Professional Documents
Culture Documents
Sch o la rs
Jo u rn a ls
African Journal of Physics Vol. 3 (5), pp. 110-118, May, 2016. Available online at
www.internationalscholarsjournals.org © International Scholars Journals
Author(s) retain the copyright of this article.
It is very useful to monitor and maintain a good power quality in an electric power system especially on
the distribution network. This paper describes a numerical method for calculation the propagation and
distortion of harmonics caused by a nonlinear load such as Adjustable Speed Drives (ASD) in a balance
distribution network. ASD injects harmonics current into the network, which causes voltage distortion
problems. Usually, the harmonics current, harmonics voltage, and Total Harmonics Distortion (THD) are
used as indices of power quality in harmonics case. They can be calculated at every buses of a
distribution network, as objective of this research. Another aim is to evaluate VTHD in every bus according
to its limitation in IEEE Standard 519-1992. This research uses harmonics current spectrum of an ASD as
sources and power flow study in ETAP Powerstation. Final conclusion of this work will be compared with
the IEEE tests and ETAP Powerstation as a validation. The IEEE Test System 13-buses, a balance
industrial system, were used as a case study. This work uses the Matlab software in m-file and the ETAP.
Key words: harmonics, propagation, THD, nonlinear load, balance distribution network.
INTRODUCTION
Quality of electric power in power system can be unbalance and harmonics [Wardhani, 1996].
classified in two categories; there are quality in transient Numerical analysis and simulations of harmonics are
and steady state condition. Quality in transient situation is used to quantify the distortion in voltage and current
observed according to the duration of disturbance and it waveforms on a power system distribution network in
can be categorized in three groups. The first is the fast order to determine the existence and mitigation of
transient such as switching-surge, spike (0.5 to 200 resonant conditions.
microseconds with frequency 0.2 to 5 kHz), pulse, and Ribeiro and Arillaga et al., proposed the models of
notch. The second is over voltage which more than 110% power system devices for calculating the harmonics
of nominal voltage, or under voltage which it is below of propagation caused by a nonlinear loads [Ribeiro,;
80 - 85% of nominal voltage, that occurs continuously in Arillaga et al., 1985].
80 millisecond to one second. These disturbances usually Stavros et al. shown the harmonics power flow caused
called as voltage dip such as voltage sag, depression, by wind turbine. They use different devices models with
interruption, flicker, and fluctuation. The third is blackout Ribeiro’s]. This work combines the both models.
or outage. This paper presents propagation of harmonics voltage,
Quality in steady state condition has continued property harmonics current and VTHD (voltage THD) caused by
such as variation of voltage, variation of frequency, phase an ASD installed on Bus-9 in a 13 buses balance
Sunaryati 110
Table 1. IEEE standard 519-1992 for voltage distortion limits [IEEE Standard 519-1992].
A B C 2
R1 h
RT
R1 jX1
R1 h jhX1
0.9 0.1h 0.9 0.1h
jhX1 X
Rp T
Figure 2. Transformer
model [Stavros et al.,
RS RT (4)
Modeling of distribution system and its component
X p hXT (5)
For correctly assessing the magnitude of harmonics in
power system, it is important to model all system
components. Rp 80RT (6)
2 2 2
Z h h XT Rp hXT R p
Load model
T (25) R1 R2 h2 X 2 j R2 h2 X 2 (7)
p T p T
There are three alternative load models for harmonics
analysis. Where in all cases, R1 and X1 are the
fundamental frequency resistance and reactance, related Distribution line model
to the nominal power of the load, where h is harmonics
order [Figure 1] [Stavros et al.,]. Distribution line is represented in equivalent circuit exact
Sunaryati 112
20
18
AC line 16
A L 14
magnitude (%)
o
12
B DC bus a
C d 10
8
6
4
2
0
Figure 3. Typical six-pulse front end 5 7 11 13 17 19 23 25 29 31 35 37
converter for AC drives [Product Data Harmonic order
Bulletin, 1994].
Figure 4. Spectrum of harmonic current caused by
6- Pulse ASD [Product Data Bulletin, 1994].
5 18.24 -55.68
0.1
7 11.90 -84.11
11 5.73 -143.56 0.05
13 4.01 -175.58 0
17 1.93 111.39
-0.05
19 1.39 68.30
23 0.94 -24.61 -0.1
2 h = (n x p) ± 1 (9)
0.646h
R R 1 (8)
192 0.518h 2 Where:
n = an integer (1, 2, 3, 4, 5 …)
p = number of pulses or rectifiers
Non-linear loads
For example, using a 6 pulse rectifier, the characteristic
harmonics will be:
Generally, the harmonic in power system analysis is
caused by nonlinear loads, such as fluorescent lamp, h = (1 x 6) ± 1 5th & 7th harmonics
solid state power conversion equipment like ASD [Arillaga
h = (2 x 6) ± 1 11th & 13th harmonics h
et al., 1985]. The terms “linear” and “non-linear” define = (3 x 6) ± 1 17th & 19th harmonics
the relationship of current to the voltage waveform. A
linear relationship exists between the voltage and current, h = (4 x 6) ± 1 23rd & 25th harmonics [Product Data
which is typical of an across-the-line load. A non-linear Bulletin, 1994]
load has a discontinuous current relationship that does
not correspond to the applied voltage waveform [Figure 3 Spectrum of harmonics current caused by six pulses ASD
and Table 2] [Product Data Bulletin, 1994]. is described on Figure 4, where its ITHD is 23.06%.
One example of nonlinear loads is ASD. The Signal of harmonics current caused by six pulses ASD
characteristics of harmonics on it are based on the is plotted on Figure 5. Admittance matrices of system
number of rectifiers (pulse number) used in a circuit and [Grainger and dan Stevenson, 1994; Gungor, 1988] can
113 Afr. J. Physics
h * Zh (n,9) Ibus-h Table 3. Per-Unit Line and Cable Impedance Data (base values:
13.8 kV; 10,000 kVA) [Abu-hashim et al., 1999].
Bus-n
From To R X R/X
Iasd
Vbus-h 1 2 0.00139 0.00296 0.516
Bus_9 5 3 0.00122 0.00243 0.502
5 6 0.00075 0.00063 1.19
5 7 0.00157 0.00131 1.198
Figure 6. Circuit for calculating the 5 8 0.00109 0.00091 1.19
harmonics voltage, harmonics currents,
VTHD, and ITHD [Stavros et al., ????].
V
bush hxZh (n,9)xIbush (12)
STUDY CASE
The system impedance of the system in Figure 6 was
determined from the fault MVA and X/R ratio at the utility
connection point. These values are 1000 MVA and 22.2,
respectively. This data was used for
obtaining system
equivalent impedance of the system.
The local (in-plant) generator was represented as a simple
determined from
Thevenin equivalent. The internal voltage,
the converged power flow solution, is
13.98/-1.52 kV. The equivalent impedance is the sub-
transient impedance which is 0.0366 + j1.3651 ohm.
The plant power factor correction capacitors are rated at 6000
kvar.
Figure 7. Load flow study of IEEE Test System 13 buses –
a balanced industrial system [Abu-hashim et al., 1999].
Flow chart of this research is shown in Figure 8.
RESULTS
be formed as:
The result of this research includes impedance diagram,
Yh (1,1) Yh (1,2) ... Yh (1,13) harmonics voltage spectrum, harmonics current
spectrum, impedance scan and validation of VTHD as
Yh (2,2) ... Yh (1,13) mentioned as follows.
Yh Yh (2,1) (10)
... ... ... ...
Harmonic impedance diagram
Yh (13,1) Yh (13,2) ... Yh (n, n) One of the results of this research is diagram of
Impedance matrices of Equation (10) is [3] harmonics impedance. It can be calculated by using the
Equations (3) to (8), and the results are shown in Figure
1
Yh Y h (11) 9. The data in Tables 5 and 6 will be used in this step [Abu-hashim
et al., 1999].
Table 5. Generation, Load, and Bus Voltage Data (from power flow study results) [Abu-hashim et al., 1999].
Bus Name Bus # Vmag (p.u.) (deg) Pgen kW Qgen kvar Pload kW Qload kvar
100:UTIL-69 1 1.000 0.00 7450 540 - -
01:69-1 2 0.999 -0.13 - - - -
03:MILL-1 5 0.994 -2.40 - - 2240 2000
50:GEN1 3 0.995 -2.39 2000 1910 - -
51:Aux 4 0.995 -3.53 - - 600 530
05:FDR F 6 0.994 -2.40 - - - -
49:RECT 9 0.980 -4.72 - - 1150 290
39:T3 SEC 10 0.996 -4.85 1310 1130
26:FDR G 7 0.994 -2.40 - - - -
06:FDR H 8 0.994 -2.40 - - - -
11:T4 SEC 12 0.979 -3.08 - - 370 330
19: T7 SEC 13 1.001 -4.69 - - 2800 2500
29:T11 SEC 11 0.981 -4.16 - - 810 800
calculated as follows:
-5 In Figure 13, the harmonics current on Bus-7 is higher
V7(1) = (1.8)(10 )(69kV) = 1.242 volt. than Bus 3, 5, 6, 8 and it is higher on Bus 11 than on
Bus-4, 9, 12.
-5
V7(2) = (0.3)(10 )(69kV) = 0.207 volt. In Figure 14, for overall value, the ITHD is higher than
VTHD. It can be clearly seen that the VTHD on Bus-9 and
It can be clearly seen that V7 on Bus-1 is higher than Bus-10 in this work were 10.61 and 10.63% respectively.
Bus-2. In Figure 11, the harmonics voltage on Bus-3 is
more higher than Bus 5, 6, 7 and 8, and it is more higher Whereas the ITHD is dispersed. ITHD on Bus 11 is
on Bus 9 than Bus-4,11, and 12. higher than others. Five the biggest ITHD are on Bus-11,
13, 7, 8 and 12. VTHD on Bus 9 and 10 are higher than
-4
V11(7) = (3.5)(10 )(13.8kV) = 4.8 volt. on the others Buses.
-4
V11(8) = (2.1)(10 )(13.8kV) = 2.89 volt.
Validation and comparison of VTHD
Harmonic current spectrum For comparison purposes as has been shown on Figure
15, the IEEE test results, this work Matlab), and ETAP
In Figure 12, the harmonics current on Bus-1 is higher Powerstation results are presented.
than Bus 2, and it is higher on Bus 13 than in Bus-10. Dominant VTHD of IEEE result, that is 8.02%, was
th
The 7 harmonics current on Bus-1 can be calculated as occurred in one bus that is the Bus-9. This work shows
follows: that the dominant VTHD were occurred on two buses, the
Bus-9 and Bus-10, there are is 10.61% and 10.63%
-3
I7(1) = (4.3)(10 )(83.67A) = 0.36 ampere. respectively. VTHD on ETAP result is 11.73% on Bus-9.
115 Afr. J. Physics
start
0.00192
j0.07168h
(power flow study)
input data on Table 3,4, and 3 1
0.006395 0.00123
5 into ETAP Powerstation,
i.e: Figure 7 0.00122 30.2368 T2 j0.37796h j0.00296h
4 2
j0.00243h 0.00313
9.31683
change all of the system 2.48403
data become per unit system j8.26962h 4.2592 T1 j0.05324h
j2.21788h
(p.u) in m-file of Matlab
5
n+1
results of frequency scan show the resonance occurrence
calculate the harmonic voltage, between harmonics 25 and 30.
harmonics currents, VTHD, and
The characteristics of driving point impedance, that
ITHD in every bus (Figure 6 resulted through frequency scan in Figure 16, 17, 18, 19,
and Equation (12)) were same on the some buses, but it shows resonance in
Vbush h * Zh (n,9) * Ibush two buses, that is Bus 12 and 13.
For comparison between Figures 14 and 15, VTHD on
the Bus 9 and 10 are relatively high, but the ITHD is 2.8%
on Bus 9 and it is 0% on the Bus 10.
were every buses had No
calculated?
Conclusions
-5 -3
Magnitude Harmonics Voltages (Vh) Magnitud Harmonics Current (Ih)
3x 10 6 x 10
Vh Bus-1, Base=69 kV Ih Bus-1, Base=83.67A
Vh Bus-2, Base=69 kV
volt
Ih Bus-2, Base=83.67A
Ih (p.u) volt
2 4
V (p.u
h )
1
2
0 5 10 15 20 25 30 35 40
Harmonics Order 0 5 10 15 20 25 30 35 40
Magnitude Harmonics Voltages (Vh) Harmonics Order
0.08 Magnitud Harmonics Current (Ih)
Vh Bus-10, Base = 4.16kV 0.1
0.06 Vh Bus-13, Base = 2.4kV Ih Bus-10, Base = 1387.86A
Vh (p.u) volt
0.04
0.05
0.02
0 5 10 15 20 25 30 35 40
Harmonics Order
0 5 10 15 20 25 30 35 40
Harmonics Order
Figure 10. Harmonics voltage spectrum on Buses-1, 2, 10,
13.
Figure 12. Harmonics current spectrum on Buses -1, 2, 5,
3, 4, 6.
-4
Magnitude Harmonics Voltages (Vh)
4 x 10
Vh Bus-3, Base=13.8kV Magnitud Harmonics Current (Ih)
3 Vh Bus-5, Base=13.8kV
volt
0.1
Ih Bus-3, Bas e = 418.34A
h (p.u) volt
0 5 10 15 20 25 30 35 40
Harmonics Order 0 5 10 15 20 25 30 35 40
Magnitud Harmonics Voltages (Vh) Harmonics Order
0.08 Magnitud Harmonics Current (Ih)
Vh Bus-4, Bus 0.48 kV 0.1
Ih Bus-4, Base = 1202.13A
0.06 Vh Bus-9, Bus 0.48 kV
Vh (p.u) volt
0.02
0 5 10 15 20 25 30 35 40 0 5 10 15 20 25 30 35 40
Harmonics Order Harmonics Order
Figure 11. Harmonics voltage spectrum on Buses-7, 8, 11, 9, Figure 13. Harmonics current spectrum on Buses-7, 8, 9,
10, 12, 13. 10, 11, 12, 13.
117 Afr. J. Physics
10 4
3.5
8
3
Zh (p.u.)
6 2.5
2
4
1.5
2 1
0.5
0 0 2 4 6 8 10 12 14
Bus Number
0 0 5 10 15 20 25 30 35 40 45 50
Harmonic order
Figure 14. VTHD and ITHD on every bus.
Figure 17
Comparison of VTHD (%) Frequency Scan between Bus-9 to Bus-12 and Bus-9 to Bus-13
IEEE test 60
Z912
12 Z913
ETAP 50
10
Matlab
8 40
6
Zh (p.u.)
30
4
2 20
0
1 2 3 4 5 6 7 8 9 10 11 12 13
10
Bus Number
0 0 5 10 15 20 25 30 35 40 45 50
Figure 15. Comparison of VTHD on every bus in IEEE test [Abu- Harmonic order
hashim et al., 1999], Matlab and the ETAP.
Figure 18
4
Zh (p.u.)
3
Zh (p.u.)
00 5 10 15 20 25 30 35 40 45 50
Harmonic order 0
0 5 10 15 20 25 30 35 40 45 50
Harmonic order
Figure 16 Figure 19
Sunaryati 118
FURTHER WORK
According to the exceeding of the limitation of VTHD as Product Data Bulletin, Power System Harmonics Causes
shown on IEEE Standard 519-1992, it is needed a and Effects of Variable Frequency Drives Relative to the
solution for reducing the VTHD. The active or passive IEEE 519-1992 Standard, Bulletin No. 8803PD9402,
filter or combination of them can be used in these August, 1994, Raleigh, NC, U.S.A.
purposes. Ranade SJ, Xu W. An Overview Of Harmonics Modeling
And Simulation, New Mexico State University Las
Cruces, NM, USA.
REFERENCES Reactive Power and Harmonic Compensation:
www.stacoenergy.com (29/04/2009)
Abu-hashim R, Burch R, Chang G, Grady M, Gunther E, Ribeiro PF. without year, “Distribution system and other
Halpin M, Hatziadoniu C, Liu Y, Marz M, Ortmeyer T, elements modeling”, BWX Technologies, Inc. Naval
Rajagopalan V, Ranade S, Ribeiro P (vice chair), Sims Nuclear Fuel Division, Lynchburg, VA.
T, Xu W (chair, editor) (1999). “Test Systems for Sankaran PE (1995). “Effects of Harmonics on Power
Harmonics Modeling and Simulation”, Task Force on Systems-Part1”, EC & M, Pp: 33-42.
Harmonics and Simulation, Transmission & Distribution Stavros A, Papathanassiou, Michael P, Papadopoulos,
Committee, IEEE Power Engineering Society, Pp. 579- Harmonic Analysis in a Power System with Wind
585. Generation, National Technical University of Athens
Arillaga L, Bradley DA, dan Bodger PS (1985). Power (NTUA), 9 Iroon Polytechnioust., 15780 Athens,
System Harmonics, John Wiley. Greece.
Dugan RC, Granaghan MF, Surya Santoso, Beaty HW Wagner VE, (Chairman), Balda JC, Barnes TM,
(2004). Electrical Power System Quality, McGraw Hill, Emannuel AE, Ferraro RJ, Griffith DC, Hartmann
Grainger JJ, dan Stevenson WD (1994). Power Systems DP,Horton WF, Jewell WT, McEachern A, Phileggi DJ,
Analysis, McGraw-Hill Book Inc, New York. dan Reid WE (1993). “Effects of Harmonics on
Gungor BR (1988). Power Systems, Harcourt Brace Equipment”, IEEE Transactions on Power Delivery, 8(2)
Jovanovich, Publishers, USA. 672 - 680.
http://ecmweb.com/mag/electric_effects_harmonics_pow Wardhani (1996). “Pengaruh Beban Industri pada Mutu
er_2/ : Effects of harmonics on power systems Tenaga listrik”, PT. PLN (Persero) Distribusi Jawa
(28/04/2009) Timur, Pp. 15 – 23.
IEEE Standard 519-1992, IEEE Recommended Practices
and Requirements for Harmonic Control in Electric
Power Systems.