Characteristics

• This unit has Accumulation function, it can minimize the false alarm that
caused by unstable pulse or any abnormal signal ( false alarm ) and no effect
on the function of fire alarm at all.
• Each zone uses two different LED to indicate Fire alarm and Disconnection.
• Zone test switch uses single-loop press type to improve the twisting switch
that its contact failure will caused by dust and improper use.
• Logical switch is different from traditional switch that needs to switch over
higher voltage directly, it can prevent the damage caused by unstable voltage.
• External indicator power-save device can select Light ON or OFF under
normal condition during power-off status, and stay blinking during alarm status
which extend the operation life of control panel. (Prevent the control panel loss
its function by wear-off on battery under power-off period)
• Easy to switch from fire alarm to smoke evacuation, sprinkling or foam system.
• Movable zone indication labels, they can be easily changed without affect its
magnificent appearance.
• Annunciator is available on model AH-02124.

1
Specification

Model AH-00212 (1~10 Zone) AH-00212 (1 Zone)


Power 220V AC/50Hz *Others also available
Voltage Scope Nominal Voltage±20%
Battery Capacity 24V DC 1.2Ah 24V DC 0.8Ah
Charging Voltage,
Current 26V DC 100~400mA *With auto adjustment function
Exterior
Round-trip under 50Ω
Resistance
# of heat detector
No limit *Except electronic-type
connected
# of smoke
detector 30/zone *Horing Lih manufactured
connected
Max. Output
1A 500mA
Current
Digital Switch 500000 Cycles Min. reliability
End of Line
10kΩ *One per zone
Resistor
Material 1.2mm steel plate
Color Ivory white *Others also available
350mm (H) x 285mm (W) x 280mm (H) x 160mm (W) x
Dimensions
105mm (D) 70mm (D)
Accessory
Dual signal transfer contacts, aux. contacts
Functions

General
These conventional panels provide a cost-effective solution to fire detection from
small to large size installations which have 4, 8 and 32 zones selecting models.

2
These units have beendesigned to offer high standards of performance, reliability
and quality to comply with EN-54, part 2 & 4.

4 Zone 8 Zone 32 Zone

Optional Features

• Output for extinguishing facility and activated only when alarm from 2 cross-
zones.
• LCD display (2x20) with simple function keypad.

Characteristics

• Input power supervisory LEDs (Normal, Low, and High).


• Auto-dialer disable function.
• Current panel capacity confirmation.
• Fully supervisory to all inputs and outputs.
• Indication for open, short circuit and head removal on detection loop.
• Ground fault and PCB Link fault detection.
• Resettable fuses that can automatically cut off power for circuit protection.
• Twin sounder circuit outputs and each rated at 1A @24VDC.
• Built-in output per zone for Repeater panels.
• Auto-monitoring for open and short circuit on batteries.
• Zones disable facility enabling simple servicing and maintenance.
• On-board key switch enable for board operation.(4 zone and 8 zone only)
• Complete with integral charger for sealed lead acid batteries.
• Lamp test feature.

3
Specification

32 Zone 8 Zone 4 Zone


Model AH-03312-32L AH-03312-8L AH-03312-4L
Power 220V AC/50Hz *Others also available
Standby Voltage 24V DC
Battery Capacity 24V/12Ah 24V/7Ah 24V/4Ah
Max. Output Current 2A @24V DC
# of heat detector
No limit *Except electronic-type
connected
# of smoke detector
30/zone *Horing Lih manufactured
connected
Max. No. of Bells
40 per sounder circuit
@25mA
End of Line Resistor 4.7kΩ *One per zone
Material 1.2mm steel plate
550mm(H) 370mm(H) 320mm(H)
Dimensions 400mm(W) 340mm(W) 250mm(W)
150mm(D) 135mm(D) 130mm(D)

Approval