taken from [1] and are listed in Table 1.
2 Model Parameters
2.2 Generators
Data have been taken from [1] and have
been completed by assuming the following
typical values as nominal voltages: Generator “Gen 0001” is the slack genera-
tor, therefore voltage magnitude and voltage
angle are given (1.060 p.u., 0.0 degrees).
• Bus 1 - Bus 5: 132 kV
The other generators are configured to con-
trol the active power injection and voltage
• Bus 6, Bus 9 - Bus 14: 33 kV
magnitudes at the connected buses. There-
fore the active power dispatch and controlled
• Bus 7: 1 kV
voltage magnitudes at their terminals are
given. The data have been taken from [1]
• Bus 8: 11 kV
and are listed in Table 2 and 3. The ma-
∗ DIgSILENT GmbH, Heinrich-Hertz-Str. 9, 72810 chines at the buses 3, 6 and 8 are syn-
Gomaringen, Germany, www.digsilent.de chronous condensers.
DIgSILENT
Load_0013
Load_0014
Bus_0013
Load_0012
Li
TypLne_001
3 3 ne 00 3_00
01 01 13 14
to 00
_0 0
12 to 14
00 12 Bus_0014
e_ 00 Load_0011
Bus_0012 Lin Lne
p
Ty
Line_0006_0013
TypL e_00
ne 00 09_0
09 to 014
0014
Bus_0011
TypLine_
Ln 00
e 0 06_ Shnt_0009
00 00
6 to 12
00 Bus_0010
Load_0009
12 11 Line_001
Gen_0001 6_00 0011 TypLne 0_00
TypSym_0001 _000 06 to 0010 to 11
Linene 00 0011 Line_000
~ TypL TypLne 9_00
0009 to 10
SG 0010
Bus_0008
Load_0006
Bus_0009
Trf_0007_0009
Bus_0001 Bus_0006
TypSym_0006
TypSym_0008
Gen_0006
Gen_0008
SG
SG
~
~
TypTr2 0005 to 0006
Trf_0004_0009
Bus_0007
Load_0005
Load_0004
_0005 004
Line_0002 to 0005 Line_0002_0
to 0004
TypLne
0002 TypLne 0002
SG
~
Line
Gen_0002 TypLne_0002_0003
TypSym_0002 0002 to
0003
Bus_0003
Load_0003
SG
~
Gen_0003
TypSym_0003
Inactive
Out of Calculation
De-energized
Voltage Levels
132, kV 14 Bus System Project:
33, kV DIgSILENT
01 - Load Flow Case Original Grid Graphic: 14 Bus System
11, kV GmbH
1, kV Date: 5/23/2014
PowerFactory 15.1.4 Annex:
Un2 [kV2 ]
R [Ω] = r [p.u.] · (1)
Line data are given in per unit (p.u.) based Sb [MVA]
on the base power Sb = 100 MVA as repre- U 2 [kV2 ]
sented in Table 5, without information about X [Ω] = x [p.u.] · n (2)
Sb [MVA]
the line length [1]. The susceptance b in p.u.
Qc [Mvar] = 2 · qc/2 [p.u.] · Sb [MVA](3)
is twice the given line charging qc/2 in p.u.,
Qc [Mvar]
which is given as one-half of the total charg- B [µS] = · 10−6 (4)
ing of lines [1] (Eq. (3)). 2
Un [kV ] 2
S [MVA]
For the PowerFactory model input data are = b [p.u.] · b · 10−6
required in Ω/km and µS/km (or µF/km) re- Un2 [kV2 ]
spectively. Line data have been recalculated
for the network model with a nominal voltage
Un given in Table 4 using Equations (1) – (4). 2.2.2 Transformers
As there is no line length given in [1], the
length of each line in the PowerFactory Transformer data are given in per unit (p.u.)
model has been set to 1 km. Line data of as represented in Table 6 based on the base
the PowerFactory model are represented in power Sb = 100 MVA [1]. The rated power
Table 4. The rated current of each line is not of each transformer is assumed as Sr =
known and therefore assumed to be 1 kA. 100 MVA.
The line between bus 1 and bus 2 is a double Transformer parameters of the PowerFactory
circuit, and has therefore been modelled as model are given in Table 6. In addition tap
two parallel lines with adapted parameters in changers are modelled in order to achieve
the PowerFactory model. the transformer taps as given in Table 6.
References
uk,LV−HV =
(7)
[1] L. L. Freris, A. M. Sasson: “Investiga-
uk,LV · Sr,LV + uk,HV · Sr,HV
tion of the load-flow problem”, PROC.
min(Sr,LV , Sr,HV ) IEE, Vol. 115, No. 10, October 1968, pp.
1459-1470
HV
uk,HV
uk,LV uk,MV
LV MV
2.3 Shunt
DIgSILENT
1,12
1,09
1,06
1,03
1,00
0,97
01
02
03
04
05
06
07
08
09
10
11
12
13
14
00
00
00
00
00
00
00
00
00
00
00
00
00
00
s_
s_
s_
s_
s_
s_
s_
s_
s_
s_
s_
s_
s_
s_
Bu
Bu
Bu
Bu
Bu
Bu
Bu
Bu
Bu
Bu
Bu
Bu
Bu
Bu
Voltage, Magnitude in p.u.
DIgSILENT
250,00
200,00
150,00
100,00
50,00
0,00
1
8
00
00
00
00
00
_0
_0
_0
_0
_0
n
n
Ge
Ge
Ge
Ge
Ge
Active Power in MW
80,00
60,00
40,00
20,00
0,0000
-20,00
1
8
00
00
00
00
00
_0
_0
_0
_0
_0
n
n
Ge
Ge
Ge
Ge
Ge
Minimum Maximum
Generator Bus Type Voltage in p.u.
capability in MVA capability in MVA
Gen 0001 Slack 1.060 N.A. N.A.
Gen 0002 PV 1.045 -40.0 50.0
Gen 0003 PV 1.010 0.0 40.0
Gen 0006 PV 1.070 -6.0 24.0
Gen 0008 PV 1.090 -6.0 24.0
Table 6: Data of transformers given in [1] based on 100 MVA, with rated voltages added in the
PowerFactory model