PT PLN (PERSERO) Doc. No.

TRANSMISI JAWA BAGIAN TENGAH


Komplek PLN Cigereleng - Bandung Valid. JULI 2018
DAFTAR SETELAN RELE PROTEKSI GI 150 KV XXXX

1. Proteksi : Trafo #3 150/20 kV, 60 MVA, YNyn0 (d), 12.67%, NGR 12 Ω

JENIS TIPE SETELAN YANG EVALUASI PLN TJBT


RELAI RELAI DIUSULKAN ( nilai sekunder )
( nilai sekunder )
Differential SIFANG CT150 = 300/1 A; CT20 = 2000/5 A
Relay + REF CSC-326
HV dan LV HV PARAMETER
Internally Auto Trans 0 Control Word
Two-Wind Trans 0 Control Word
CT Fail Detect 1 Control Word
HV Wind Conn/Y-0 D-1 0
MV Wind Conn/Y-0 D-1 0
LV Wind Conn/Y-0 D-1 1
Vet Grp Angle 1
SN 60.0 MVA
HV UN 150.0 kV
HV VT Ratio 1500.0
HV CT Pri 300.0 A
HV CT Sec 1.0 A
HV Voltage Chan Sel 1
MV Voltage Chan Sel 2
HV NCT PARAMETER
HV NCT Pri(REF) 300.0 A
HV NCT Sec(REF) 1.0 A
HV NCT Pri(BU) 300.0 A
HV NCT Sec(BU) 1.0 A
MV PARAMETER
MV UN 20.0 kV
MV VT Ratio 200.0
MV CT Pri 2000.0 A
MV CT Sec 5.0 A
MV NCT PARAMETER
MV NCT Pri(REF) 2000.0 A
MV NCT Sec(REF) 5.0 A
MV NCT Pri(BU) 2000.0 A
MV NCT Sec(BU) 5.0 A
LV PARAMETER
LV UN 20.0 kV
LV VT Ratio 200.0
LV CT Pri 2000.0 A
LV CT Sec 5.0 A
LV Sec Inside Delta 5.0 A
DIFFERENTIAL PROTECTION
Func_Inst Diff 1 Control Word

1/2 Daftar Evaluasi Setelan Rele Proteksi Dibuat : Diperiksa : Disetujui :


Rev. 00 GI 150 kV XXX Tgl : Tgl: Tgl:

RUANG LINGKUP SERTIFIKASI ISO 9001:2000


PENGEMBANGAN DAN PEMBINAAN INSTALASI PENYALURAN TENAGA LISTRIK
SISTEM JAWA BALI DI PT PLN (PERSERO) TRANSMISI JAWA BAGIAN TENGAH
PT PLN (PERSERO) Doc. No.
TRANSMISI JAWA BAGIAN TENGAH
Komplek PLN Cigereleng - Bandung Valid. JULI 2018
DAFTAR SETELAN RELE PROTEKSI GI 150 KV XXXX

Func_Percent Diff 1 Control Word


Block Diff at Inrush 1 Control Word
2nd Harm Not Wave 0 Control Word
Block Diff at Overexcit 1 Control Word
Overexcit 3rd NOT 5th 0 Control Word
Func_Diff Alarm 0 Control Word
Block Diff at CT_Fail 0 Control Word
HV D_side Eliminate I0 0 Control Word
MV D_side Eliminate I0 0 Control Word
LV D_side Eliminate I0 1 Control Word
Diff Includes LV Cur 0 Control Word
I_Inst Diff 6.16 A
I_Percent Diff 0.231 A
I_ResPoint1 Diff 0.77 A
I_ResPoint2 Diff 3.08 A
Slope1_Diff 0.0
Slope2_Diff 0.3
Slope3_Diff 0.8
Ratio_2nd Harm 0.15
Ratio_3/5th Harm 0.3
T_2nd Harm Block 20.0 s
T_3/5th Harm Block 20.0 s
HV REF PROTECTION
HV Func_REF Trip 1 Control Word
HV Func_REF Alarm 0 Control Word
Block HV REF at HV
1 Control Word
CT_Fail
HV 3I0_REF 0.154 A
HV Slope_REF 0.5
HV T_REF Trip 0.0 s
HV 3I0_REF Alarm 10.0 A
HV T_REF Alarm 5.0 s
MV REF PROTECTION
MV Func_REF Trip 1 Control Word
MV Func_REF Alarm 0 Control Word
Block MV REF at MV
1 Control Word
CT_Fail
MV 3I0_REF 0.866 A
MV Slope_REF 0.5
MV T_REF Trip 0.0 s
MV 3I0_REF Alarm 10.0 A
MV T_REF Alarm 0.05 s

2/2 Daftar Evaluasi Setelan Rele Proteksi Dibuat : Diperiksa : Disetujui :


Rev. 00 GI 150 kV XXX Tgl : Tgl: Tgl: