DUCT SIZING
The function of a duct sizing is to transmit air from the air handling apparatus to the
space to be conditioned. To fulfill this function in physical manner, the system must be
designed with prescribe limits available space, frictional loss, sound level, heat and leakage
Operating pressure for all terminals = 0.15 in. wg (From HVAC, by McQuiston, 5th Ed, PP 437)
Initial Duct supply air Velocity = 1 700 fpm (From the Book of Carrier, PP 2-37, Table 7)
Initial Duct return air Velocity = 1 500 fpm (From the Book of Carrier, PP 2-37, Table 7)
ZONE 1
22399
CFM supply for each terminal= =457.12cfm
49
Q 22399
A= = =13.18
V 1700
Duct area = percent of area times initial duct area (fan at section 1)
The Duct sizes can then be determined by using Carrier handbook, PP 2-36, Table 6.
The Additional Equivalent Length can be determining from Carrier handbook, PP 2-44,
Table 12.
CFM Added
Duct Air Are Area Duct Lengt Length
Capacity Item Equiv.
Section Quantity a% ft Size h (m) (ft.)
% length
13.1
AHU1-A 22399.00 100.00 100 8 44 X 46 Duct Elbow 8.6 28.208 25
11.7
A-B 19199.16 85.71 89.5 9 40 X 46 Duct 4.5 14.76
10.2
B-C 15999.32 71.43 78 8 40 X 40 Duct 4.5 14.76
C-D 14627.96 65.31 72.5 9.55 38 X 40 Duct 4.5 14.76
D-E 13256.60 59.18 67.5 8.89 34 X 40 Duct 4.5 14.76
E-F 11885.24 53.06 61 8.04 34 X 36 Duct 4.5 14.76
F-36 6399.80 28.57 36.5 4.81 22 X 36 Duct Elbow 5.5 18.04 13
A-1 3199.84 14.29 20.5 2.70 22 X 20 Elbow Duct 1 3.28 11
1-2 2742.72 12.24 18.5 2.44 20 X20 Duct 4.5 14.76
2-3 2285.60 10.20 16.5 2.17 18 X 20 Duct 4.5 14.76
3-4 1828.48 8.16 13 1.71 14 X 20 Duct 4.5 14.76
4-5 1371.36 6.12 10.5 1.38 14 X 16 Duct 4.5 14.76
5-6 914.24 4.08 7 0.92 10 X 16 Duct 4.5 14.76
6-7 457.12 2.04 3.5 0.46 10 X 8 Duct 4.5 14.76
B-8 3199.84 14.29 20.5 2.70 22 X 20 Elbow Duct 1 3.28 11
8-9 2742.72 12.24 18.5 2.44 20 X20 Duct 4.5 14.76
9-10 2285.60 10.20 16.5 2.17 18 X 20 Duct 4.5 14.76
10-11 1828.48 8.16 13 1.71 14 X 20 Duct 4.5 14.76
11-12 1371.36 6.12 10.5 1.38 14 X 16 Duct 4.5 14.76
12-13 914.24 4.08 7 0.92 10 X 16 Duct 4.5 14.76
13-14 457.12 2.04 3.5 0.46 10 X 8 Duct 4.5 14.76
C-15 1371.36 6.12 10.5 1.38 14 X 16 Elbow Duct 1 3.28 9
15-16 914.24 4.08 7 0.92 10 X 16 Duct 4.5 14.76
16-17 457.12 2.04 3.5 0.46 10 X 8 Duct 4.5 14.76
D-18 1371.36 6.12 10.5 1.38 14 X 16 Elbow Duct 1 3.28 9
18-19 914.24 4.08 7 0.92 10 X 16 Duct 4.5 14.76
19-20 457.12 2.04 3.5 0.46 10 X 8 Duct 4.5 14.76
E-21 1371.36 6.12 10.5 1.38 14 X 16 Elbow Duct 1 3.28 9
21-22 914.24 4.08 7 0.92 10 X 16 Duct 4.5 14.76
22-23 457.12 2.04 3.5 0.46 10 X 8 Duct 4.5 14.76
F-24 5484.44 24.49 32.5 4.28 20 X 36 Elbow Duct 1 3.28 22
24-25 5028.32 22.45 29.5 3.89 18 X 36 Duct 4.5 14.76
25-26 4571.20 20.41 27 3.56 16 X 36 Duct 4.5 14.76
26-27 4114.08 18.37 25 3.29 14 X 34 Duct 4.5 14.76
27-28 3656.96 16.33 23 3.03 14 X 34 Duct 4.5 14.76
28-29 3199.84 14.29 20.5 2.70 22 X 20 Duct 4.5 14.76
29-30 2742.72 12.24 18.5 2.44 20 X20 Duct 4.5 14.76
30-31 2285.60 10.20 16.5 2.17 18 X 20 Duct 4.5 14.76
31-32 1828.48 8.16 13 1.71 14 X 20 Duct 4.5 14.76
32-33 1371.36 6.12 10.5 1.38 14 X 16 Duct 4.5 14.76
33-34 914.24 4.08 7 0.92 10 X 16 Duct 4.5 14.76
34-35 457.12 2.04 3.5 0.46 10 X 8 Duct 4.5 14.76
36-37 5942.56 26.53 34.5 4.55 20 X 36 Duct 4.5 14.76
37-38 5485.44 24.49 32.5 4.28 20 X 36 Duct 4.5 14.76
38-39 5028.32 22.45 30.5 4.02 18 X 36 Duct 4.5 14.76
39-40 4571.20 20.41 27 3.56 16 X 36 Duct 4.5 14.76
40-41 4114.08 18.37 25 3.29 14 X 34 Duct 4.5 14.76
41-42 3656.96 16.33 23 3.03 14 X 34 Duct 4.5 14.76
42-43 3199.84 14.29 20.5 2.70 22 X 20 Duct 4.5 14.76
43-44 2742.72 12.24 18.5 2.44 20 X20 Duct Elbow 4.5 14.76 11
44-45 2285.60 10.20 16.5 2.17 18 X 20 Duct 4.5 14.76
45-46 1828.48 8.16 13 1.71 14 X 20 Duct 4.5 14.76
46-47 1371.36 6.12 10.5 1.38 14 X 16 Duct 4.5 14.76
47-48 914.24 4.08 7 0.92 10 X 16 Duct 4.5 14.76
48-49 457.12 2.04 3.5 0.46 10 X 8 Duct 4.5 14.76
TOTAL LENGTH 759.648 120
The total friction loss in the duct work from fan to last terminal 49 is:
Loss = total equivalent length x friction rate
For the total equivalent length, it appears that the longer run is from AHU 1 to terminal
49: 312.3 + 47 = 359.3 ft.
Friction rate: using Vsupply = 1700 fpm, cfm = 22399, Fr = 0.062 (from chart 7, page 2-33
friction loss for round duct)
Loss = 359.3 ft. x (0.062 in wg /100 ft.)
Loss = 0.223 in wg
The total static pressure required at fan discharge is the sum of the terminal operating
pressure and the loss in the duct work. Credit can be taken for the regain between the
first and last section of the duct.
From chart 7, p. 2-33 of Carrier Handbook with cfm of 457.12 and equivalent circular
duct diameter = 9.8 in., velocity in the last section = 920 fpm.
Using 75% regain coefficient;
2
Regain = 0.75 [ ( 1700/4000 )−( 920/ 4000 ) ] = 0.096 in wg
Therefore, the total static pressure at fan discharge is;
= duct friction + terminal pressure – regain
= 0.223 + 0.15 – 0.096
= 0.277 in wg
21049
CFM return for eachterminal= =1503.5 cfm
14
Adde
Air CFM d
Duct Are Area Duct Lengt Length
Quantit Capacit Item Equiv.
Section a% ft. Size h (m) (ft)
y y% Lengt
h
AHU 1 - 14.0 Duct
46 x 48
1 21049 100.00 100 3 Elbow 15.25 50.02 25
94. 13.2
46 x 44
1-2 19545.5 92.86 5 6 Duct 6.46 21.1888
89. 12.5 Duct
44 x 44
2-3 18042 85.71 5 6 Elbow 10.6 34.768 24
Duct
30 x 32
3-A 7517.5 35.71 44 6.17 Elbow 4.5 14.76 16
20. Duct
16 x 28
A-10 3007 14.29 5 2.88 Elbow 4.5 14.76 10
11.
16 x 16
10-11 1503.5 7.14 5 1.61 Duct 9 29.52
A-12 4510.5 21.43 28 3.93 22 x 28 Duct 9 29.52
20.
16 x 28
12-13 3007 14.29 5 2.88 Duct 9 29.52
11.
16 x 16
13-14 1503.5 7.14 5 1.61 Duct 9 29.52
3-4 9021 42.86 51 7.16 32 x 34 Duct 9 29.52
4-5 7517.5 35.71 44 6.17 32 x 30 Duct 9 29.52
36. Duct
28 X 28
5-6 6014 28.57 5 5.12 Elbow 9 29.52 15
6-7 4510.5 21.43 28 3.93 22 x 28 Duct 9 29.52
20.
16 x 28
7-8 3007 14.29 5 2.88 Duct 9 29.52
11.
16 x 16
8-9 1503.5 7.14 5 1.61 Duct 9 29.52
430.696
TOTAL LENGTH 8 90
The total friction loss in the duct work from fan to last terminal 14 is:
Loss = total equivalent length x friction rate
For the total equivalent length, it appears that the longer run is from AHU 1 to terminal
9: 86.3 + 64 = 150.3 ft.
Friction rate: using Vsupply = 1500 fpm, cfm = 21049, Fr = 0.047 (from chart 7, page 2-33
friction loss for round duct)
Loss = 150.3 ft. x (0.047 in wg /100 ft.)
Loss = 0.0706 in wg
The total static pressure required at fan discharge is the sum of the terminal operating
pressure and the loss in the duct work. Credit can be taken for the regain between the
first and last section of the duct.
From chart 7, p. 2-33 of Carrier Handbook with cfm of 1503.5 and equivalent circular
duct diameter = 17.5 in., velocity in the last section = 920 fpm.
Using 75% regain coefficient;
2
Regain = 0.75 [ ( 1500/4000 )−( 920/ 4000 ) ] = 0.0658 in wg
Therefore, the total static pressure at fan discharge is;
= duct friction + terminal pressure – regain
= 00706 + 0.15 – 0.0658
= 0.15 in wg
ZONE 2
50136
CFM supply for each terminal= =1193.7 cfm
42
Q 50136
A= = =29.5
V 1700
Duct area = percent of area times initial duct area (fan at section 1)
The Duct sizes can then be determined by using Carrier handbook, PP 2-36, Table 6.
Table 12.
CFM Added
Duct Air Are Area Duct Length Length
Capacit Item Equiv.
Section Quantity a% ft Size (m) (ft)
y% length
29.5
AHU2-A 50136.00 100.00 100 0 64 x 72 Duct Elbow 10.75 35.26 34.67
29.5
A-B 50136.00 100.00 100 0 64 x 72 Duct Elbow 10.7 35.096 34.67
25.2 Series of
B-C 40586.40 80.95 85.5 2 64 x 60 Elbow 7 22.96 33.67
20.3 Series of
C-D 31036.80 61.91 69 6 52 x 60 Elbow 4.2 13.776 28.67
15.6 Series of
D-E 22680.90 45.24 53 4 52 x 46 Elbow 4.7 15.416 26.5
10.7
E-F 14325.00 28.57 36.5 7 36 x 46 Elbow Duct 3.5 11.48 20
F-38 5969.10 11.91 18.5 5.46 30 x 28 Duct Elbow 6.6 21.648 16
B-1 9549.60 19.05 26 7.67 32 x 38 Elbow Duct 2.6 8.528 20
1-2 8355.90 16.67 24 7.08 32 x 34 Duct 4.5 14.76
2-3 7162.20 14.29 20.5 6.05 28 x 34 Duct 4.5 14.76
3-4 5968.50 11.90 18.5 5.46 28 x 30 Duct 4.5 14.76
4-5 4774.80 9.52 16.5 4.87 28 x 26 Duct 4.5 14.76
5-6 3581.10 7.14 11.5 3.39 20 x 26 Duct 4.5 14.76
6-7 2387.40 4.76 9 2.66 20 x 20 Duct 4.5 14.76
7-8 1193.70 2.38 3.5 1.03 10 x 16 Duct 4.5 14.76
C-9 9549.60 19.05 26 7.67 32 x 38 Elbow Duct 2.4 7.872 20
9-10 8355.90 16.67 24 7.08 32 x 34 Duct 4.5 14.76
10-11 7162.20 14.29 20.5 6.05 28 x 34 Duct 4.5 14.76
11-12 5968.50 11.90 18.5 5.46 28 x 30 Duct 4.5 14.76
12-13 4774.80 9.52 16.5 4.87 28 x 26 Duct 4.5 14.76
13-14 3581.10 7.14 11.5 3.39 20 x 26 Duct 4.5 14.76
14-15 2387.40 4.76 9 2.66 20 x 20 Duct 4.5 14.76
15-16 1193.70 2.38 3.5 1.03 10 x 16 Duct 4.5 14.76
D-17 8355.90 16.67 24 7.08 32 x 34 Elbow Duct 4.35 14.268 18
17-18 7162.20 14.29 20.5 6.05 28 x 34 Duct 4.5 14.76
18-19 5968.50 11.90 18.5 5.46 28 x 30 Duct 4.5 14.76
19-20 4774.80 9.52 16.5 4.87 28 x 26 Duct 4.5 14.76
20-21 3581.10 7.14 11.5 3.39 20 x 26 Duct 4.5 14.76
21-22 2387.40 4.76 9 2.66 20 x 20 Duct 4.5 14.76
22-23 1193.70 2.38 3.5 1.03 10 x 16 Duct 4.5 14.76
E-24 8355.90 16.67 24 7.08 32 x 34 Elbow Duct 8.14 26.6992 18
24-25 7162.20 14.29 20.5 6.05 28 x 34 Duct 4.5 14.76
25-26 5968.50 11.90 18.5 5.46 28 x 30 Duct 4.5 14.76
26-27 4774.80 9.52 16.5 4.87 28 x 26 Duct 4.5 14.76
27-28 3581.10 7.14 11.5 3.39 20 x 26 Duct 4.5 14.76
28-29 2387.40 4.76 9 2.66 20 x 20 Duct 4.5 14.76
29-30 1193.70 2.38 3.5 1.03 10 x 16 Duct 4.5 14.76
F-31 8355.90 16.67 24 7.08 32 x 34 Elbow Duct 3.6 11.808 18
31-32 7162.20 14.29 20.5 6.05 28 x 34 Duct 4.5 14.76
32-33 5968.50 11.90 18.5 5.46 28 x 30 Duct 4.5 14.76
33-34 4774.80 9.52 16.5 4.87 28 x 26 Duct 4.5 14.76
34-35 3581.10 7.14 11.5 3.39 20 x 26 Duct 4.5 14.76
35-36 2387.40 4.76 9 2.66 20 x 20 Duct 4.5 14.76
36-37 1193.70 2.38 3.5 1.03 10 x 16 Duct 4.5 14.76
38-39 4774.80 9.52 16.5 4.87 28 x 26 Duct 4.5 14.76
39-40 3581.10 7.14 11.5 3.39 20 x 26 Duct 4.5 14.76
40-41 2387.40 4.76 9 2.66 20 x 20 Duct 4.5 14.76
41-42 1193.70 2.38 3.5 1.03 10 x 16 Duct 4.45 14.596
TOTAL LENGTH 756.0072 288.18
The total friction loss in the duct work from fan to last terminal 42 is:
Loss = total equivalent length x friction rate
For the total equivalent length, it appears that the longer run is from AHU 2 to terminal
42: 211.04 + 174.18 = 385.22 ft.
Friction rate: using Vsupply = 1700 fpm, cfm = 50136, Fr = 0.032 (from chart 7, page 2-33
friction loss for round duct)
Loss = 385.22 ft. x (0.032 in wg /100 ft.)
Loss = 0.1387 in wg
The total static pressure required at fan discharge is the sum of the terminal operating
pressure and the loss in the duct work. Credit can be taken for the regain between the
first and last section of the duct.
From chart 7, p. 2-33 of Carrier Handbook with cfm of 1193.7 and equivalent circular
duct diameter = 13.7 in., velocity in the last section = 1220 fpm.
Using 75% regain coefficient;
2
Regain = 0.75 [ ( 1700/4000 )−( 1220/4000 ) ] = 0.0657 in wg
Therefore, the total static pressure at fan discharge is;
= duct friction + terminal pressure – regain
= 0.1387 + 0.15 – 0.0657
= 0.223 in wg
Duct Sizing for Return Air in Zone 2:
47533.5
CFM return for eachterminal= =1760.5cfm
27
Q 47533.5
A= = =31.69
V 1500
Adde
Air CFM d
Duct Are Area Duct Lengt Length
Quantit Capacit Item Equiv.
Section a% ft. Size h (m) (ft)
y y% Lengt
h
AHU 2 - 31.6 Elbow
68 x 72
1 47533.5 100.00 100 9 Duct 15.55 51.004 36.33
96. 30.5 series
68 x 72
1-2 45773 96.30 5 8 Elbow 5.44 17.8432 36.33
94. 29.9
64 x 72
2-3 44012.5 92.59 5 5 Duct 9 29.52
91. 29.0
64 x 72
3-4 42242 88.87 5 0 Duct 9 29.52
88. 28.0
64 x 68
4-5 40491.5 85.19 5 5 Duct 9 29.52
27.2
64 x 68
5-6 38731 81.48 86 5 Duct 9 29.52
26.3
60 x 68
6-7 36970.5 77.78 83 0 Duct 5.25 17.22
25.3
60 x 60
7-8 35210 74.07 80 5 Duct 5.25 17.22
20.2 Duct
52 x 60
8-A 26407.5 55.56 64 8 Elbow 3.5 11.48 28
15.5 Elbow
52 x 46
A-B 19365.5 40.74 49 3 Duct 6.95 22.796 28
33. 10.6
36 x 46
B-C 12323.5 25.93 5 2 Duct 6.95 22.796
C-25 5281.5 11.11 17. 5.55 36 x 24 Duct 6.95 22.796
5
21.
36 x 30
8-9 7042 14.81 5 6.81 Duct 9 29.52
17.
36 x 24
9-10 5281.5 11.11 5 5.55 Duct 9 29.52
11.
24 x 24
10-11 3521 7.41 5 3.64 Duct 9 29.52
11-12 1760.5 3.70 7 2.22 16 x 24 Duct 9 29.52
21. Elbow
36 x 30
A-13 7042 14.81 5 6.81 Duct 4.5 14.76 16
17.
36 x 24
13-14 5281.5 11.11 5 5.55 Duct 9 29.52
11.
24 x 24
14-15 3521 7.41 5 3.64 Duct 9 29.52
15-16 1760.5 3.70 7 2.22 16 x 24 Duct 9 29.52
21. Elbow
36 x 30
B-17 7042 14.81 5 6.81 Duct 3 9.84 16
17.
36 x 24
17-18 5281.5 11.11 5 5.55 Duct 9 29.52
11.
24 x 24
18-19 3521 7.41 5 3.64 Duct 9 29.52
19-20 1760.5 3.70 7 2.22 16 x 24 Duct 9 29.52
21. Elbow
36 x 30
C-21 7042 14.81 5 6.81 Duct 1.5 4.92 16
17.
36 x 24
21-22 5281.5 11.11 5 5.55 Duct 9 29.52
11.
24 x 24
22-23 3521 7.41 5 3.64 Duct 9 29.52
23-24 1760.5 3.70 7 2.22 16 x 24 Duct 9 29.52
11.
24 x 24
25-26 3521 7.41 5 3.64 Duct 9 29.52
26-27 1760.5 3.70 7 2.22 16 x 24 Duct 9 29.52
773.555 176.6
TOTAL LENGTH 2 6
The total friction loss in the duct work from fan to last terminal 27 is:
Loss = total equivalent length x friction rate
For the total equivalent length, it appears that the longer run is from AHU 2 to terminal
27: 109.83 + 128.66 = 238.5 ft.
Friction rate: using Vsupply = 1500 fpm, cfm = 47533.5, Fr = 0.028 (from chart 7, page 2-
33 friction loss for round duct)
Loss = 238.5 ft. x (0.028 in wg /100 ft.)
Loss = 0.0668 in wg
The total static pressure required at fan discharge is the sum of the terminal operating
pressure and the loss in the duct work. Credit can be taken for the regain between the
first and last section of the duct.
From chart 7, p. 2-33 of Carrier Handbook with cfm of 1760.5 and equivalent circular
duct diameter = 21.3 in., velocity in the last section = 720 fpm.
Using 75% regain coefficient;
2
Regain = 0.75 [ ( 1500/4000 )−( 720/4000 ) ] = 0.0812 in wg
Therefore, the total static pressure at fan discharge is;
= duct friction + terminal pressure – regain
= 0.0668 + 0.15 – 0.0812
= 0.1356 in wg
ZONE 3
60838.8
CFM supply for each terminal= =770.11 cfm
79
Q 60838.8
A= = =3 5.79
V 1700
Duct area = percent of area times initial duct area (fan at section 1)
The Duct sizes can then be determined by using Carrier handbook, PP 2-36, Table 6.
Table 12.
CFM Added
Duct Air Capacity Area Area Duct Length Equiv.
Section Quantity % % ft Size Item (m) Length (ft) length
AHU 3 - A 60838.80 100.00 100 35.79 72 x 76 Duct Elbow 7.8 25.584 38
A-1 53907.80 88.61 91.5 32.75 68 x 76 series elbow 8 26.24 36.33
1-2 53137.70 87.34 90 32.21 68 x 68 series elbow 5.4 17.712 36
2-B 52367.59 86.08 89.5 32.03 68 x 68 series elbow 1.2 3.936 36
B-C 40815.94 67.09 73.5 26.31 68 x 56 series elbow 8.4 27.552 35
C-D 29264.29 48.10 56 20.04 52 x 56 series elbow 3.76 12.3328 29.56
D-E 16942.53 27.85 35.5 12.71 42 x 44 series elbow 8.6 28.208 24
E-68 2310.44 3.80 7 2.51 18 x 20 Duct Elbow 3.9 12.792 10
B-3 11551.65 18.99 26 9.31 36 x 38 Elbow Duct 2.4 7.872 19.83
3-4 10781.54 17.72 25 8.95 36 x 36 Duct 4 13.12
4-5 10011.43 16.46 23 8.23 34 x 36 Duct 4.2 13.776
5-6 9241.32 15.19 21.5 7.69 34 x 34 Duct 4.15 13.612
6-7 8471.21 13.92 20.5 7.34 32 x 34 Duct 4 13.12
7-8 7701.1 12.66 19.5 6.98 32 x 32 Duct 4.2 13.776
8-9 6930.99 11.39 18.5 6.62 30 x 32 Duct 4.15 13.612
9-10 6160.88 10.13 16.5 5.91 30 x 30 Duct 4 13.12
10-11 5390.77 8.86 14.5 5.19 26 x 30 Duct 4.2 13.776
11-12 4620.66 7.59 13 4.65 26 x 26 Duct 4.15 13.612
12-13 3850.55 6.33 10.5 3.76 26 x 24 Duct 4 13.12
13-14 3080.44 5.06 9 3.22 20 x 24 Duct 4.2 13.776
14-15 2310.33 3.80 7 2.51 20 x 18 Duct 4.15 13.612
15-16 1540.22 2.53 5.5 1.97 16 x 18 Duct 4 13.12
16-17 770.11 1.27 2 0.72 6 x 18 Duct 4.2 13.776
C-18 11551.65 18.99 26 9.31 36 x 38 Elbow Duct 5.87 19.2536 19.83
18-19 10781.54 17.72 25 8.95 36 x 36 Duct 4 13.12
19-20 10011.43 16.46 23 8.23 34 x 36 Duct 4.2 13.776
20-21 9241.32 15.19 21.5 7.69 34 x 34 Duct 4.15 13.612
21-22 8471.21 13.92 20.5 7.34 32 x 34 Duct 4 13.12
22-23 7701.1 12.66 19.5 6.98 32 x 32 Duct 4.2 13.776
23-24 6930.99 11.39 18.5 6.62 30 x 32 Duct 4.15 13.612
24-25 6160.88 10.13 16.5 5.91 30 x 30 Duct 4 13.12
25-26 5390.77 8.86 14.5 5.19 26 x 30 Duct 4.2 13.776
26-27 4620.66 7.59 13 4.65 26 x 26 Duct 4.15 13.612
27-28 3850.55 6.33 10.5 3.76 26 x 24 Duct 4 13.12
28-29 3080.44 5.06 9 3.22 20 x 24 Duct 4.2 13.776
29-30 2310.33 3.80 7 2.51 20 x 18 Duct 4.15 13.612
30-31 1540.22 2.53 5.5 1.97 16 x 18 Duct 4 13.12
31-32 770.11 1.27 2 0.72 6 x 18 Duct 4.2 13.776
D-33 12321.76 20.25 27 9.66 36 x 38 Elbow Duct 4.7 15.416 19.83
33-34 11551.65 18.99 26 9.31 36 x 38 Duct 6.4 20.992
34-35 10781.54 17.72 25 8.95 36 x 36 Duct 4.5 14.76
35-36 10011.43 16.46 23 8.23 34 x 36 Duct 4.5 14.76
36-37 9241.32 15.19 21.5 7.69 34 x 34 Duct 3.4 11.152
37-38 8471.21 13.92 20.5 7.34 32 x 34 Duct 4.5 14.76
38-39 7701.1 12.66 19.5 6.98 32 x 32 Duct 4.5 14.76
39-40 6930.99 11.39 18.5 6.62 30 x 32 Duct 3.4 11.152
40-41 6160.88 10.13 16.5 5.91 30 x 30 Duct 4.5 14.76
41-42 5390.77 8.86 14.5 5.19 26 x 30 Duct 4.5 14.76
42-43 4620.66 7.59 13 4.65 26 x 26 Duct 3.4 11.152
43-44 3850.55 6.33 10.5 3.76 26 x 24 Duct 4.5 14.76
44-45 3080.44 5.06 9 3.22 20 x 24 Duct 4.5 14.76
45-46 2310.33 3.80 7 2.51 20 x 18 Duct 3.4 11.152
46-47 1540.22 2.53 5.5 1.97 16 x 18 Duct 4.5 14.76
47-48 770.11 1.27 2 0.72 6 x 18 Duct 4.5 14.76
E-49 14632.09 24.05 31.5 11.27 40 x 40 Elbow Duct 0.8 2.624 21.56
49-50 13861.98 22.78 30.5 10.92 40 x 40 Duct 4.5 14.76
50-51 13091.89 21.52 29.5 10.56 40 x 38 Duct 4.5 14.76
51-52 12321.76 20.25 27 9.66 36 x 38 Duct Elbow 4.2 13.776 19.83
52-53 11551.65 18.99 26 9.31 36 x 38 Duct 6.3 20.664
53-54 10781.54 17.72 25 8.95 36 x 36 Duct 4.5 14.76
54-55 10011.43 16.46 23 8.23 34 x 36 Duct 4.5 14.76
55-56 9241.32 15.19 21.5 7.69 34 x 34 Duct 3.4 11.152
56-57 8471.21 13.92 20.5 7.34 32 x 34 Duct 4.5 14.76
57-58 7701.1 12.66 19.5 6.98 32 x 32 Duct 4.5 14.76
58-59 6930.99 11.39 18.5 6.62 30 x 32 Duct 3.4 11.152
59-60 6160.88 10.13 16.5 5.91 30 x 30 Duct 4.5 14.76
60-61 5390.77 8.86 14.5 5.19 26 x 30 Duct 4.5 14.76
61-62 4620.66 7.59 13 4.65 26 x 26 Duct 3.4 11.152
62-63 3850.55 6.33 10.5 3.76 26 x 24 Duct 4.5 14.76
63-64 3080.44 5.06 9 3.22 20 x 24 Duct 4.5 14.76
64-65 2310.33 3.80 7 2.51 20 x 18 Duct 3.4 11.152
65-66 1540.22 2.53 5.5 1.97 16 x 18 Duct 4.5 14.76
66-67 770.11 1.27 2 0.72 6 x 18 Duct 4.5 14.76
68-69 1540.22 2.53 5.5 1.97 10 x 12 Duct 4.5 14.76
69-70 770.11 1.27 2 0.72 6 x 10 Duct 4.5 14.76
A-H 6930.99 11.39 18.5 6.62 30 x 32 Duct Elbow 4.4 14.432
H-71 6930.99 11.39 18.5 6.62 30 x 32 series elbow 4.85 15.908
71-72 6160.88 10.13 16.5 5.91 30 x 30 series elbow 5.6 18.368 16
72-73 5390.77 8.86 14.5 5.19 26 x 30 series elbow 5 16.4 15.625
73-74 4620.66 7.59 13 4.65 26 x 26 series elbow 5.8 19.024 13.875
74-75 3850.55 6.33 10.5 3.76 26 x 24 series elbow 5.9 19.352 13.75
75-76 3080.44 5.06 9 3.22 20 x 24 series elbow 6.25 20.5 11
76-77 2310.33 3.80 7 2.51 20 x 18 series elbow 5.45 17.876 10
77-78 1540.22 2.53 5.5 1.97 16 x 18 series elbow 5 16.4 10
78-79 770.11 1.27 2 0.72 6 x 18 series elbow 4.86 15.9408 8
TOTAL LENGTH 1250.4672 444.02
The total friction loss in the duct work from fan to last terminal 79 is:
Loss = total equivalent length x friction rate
For the total equivalent length, it appears that the longer run is from AHU 3 to terminal
67: 399.64 + 276.28 = 675.92 ft.
Friction rate: using Vsupply = 1700 fpm, cfm = 60838.8, Fr = 0.0325 (from chart 7, page
2-33 friction loss for round duct)
Loss = 675.92 ft. x (0.0325 in wg /100 ft.)
Loss = 0.22 in wg
The total static pressure required at fan discharge is the sum of the terminal operating
pressure and the loss in the duct work. Credit can be taken for the regain between the
first and last section of the duct.
From chart 7, p. 2-33 of Carrier Handbook with cfm of 770.11 and equivalent circular
duct diameter = 11.5 in., velocity in the last section = 1110 fpm.
Using 75% regain coefficient;
2
Regain = 0.75 [ ( 1700/4000 )−( 1110/4000 ) ] = 0.0777 in wg
Therefore, the total static pressure at fan discharge is;
= duct friction + terminal pressure – regain
= 0.22 + 0.15 – 0.0777
= 02923 in wg
57253.8
CFM return for eachterminal= =2120.5 cfm
27
air quantity ∈duct section
Percent of cfm =
total air quantity
Q 57253.8
A= = =38.17
V 1500
Adde
Air CFM d
Duct Are Area Duct Lengt Length
Quantit Capacit Item Equiv.
Section a% ft. Size h (m) (ft)
y y% Lengt
h
AHU 3 - 38.1
68 x 88
1 57253.8 100.00 100 7 Elbow 32 104.96 39.44
96. 36.8
64 x 88
1-2 55133.3 96.30 5 3 Duct 8.2 26.896
94. 36.0
64 x 88
2-3 53012.8 92.59 5 7 Duct 8.2 26.896
91. 34.9
64 x 84
3-4 50892.3 88.89 5 3 Duct 8.2 26.896
88. 33.7
64 x 80
4-5 48771.8 85.19 5 8 Duct 8.2 26.896
32.8
64 x 80
5-6 46651.3 81.48 86 3 Duct 8.2 26.896
31.6 Elbow
60 x 80
6-A 44530.8 77.78 83 8 Duct 12.6 41.328 40.33
21.3 Duct
60 x 56
A-15 27566.8 48.15 56 8 Elbow 12.7 41.656 30.33
37. 14.3 Elbow
42 x 54
A-7 16964 29.63 5 1 Duct 3.9 12.792 29
33. 12.7
42 x 48
7-8 14843.5 25.93 5 9 Duct 8.2 26.896
29. 11.2
42 x 42
8-9 12723 22.22 5 6 Duct 8.2 26.896
9-10 10602.5 18.52 26 9.92 38 x 42 Duct 8.2 26.896
21.
38 x 34
10-11 8482 14.81 5 8.21 Duct 8.2 26.896
17.
30 x 34
11-12 6361.5 11.11 5 6.68 Duct 8.2 26.896
11.
30 x 24
12-13 4241 7.41 5 4.39 Duct 8.2 26.896
13-14 2120.5 3.70 7 2.67 18 x 24 Duct 8.2 26.896
19.8
56 x 56
15-16 25446 44.44 52 5 Duct 4.5 14.76
16-17 23325.5 40.74 49 18.7 52 x 56 Duct 7.9 25.912
0
17.1
52 x 50
17-18 21205 37.04 45 8 Duct 4.5 14.76
15.6
48 x 50
18-19 19084.5 33.33 41 5 Duct 7.9 25.912
37. 14.3
42 x 54
19-20 16964 29.63 5 1 Duct 4.5 14.76
33. 12.7
42 x 48
20-21 14843.5 25.93 5 9 Duct 7.9 25.912
29. 11.2
42 x 42
21-22 12723 22.22 5 6 Duct 4.5 14.76
22-23 10602.5 18.52 26 9.92 38 x 42 Duct 7.9 25.912
21.
38 x 34
23-24 8482 14.81 5 8.21 Duct 4.5 14.76
17.
30 x 34
24-25 6361.5 11.11 5 6.68 Duct 4.5 14.76
11.
30 x 24
25-26 4241 7.41 5 4.39 Duct 4.5 14.76
26-27 2120.5 3.70 7 2.67 18 x 24 Duct 4.5 14.76
745.21
TOTAL LENGTH 6 139.1
The total friction loss in the duct work from fan to last terminal 27 is:
Loss = total equivalent length x friction rate
For the total equivalent length, it appears that the longer run is from AHU 3 to terminal
27: 166.22 + 110.06 = 276.28 ft.
Friction rate: using Vsupply = 1500 fpm, cfm = 57253.8, Fr = 0.025 (from chart 7, page 2-
33 friction loss for round duct)
Loss = 276.28 ft. x (0.025 in wg /100 ft.)
Loss = 0.069 in wg
The total static pressure required at fan discharge is the sum of the terminal operating
pressure and the loss in the duct work. Credit can be taken for the regain between the
first and last section of the duct.
From chart 7, p. 2-33 of Carrier Handbook with cfm of 2120.5 and equivalent circular
duct diameter = 22.6 in., velocity in the last section = 780 fpm.
Using 75% regain coefficient;
2
Regain = 0.75 [ ( 1500/4000 )−( 780/4000 ) ] = 0.0777 in wg
Therefore, the total static pressure at fan discharge is;
= duct friction + terminal pressure – regain
= 0.069 + 0.15 – 0.0777
= 0.142 in wg
ZONE 4
26131
CFM supply for each terminal= =580.7 cfm
45
Q 26131
A= = =15.37
V 1700
Duct area = percent of area times initial duct area (fan at section 1)
The Duct sizes can then be determined by using Carrier handbook, PP 2-36, Table 6.
The Additional Equivalent Length can be determining from Carrier handbook, PP 2-44,
Table 12.
Adde
Air CFM
Duct Are Area Duct Lengt Length(ft d
Quantit Capacit Item
Section a% ft Size h (m) ) Equiv.
y y%
length
15.3
AHU 4 - 1 26131 100.00 100 7 48 x 50 Duct 8.88 29.1264
15.0
1-2 25550.3 97.78 98 6 46 x 50 Duct 4.5 14.76
14.8
2-3 24969.6 95.56 96.5 3 46 x 50 Duct 4.5 14.76
14.5
3-4 24388.9 93.33 94.5 2 46 x 50 Duct 4.5 14.76
14.2
4-A 23808.2 91.11 93 9 46 x 48 Elbow Duct 6 19.68 25
12.1
A-B 19162.6 73.33 79 4 42 x 44 Duct 4.5 14.76
B-C 14517 55.55 64 9.84 42 x 36 Duct 4.5 14.76
C-D 9871.4 37.78 46 7.07 34 x 32 Duct Elbow 3.5 11.48 18
D-E 9290.7 35.55 44 6.76 32 x 32 Duct 4.5 14.76
E-F 8710 33.33 41 6.30 32 x 30 Duct 4.5 14.76
F-G 8129.3 31.11 39 5.99 30 x 30 Duct 4.5 14.76
G-H 6387.2 24.44 31.5 4.84 28 x 28 Duct 4.5 14.76
H-I 4645.1 17.78 25 3.84 24 x 28 Duct 4.5 14.76
I-J 2903 11.11 17.5 2.69 24 x 18 Duct 4.5 14.76
A-5 4645.6 17.78 25 3.84 24 x 28 Elbow Duct 1.5 4.92 13
5-6 4064.9 15.56 23 3.54 20 x 28 Duct 4.5 14.76
6-7 3484.2 13.33 19.5 3.00 20 x 24 Duct 4.5 14.76
7-8 2903.5 11.11 17.5 2.69 18 x 24 Duct 4.5 14.76
8-9 2322.8 8.89 14.5 2.23 18 x 20 Duct 4.5 14.76
9-10 1742.1 6.67 11.5 1.77 14 x 20 Duct 4.5 14.76
10-11 1161.4 4.44 7 1.08 14 x 12 Duct 4.5 14.76
11-12 580.7 2.22 3.5 0.54 8 x 12 Duct 4.5 14.76
B-13 4645.6 17.78 25 3.84 24 x 28 Elbow Duct 1.5 4.92 13
13-14 4064.9 15.56 23 3.54 20 x 28 Duct 4.5 14.76
14-15 3484.2 13.33 19.5 3.00 20 x 24 Duct 4.5 14.76
15-16 2903.5 11.11 17.5 2.69 18 x 24 Duct 4.5 14.76
16-17 2322.8 8.89 14.5 2.23 18 x 20 Duct 4.5 14.76
17-18 1742.1 6.67 11.5 1.77 14 x 20 Duct 4.5 14.76
18-19 1161.4 4.44 7 1.08 14 x 12 Duct 4.5 14.76
19-20 580.7 2.22 3.5 0.54 8 x 12 Duct 4.5 14.76
C-21 4645.6 17.78 25 3.84 24 x 28 Elbow Duct 1.5 4.92 13
21-22 4064.9 15.56 23 3.54 20 x 28 Duct 4.5 14.76
22-23 3484.2 13.33 19.5 3.00 20 x 24 Duct 4.5 14.76
23-24 2903.5 11.11 17.5 2.69 18 x 24 Duct 4.5 14.76
24-25 2322.8 8.89 14.5 2.23 18 x 20 Duct 4.5 14.76
25-26 1742.1 6.67 11.5 1.77 14 x 20 Duct 4.5 14.76
26-27 1161.4 4.44 7 1.08 14 x 12 Duct 4.5 14.76
27-28 580.7 2.22 3.5 0.54 8 x 12 Duct 4.5 14.76
D-29 580.7 2.22 3.5 0.54 8 x 12 Elbow Duct 1 3.28 5
E-30 580.7 2.22 3.5 0.54 8 x 12 Elbow Duct 1 3.28 5
F-31 580.7 2.22 3.5 0.54 8 x 12 Elbow Duct 1 3.28 5
G-32 1742.1 6.67 11.5 1.77 14 x 20 Elbow Duct 1 3.28 8
32-33 1161.4 4.44 7 1.08 14 x 12 Duct 4.5 14.76
33-34 580.7 2.22 3.5 0.54 8 x 12 Duct 4.5 14.76
H-35 1742.1 6.67 11.5 1.77 14 x 20 Elbow Duct 1 3.28 8
35-36 1161.4 4.44 7 1.08 14 x 12 Duct 4.5 14.76
36-37 580.7 2.22 3.5 0.54 8 x 12 Duct 4.5 14.76
I-38 1742.1 6.67 11.5 1.77 14 x 20 Elbow Duct 1 3.28 8
38-39 1161.4 4.44 7 1.08 14 x 12 Duct 4.5 14.76
39-40 580.7 2.22 3.5 0.54 8 x 12 Duct 4.5 14.76
J-41 1742.1 6.67 11.5 1.77 14 x 20 Elbow Duct 1 3.28 8
41-42 1161.4 4.44 7 1.08 14 x 12 Duct 4.5 14.76
42-43 580.7 2.22 3.5 0.54 8 x 12 Duct 4.5 14.76
J-44 1160.9 4.44 7 1.08 14 x 12 Duct Elbow 5.5 18.04 8
44-45 580.7 2.22 3.5 0.54 8 x 12 Duct 4.5 14.76
TOTAL LENGTH 721.2064 137
The total friction loss in the duct work from fan to last terminal 45 is:
Loss = total equivalent length x friction rate
For the total equivalent length, it appears that the longer run is from AHU 4 to terminal
43: 260.33 + 51 = 311.33 ft.
Friction rate: using Vsupply = 1700 fpm, cfm = 26131, Fr = 0.056 (from chart 7, page 2-33
friction loss for round duct)
Loss = 311.33 ft. x (0.056 in wg /100 ft.)
Loss = 0.1743 in wg
The total static pressure required at fan discharge is the sum of the terminal operating
pressure and the loss in the duct work. Credit can be taken for the regain between the
first and last section of the duct.
From chart 7, p. 2-33 of Carrier Handbook with cfm of 580.7 and equivalent circular duct
diameter = 10.7 in., velocity in the last section = 940 fpm.
Using 75% regain coefficient;
2
Regain = 0.75 [ ( 1700/4000 )−( 940/ 4000 ) ] = 0.09405 in wg
Therefore, the total static pressure at fan discharge is;
= duct friction + terminal pressure – regain
= 0.1743 + 0.15 – 0.09405
= 0.230 in wg
Q 24706
A= = =16.47
V 1500
Adde
Air CFM d
Duct Are Area Duct Lengt Length
Quantit Capacit Item Equiv.
Section a% ft. Size h (m) (ft)
y y% Lengt
h
AHU 4 - 16.4
50 x 50
A 24706 100.00 100 7 Duct 0.95 3.116
20588.3 14.3 Elbow
44 x 50
A-1 3 83.33 87 3 Duct 3.88 12.7264 27
19215.7 13.6 Duct
44 x 48
1-B 8 77.78 83 7 Elbow 8.82 28.9296 24
15098.1 11.2
42 x 42
B-C 1 61.11 68 0 Duct 4.5 14.76
C-D 9607.89 38.89 47 7.74 30 x 40 Duct 4.5 14.76
D-15 5490.22 22.22 29.5 4.86 30 x 26 Duct 4 13.12
Elbow
24 x 26
A-2 4117.67 16.67 24 3.95 Duct 5 16.4 14
2-3 2745.11 11.11 17.5 2.88 22 x 20 Duct 9 29.52
3-4 1372.56 5.56 10.6 1.75 14 x 20 Duct 9 29.52
Elbow
24 x 26
B-5 4117.67 16.67 24 3.95 Duct 8.82 28.9296 14
5-6 2745.11 11.11 17.5 2.88 22 x 20 Duct 9 29.52
6-7 1372.56 5.56 10.6 1.75 14 x 20 Duct 9 29.52
Elbow
30 x 26
C-8 5490.22 22.22 29.5 4.86 Duct 4.32 14.1696 15
8-9 4117.67 16.67 24 3.95 24 x 26 Duct 9 29.52
9-10 2745.11 11.11 17.5 2.88 22 x 20 Duct 9 29.52
10-11 1372.56 5.56 10.6 1.75 14 x 20 Duct 9 29.52
Elbow
24 x 26
D-12 4117.67 16.67 24 3.95 Duct 8.82 28.9296 14
12-13 2745.11 11.11 17.5 2.88 22 x 20 Duct 9 29.52
13-14 1372.56 5.56 10.6 1.75 14 x 20 Duct 9 29.52
Duct
24 x 26
15-16 4117.67 16.67 24 3.95 Elbow 9.32 30.5696 14
Duct
22 x 20
16-17 2745.11 11.11 17.5 2.88 Elbow 10 32.8 8
17-18 1372.56 5.56 10.6 1.75 14 x 20 Duct 9 29.52
534.410
TOTAL LENGTH 4 130
The total friction loss in the duct work from fan to last terminal 18 is:
Loss = total equivalent length x friction rate
For the total equivalent length, it appears that the longer run is from AHU 4 to terminal
18: 55.03 + 73 = 128.03 ft.
Friction rate: using Vsupply = 1500 fpm, cfm = 24706, Fr = 0.0435 (from chart 7, page 2-
33 friction loss for round duct)
Loss = 128.03 ft. x (0.0435 in wg /100 ft.)
Loss = 0.0557 in wg
The total static pressure required at fan discharge is the sum of the terminal operating
pressure and the loss in the duct work. Credit can be taken for the regain between the
first and last section of the duct.
From chart 7, p. 2-33 of Carrier Handbook with cfm of 1372.56 and equivalent circular
duct diameter = 18.2 in., velocity in the last section = 720 fpm.
Using 75% regain coefficient;
2
Regain = 0.75 [ ( 1500/4000 )−( 720/4000 ) ] = 0.0812 in wg
Therefore, the total static pressure at fan discharge is;
= duct friction + terminal pressure – regain
= 0.0557 + 0.15 – 0.0812
= 0.1245 in wg
ZONE 5
21216.3
CFM supply for each terminal= =848.66 cfm
25
air quantity ∈duct section
Percent of cfm =
total air quantity
Q 21216.3
A= = =12.48
V 1700
Duct area = percent of area times initial duct area (fan at section 1)
The Duct sizes can then be determined by using Carrier handbook, PP 2-36, Table 6.
The Additional Equivalent Length can be determining from Carrier handbook, PP 2-44,
Table 12.
CFM Added
Duct Air Area Area Duct Length Length
Capacit Item Equiv.
Section Quantity % ft Size (m) (ft)
y% length
AHU 5 - A 21216.43 100.00 100 12.48 44 x 44 Elbow 1.6 5.248
A-10 16124.47 76.00 81 10.11 36 x 44 Duct 4.5 14.76
10-16 11032.51 52.00 60 7.49 36 x 32 Duct 4.5 14.76
16-21 6789.21 32.00 40 4.99 24 x 32 Duct 4.5 14.76
21-25 2545.91 12.00 18.5 2.31 24 x 16 Duct 4.5 14.76
A-2 1697.32 8.00 13 1.62 16 x 16 Elbow Duct 4.5 14.76 7.67
2-1 848.66 4.00 7 0.87 8 x 16 Duct 4.5 14.76
A-3 3394.64 16.00 23 2.87 20 x 22 Elbow Duct 4.5 14.76 13.2
3-4 2545.98 12.00 18.5 2.31 20 x 18 Duct 4.5 14.76
4-5 1697.32 8.00 13 1.62 14 x 18 Duct 4.5 14.76
5-6 848.66 4.00 7 0.87 14 x 10 Duct 4.5 14.76
10-9 2545.98 12.00 18.5 2.31 20 x 18 Duct 4.5 14.76
9-8 1697.32 8.00 13 1.62 14 x 18 Duct 4.5 14.76
8-7 848.66 4.00 7 0.87 14 x 10 Duct 4.5 14.76
10-11 1697.32 8.00 13 1.62 14 x 18 Duct 4.5 14.76
11-12 848.66 4.00 7 0.87 14 x 10 Duct 4.5 14.76
16-17 848.66 4.00 7 0.87 14 x 10 Duct 4.5 14.76
16-15 2545.98 12.00 18.5 2.31 20 x 18 Duct 4.5 14.76
15-14 1697.32 8.00 13 1.62 14 x 18 Duct 4.5 14.76
14-13 848.66 4.00 7 0.87 14 x 10 Duct 4.5 14.76
21-22 848.66 4.00 7 0.87 14 x 10 Duct 4.5 14.76
21-20 2545.98 12.00 18.5 2.31 20 x 18 Duct 4.5 14.76
20-19 1697.32 8.00 13 1.62 14 x 18 Duct 4.5 14.76
19-18 848.66 4.00 7 0.87 14 x 10 Duct 4.5 14.76
25-24 1697.32 8.00 13 1.62 14 x 18 Duct 4.5 14.76
24-23 848.66 4.00 7 0.87 14 x 10 Duct 4.5 14.76
TOTAL LENGTH 374.248 20.87
The total friction loss in the duct work from fan to last terminal 25 is:
Loss = total equivalent length x friction rate
For the total equivalent length, it appears that the longer run is from AHU 5 to terminal
25: 28.5 ft.
Friction rate: using Vsupply = 1700 fpm, cfm = 21216.3, Fr = 0.064 (from chart 7, page 2-
33 friction loss for round duct)
Loss = 28.5 ft. x (0.064 in wg /100 ft.)
Loss = 0.01824 in wg
The total static pressure required at fan discharge is the sum of the terminal operating
pressure and the loss in the duct work. Credit can be taken for the regain between the
first and last section of the duct.
From chart 7, p. 2-33 of Carrier Handbook with cfm of 848.66 and equivalent circular
duct diameter = 12.9 in., velocity in the last section = 1000 fpm.
Using 75% regain coefficient;
2
Regain = 0.75 [ ( 1700/4000 )−( 1000/4000 ) ] = 0.0886 in wg
Therefore, the total static pressure at fan discharge is;
= duct friction + terminal pressure – regain
= 0.01824 + 0.15 – 0.0886
= 0.15 in wg
20766.43
CFM return for eacht erminal= =848.66 cfm
12
Q 20766.43
A= = =12.48
V 1500
Adde
d
Duct
Air CFM Equiv.
Size
Duct Quantit Capacit Are Area Lengt Length Lengt
Section y y% a% ft. Item h (m) (ft) h
AHU 5 - 20766.4 13.8 46 x Duct
A 3 100.00 100 4 46 Elbow 16.8 55.104 25
19035.8 13.0 44 x
A-B 9 91.67 94 1 46 Duct 4.66 15.2848
15574.8 80. 11.1 44 x
B-C 2 75.00 5 4 40 Duct 4.66 15.2848
12113.7 65. 36 x
C-D 5 58.33 6 9.08 40 Duct 4.66 15.2848
10383.2 34 x Duct
D-7 2 50.00 58 8.03 38 Elbow 14 45.92 20
30 x Duct
7-E 8652.68 41.67 50 6.92 36 Elbow 12.86 42.1808 16
30 x
E-F 6922.14 33.33 41 5.67 30 Duct 5.56 18.2368
32. 24 x
F-G 5191.61 25.00 5 4.50 30 Duct 5.56 18.2368
24 x Duct
G-11 3461.07 16.67 24 3.32 22 Elbow 7.96 26.1088 12
14 x Elbow
A-1 1730.54 8.33 13 1.80 22 Duct 7.8 25.584 10.5
24 x Elbow
B-2 3461.07 16.67 24 3.32 22 Duct 4.5 14.76 12
14 x
2-3 1730.54 8.33 13 1.80 22 Duct 9 29.52
24 x Elbow
C-4 3461.07 16.67 24 3.32 22 Duct 1.2 3.936 12
14 x
4-5 1730.54 8.33 13 1.80 22 Duct 9 29.52
14 x Elbow
D-6 1730.54 8.33 13 1.80 22 Duct 6.9 22.632 10.5
14 x Elbow
E-8 1730.54 8.33 13 1.80 22 Duct 6.1 20.008 10.5
14 x Elbow
F-9 1730.54 8.33 13 1.80 22 Duct 4.87 15.9736 10.5
14 x Elbow
G-10 1730.54 8.33 13 1.80 22 Duct 3.64 11.9392 10.5
14 x
11-12 1730.54 8.33 13 1.80 22 Duct 9 29.52
455.034
TOTAL LENGTH 4 149.5
The total friction loss in the duct work from fan to last terminal 12 is:
Loss = total equivalent length x friction rate
For the total equivalent length, it appears that the longer run is from AHU 5 to terminal
12: 85.95 ft. + 73 = 158.95 ft.
Friction rate: using Vsupply = 1500 fpm, cfm = 20766.43, Fr = 0.04 (from chart 7, page 2-
33 friction loss for round duct)
Loss = 158.95 ft. x (0.04 in wg /100 ft.)
Loss = 0.0636 in wg
The total static pressure required at fan discharge is the sum of the terminal operating
pressure and the loss in the duct work. Credit can be taken for the regain between the
first and last section of the duct.
From chart 7, p. 2-33 of Carrier Handbook with cfm of 1730.54 and equivalent circular
duct diameter = 19.1 in., velocity in the last section = 880 fpm.
Using 75% regain coefficient;
2
Regain = 0.75 [ ( 1500/4000 )−( 880/4000 ) ] = 0.0692 in wg
Therefore, the total static pressure at fan discharge is;
= duct friction + terminal pressure – regain
= 0.0636 + 0.15 – 0.0692
= 0.144 in wg