You are on page 1of 22

Generator set data sheet

Model: C450D5
Frequency: 50 Hz
Fuel type: Diesel

Spec sheet: SS11-CPGK


Noise data sheet (open): ND50-OS550/ND50-CS550
Airflow data sheet: AF50-550
Derate data sheet (open): DD50-OS550/DD50-CS550
Transient data sheet: TD50-550

Fuel consumption Standby Prime


kVA (kW) kVA (kW)
Ratings 450(360) 410 (328)
Load 1/4 1/2 3/4 Full 1/4 1/2 3/4 Full
US gph 6.3 11.9 17.7 24.2 5.7 10.8 15.9 21.5
L/hr 23.8 45 66.9 92 22 41 60 82

Standby Prime
Engine rating rating
Engine manufacturer Cummins
Engine model QSG12-G2
Configuration Cast iron, 6 cylinder
Aspiration Turbocharged and after cooled
Gross engine power output, kWm 409 371
BMEP at set rated load, kPa 2772 2517
Bore, mm 132
Stroke, mm 144
Rated speed, rpm 1500
Piston speed, m/s 7.2
Compression ratio 17:1
Lube oil capacity, L 34.1
Overspeed limit, rpm 1725
Regenerative power, kW 56
Governor type Electronic
Starting voltage 24V Volts DC

Fuel flow
Maximum fuel flow, L/hr 182
Maximum fuel inlet restriction, mm Hg (clean filter) 304.8
Maximum fuel inlet temperature, °C 71

Standby Prime
Air rating rating
Combustion air, L/sec 424 387
Maximum air cleaner restriction, kPa 6.2(Dirty HD AC)

Exhaust
Exhaust gas flow at set rated load, L/sec 1029 936
Exhaust gas temperature, °C 524 507
Maximum exhaust back pressure, kPa 10.2

Our energy working for you. TM

power.cummins.com
©2018 Cummins Power Generation Inc. D-6339-EN (06/18)
Standard set-mounted radiator cooling
Ambient design, °C 50
Fan load, kWm 14.08
Coolant capacity (with radiator), L 48
Cooling system air flow, m3/sec @ 12.7 mmH2O 7.15
Total heat rejection, kW 214 191
Maximum cooling air flow static restriction kPa 0.125

Weights* Open Enclosed


Unit dry weight kgs 3415 4685
Unit wet weight kgs 4066 5335

* Weights represent a set with standard features. See outline drawing for weights of other configurations.

Dimensions Length Width Height


Standard open set dimensions mm 3376 1500 2103
Enclosed set standard dimensions mm 5093 1564 2375

Genset outline
Open set

Enclosed set

Outlines are for illustrative purposes only. Please refer to the genset outline drawing for an exact representation of this model.

Alternator data
Connection Temp rise ºC Duty Alternator Voltage
Wye, 3-phase 163/125 C S/P HC5C 380-415V

Our energy working for you. TM

power.cummins.com
©2018 Cummins Power Generation Inc. D-6339-EN (06/18)
Ratings definitions
Emergency standby Limited-time running Base load (continuous)
Prime power (PRP):
power (ESP): power (LTP): power (COP):

Applicable for supplying power Applicable for supplying power Applicable for supplying power Applicable for supplying power
to varying electrical load for to a constant electrical load for to varying electrical load for continuously to a constant
the duration of power limited hours. Limited Time unlimited hours. Prime Power electrical load for unlimited
interruption of a reliable utility Running Power (LTP) is in (PRP) is in accordance with hours. Continuous Power
source. Emergency Standby accordance with ISO 8528. ISO 8528. Ten percent (COP) is in accordance with
Power (ESP) is in accordance overload capability is available ISO 8528, ISO 3046,
with ISO 8528. Fuel Stop in accordance with ISO 3046, AS 2789, DIN 6271 and
power in accordance with ISO AS 2789, DIN 6271 and BS 5514.
3046, AS 2789, DIN 6271 and BS 5514.
BS 5514.

Formulas for calculating full load currents:

Three phase output Single phase output

kW x 1000 kW x Single Phase Factor x 1000


Voltage x 1.73 x 0.8 Voltage

See your distributor for more information.


Cummins Power Generation China
No. 118, South Quanli Road
Wuhan Economic & Technological Development Zone,
Hubei, China (430058)
Tel: 86(27) 8421 4800
Fax: 86(27) 8421 4804
Email: EastAsia.cumminsPower@cummins.com
Web: power.cummins.com

Our energy working for you.™


©2017 Cummins Power Generation Inc. All rights reserved.
Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. PowerCommand, AmpSentry, InPower
and “Our energy working for you.” are trademarks of Cummins Power Generation. Other company, product, or service names
may be trademarks or service marks of others. Specifications are subject to change without notice.
D-6339-EN (06/18)
power.cummins.com
Specification sheet

Diesel
generator set
QSG12 series
engine
400 kVA - 450 kVA 50 Hz
320 kW - 400 kW 60 Hz
Description
This Cummins® Power Generation Cooling system - Standard integral set-mounted
commercial generator set is a fully integrated radiator system, designed and tested for rated
power generation system, providing optimum ambient temperatures, simplifies facility design
performance, reliability, and versatility for requirements for rejected heat.
stationary standby and prime power. Control system – The PowerCommand®
electronic control is standard equipment and
Features provides total genset system integration, including
Cummins® heavy-duty engine - Rugged 4- auto remote start/stop, precise frequency and
cycle industrial diesel delivers reliable voltage regulation, alarm and status message
power, low emissions and fast response to display, AmpSentry protection and output
load changes. metering.
Optional permanent magnet generator Enclosures - Optional weather-protective and
(PMG) - Offers enhanced motor starting sound-attenuated enclosures.
and fault clearing short circuit capability.
Warranty and service - Backed by a
Alternator - Low reactance 2/3 pitch comprehensive warranty and worldwide distributor
windings; low waveform distortion with non- network.
linear loads, fault clearing short-circuits
capability, and class H insulation.

50HZ
Genset Standby rating Prime rating Engine Alternators Genset
Model model model controller
50 Hz/kVA 50 Hz/kWe 50 Hz/kVA 50 Hz/kWe

C400D5 400 320 360 288 QSG12-G1 HC4F PC2.2/PC3.3


C450D5 450 360 410 328 QSG12-G2 HC5C PC2.2/PC3.3

60HZ

Genset Standby rating Prime rating Engine Alternators Genset


Model model model controller
60 Hz/kVA 60 Hz/kWe 60 Hz/kVA 60 Hz/kWe

C350D6 438 350 400 320 QSG12-G1 HC4F PC2.2/PC3.3


C400D6 500 400 456 365 QSG12-G2 HC5C PC2.2/PC3.3

power.cummins.com
©2018 Cummins Inc. | S-6337-EN (06/18)
Generator set specifications
Governor regulation class ISO 8528
Voltage regulation, no load to full load ± 1%
Random voltage variation ± 1%
Frequency regulation Isochronous
Random frequency variation ± 0.25%
Radio frequency emissions compliance BS EN 61000-6-2:2005 / BS EN 61000-6-3:2007 +A1:2001

Engine specifications
Design 4 cycle, in-line, turbo-charged and charge air cooled
Bore 132 mm (5.2 in)
Stroke 144 mm (5.67 in)
Displacement 11.8 liter (721 in3)
Cylinder block Cast iron, 6 cylinder
Battery capacity 100AH
Battery charging alternator OUTPUT: 28V 110 Amps
Starting voltage 24 volt, negative ground
Fuel system XPI
Fuel filter Spin on fuel filters with water separator
Air cleaner type Dry replaceable element with restriction indicator
Lube oil filter type(s) Spin on full flow filter
Standard cooling system 122 ºF (50 ºC) ambient radiator

Alternator specifications
Design Brushless, single bearing, revolving field
Stator 2/3 pitch
Rotor Single bearing, flexible disc
Insulation system Class H
Standard temperature rise Standby 125-163 ºC
Exciter type Self excited (PMG optional)
Phase rotation A (U), B (V), C (W)
Alternator cooling Direct drive centrifugal blower fan
AC waveform total harmonic distortion (THDV) No load <1.5%. Non distorting balanced linear load <5%
Telephone influence factor (TIF) < 50% per NEMA MG1
Telephone harmonic factor (THF) <2%

Available voltages
50 Hz line – neutral / line - line 60 Hz line – neutral / line - line
 127/220  220/380  120/208  220/380
 230/400  127/220  230/400
 240/416  240/416
 255/440
 277/480

Generator set options


Engine Circuit breaker Control panel Silencer
 Heavy duty air cleaner  3 or 4 pole main circuit  PowerCommand 3.3  9 dB attenuation critical
 Water jacket heater 240 V breaker  PowerCommand 3.3 MLD silencer
 Motorised 3 or 4 pole  AC output bargraph  25 dB attenuation
Enclosure circuit breaker  Shutdown audible alarm residential silencer
 Sound attenuated canopy  Aux contacts and trip alarm  Earth fault shutdown
 Shunt trip – 24 VDC Battery charger
 Control cabinet heater
Alternator  Set mounted
 Alternator heater Fuel Tank  Standalone
Warranty
  Low fuel level warning or  5 A or 10 A
Exciter voltage regulator  2 years for prime
(PMG) shutdown application
 High alternator temp  High fuel level warning  5 years for standby
shutdown  Electric fuel transfer pump application
 10 years for major
components

*Note: Some options may not be available on all models - consult factory for availability.

power.cummins.com
©2018 Cummins Inc. | S-6337-EN (06/18)
PowerCommand 2.2 control system Digital voltage regulation
 Integrated digital electronic voltage regulator.
The PowerCommand control  3-phase, 4-wire line-to-line sensing.
system is an integrated  Configurable torque matching.
microprocessor based AmpSentry AC protection
generator set control system  AmpSentry protective relay.
providing voltage regulation,  Over current and short circuit shutdown.
engine protection, alternator  Over current warning.
protection, operator interface  Single and three phase fault regulation.
and isochronous governing.  Over and under voltage shutdown.
Refer to document S-1568 for more detailed information  Over and under frequency shutdown.
 Overload warning with alarm contact.
on the control.
 Reverse power and reverse var shutdown.
Major features  Field overload.
 AmpSentry – Includes integral AmpSentry protection Engine protection
which provides a full range of alternator protection  Battery voltage monitoring, protection and testing.
functions that are matched to the alternator provided.  Overspeed shutdown.
 Power management – Control function provides battery  Low oil pressure warning and shutdown.
monitoring and testing features and smart starting  High/low coolant temperature warning or shutdown.
 Low coolant level warning or shutdown.
control system.
 Fail to start (over crank) shutdown.
 Advanced control methodology – Three phase sensing,  Fail to crank shutdown.
full wave rectified voltage regulation, with a PWM output  Cranking lockout.
for stable operation with all load types.  Sensor failure indication.
 Communications interface – Control comes standard  Low fuel level warning or shutdown (optional).
with PCC Net and Modbus interface.  Fuel-in-rupture-basin warning or shutdown (optional).
 Regulation compliant – Prototype tested: CE, UL and  Full authority electronic engine protection.
CSA compliant. Control functions
 Service – InPowerTM PC-based service tool available for  Time delay start and cool down.
detailed diagnostics, setup, data logging and fault  Real time clock for fault and event time stamping.
simulation.  Exerciser clock and time of day start/stop.
 Easily upgradeable – PowerCommand controls are  Data logging.
designed with common control interfaces.  Cycle cranking.
 Load shed.
 Reliable design – The control system is designed for  Configurable inputs and outputs (4).
reliable operation in harsh environment.  Remote emergency stop.
 Multi-language support.
PowerCommand 3.3 control system (MLD)
Operator panel features
The PowerCommand 3.3
 128 x 128 pixels graphic LED backlight LCD.
has the following additional
 Auto, manual, start, stop, fault reset and lamp test/panel
features and benefits over
lamp switches.
the PowerCommand 2.2.
 Alpha-numeric display with pushbuttons.
 LED lamps indicating genset running, remote start, not in Refer to document S-1570
auto, common shutdown, common warning, manual run for more detailed information
mode, auto mode and stop mode. on the control.

Alternator data Operator panel features


 Line-to-neutral and line-to-line AC volts.  320 x 240 pixels graphic LED backlight LCD.
 3-phase AC current.  In addition to the 2.2 functions, the operator panel
 Frequency. displays paralleling breaker status and provides for direct
 kW, kVar, power factor kVA (three phase and total). control of the paralleling breaker.
Paralleling control functions
Engine data
 DC voltage.  First Start Sensor System selects first genset to close to
 Engine speed. bus.
 Lube oil pressure and temperature.  Phase Lock Loop Synchronizer with voltage matching.
 Coolant temperature.  Sync check relay.
 Comprehensive FAE data (where applicable).  Isochronous kW and kVar load sharing.
Other data  Load govern control for utility paralleling.
 Genset model data.  Extended Paralleling (baseload/peak shave) Mode.
 Start attempts, starts, running hours, kW hours.  Digital power transfer control, for use with a breaker pair
 Load profile (operating hours at % load in 5% to provide open transition, closed transition, ramping
increments). closed transition, peaking and base load functions.
 Fault history.
 Data logging and fault simulation (requires InPower). Master less Load Demand (MLD)
 Load dependant start/stop of multi-gen system
Standard control functions  Predictive load input
 Run hour equalization
Digital governing
 Integrated digital electronic isochronous governor.
 Temperature dynamic governing.

power.cummins.com
©2018 Cummins Inc. | S-6337-EN (06/18)
Ratings definitions
Emergency Standby Power (ESP): Open
Applicable for supplying power to varying electrical load for
the duration of power interruption of a reliable utility
source. Emergency Standby Power (ESP) is in accordance
with ISO 8528. Fuel Stop power in accordance with ISO
3046, AS 2789, DIN 6271 and BS 5514.
Limited-Time Running Power (LTP):
Applicable for supplying power to a constant electrical load
for limited hours. Limited Time Running Power (LTP) is in
accordance with ISO 8528.
Enclosed
Prime Power (PRP):
Applicable for supplying power to varying electrical load for
unlimited hours. Prime Power (PRP) is in accordance with
ISO 8528. Ten percent overload capability is available in
accordance with ISO 3046, AS 2789, DIN 6271 and BS
5514.
Base load (continuous) power (COP):
Applicable for supplying power continuously to a constant
electrical load for unlimited hours. Continuous Power This outline drawing is to provide representative
(COP) in accordance with ISO 8528, ISO 3046, AS 2789, configuration details for Model series only.
DIN 6271 and BS 5514.
See respective model data sheet for specific model outline
drawing number.

Do not use for installation design

Weight and dimensions


Open Enclosed
A B C Dry wt.* Wet wt.* A B C Dry wt.* Wet wt.*
Model mm mm mm kg kg mm mm mm kg kg
C400D5 3376 1500 2103 3285 3936 5093 1564 2375 4555 5205
C450D5 3376 1500 2103 3415 4066 5093 1564 2375 4685 5335
C350D6 3376 1500 2103 3285 3936 5093 1564 2375 4555 5205
C400D6 3376 1500 2103 3415 4066 5093 1564 2375 4685 5335
* Note: Weights represent a set with standard features. See outline drawings for weights of other configurations.

Certifications
This generator set is designed in facilities
Emissions
certified to ISO 9001 and manufactured in Non-Certified
facilities certified to ISO 9001 or ISO 9002. compliance

This generator set is available with CE This generator set has been designed to
certification.
ISO 8528 comply with ISO 8528 regulation.

For more information contact your local Cummins


distributor or visit power.cummins.com

©2017 Cummins Inc. All rights reserved. Cummins is a registered trademark of Cummins Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks
of Cummins Inc. Other company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
S-6637-EN (06/18)
HCI 534C/544C - Technical Data Sheet
HCI534C/544C
SPECIFICATIONS & OPTIONS

STANDARDS WINDINGS & ELECTRICAL PERFORMANCE


Newage Stamford industrial generators meet the All generator stators are wound to 2/3 pitch. This
requirements of BS EN 60034 and the relevant section of eliminates triplen (3rd, 9th, 15th …) harmonics on the
other international standards such as BS5000, VDE 0530, voltage waveform and is found to be the optimum design
NEMA MG1-32, IEC34, CSA C22.2-100, AS1359. for trouble-free supply of non-linear loads. The 2/3 pitch
Other standards and certifications can be considered on design avoids excessive neutral currents sometimes seen
request. with higher winding pitches, when in parallel with the
mains. A fully connected damper winding reduces
VOLTAGE REGULATORS oscillations during paralleling. This winding, with the 2/3
pitch and carefully selected pole and tooth designs,
AS440 AVR - STANDARD ensures very low waveform distortion.
With this self-excited system the main stator provides
power via the Automatic Voltage Regulator (AVR) to the TERMINALS & TERMINAL BOX
exciter stator. The high efficiency semi-conductors of the Standard generators are 3-phase reconnectable with 12
AVR ensure positive build-up from initial low levels of ends brought out to the terminals, which are mounted on
residual voltage. a cover at the non-drive end of the generator. A sheet
The exciter rotor output is fed to the main rotor through a steel terminal box contains the AVR and provides ample
three-phase full-wave bridge rectifier. The rectifier is space for the customers' wiring and gland arrangements.
protected by a surge suppressor against surges caused, It has removable panels for easy access.
for example, by short circuit or out-of-phase paralleling.
The AS440 will support a range of electronic accessories, SHAFT & KEYS
including a 'droop' Current Transformer (CT) to permit All generator rotors are dynamically balanced to better
parallel operation with other ac generators. than BS6861:Part 1 Grade 2.5 for minimum vibration in
operation. Two bearing generators are balanced with a
MX341 AVR half key.
This sophisticated AVR is incorporated into the Stamford
Permanent Magnet Generator (PMG) control system. INSULATION/IMPREGNATION
The PMG provides power via the AVR to the main exciter, The insulation system is class 'H'.
giving a source of constant excitation power independent All wound components are impregnated with materials
of generator output. The main exciter output is then fed to and processes designed specifically to provide the high
the main rotor, through a full wave bridge, protected by a build required for static windings and the high mechanical
surge suppressor. The AVR has in-built protection strength required for rotating components.
against sustained over-excitation, caused by internal or
external faults. This de-excites the machine after a QUALITY ASSURANCE
minimum of 5 seconds. Generators are manufactured using production
An engine relief load acceptance feature can enable full procedures having a quality assurance level to BS EN
load to be applied to the generator in a single step. ISO 9001.
If three-phase sensing is required with the PMG system
the MX321 AVR must be used. The stated voltage regulation may not be maintained in
We recommend three-phase sensing for applications with the presence of certain radio transmitted signals. Any
greatly unbalanced or highly non-linear loads. change in performance will fall within the limits of Criteria
'B' of EN 61000-6-2:2001. At no time will the steady-state
MX321 AVR voltage regulation exceed 2%.
The most sophisticated of all our AVRs combines all the
features of the MX341 with, additionally, three-phase rms
sensing, for improved regulation and performance.
Over voltage protection is built-in and short circuit current
level adjustments is an optional facility.
NB Continuous development of our products entitles us
to change specification details without notice, therefore
they must not be regarded as binding.

Front cover drawing typical of product range.

2
HCI534C/544C
WINDING 311
CONTROL SYSTEM SEPARATELY EXCITED BY P.M.G.
A.V.R. MX321 MX341
VOLTAGE REGULATION ± 0.5 % ± 1.0 % With 4% ENGINE GOVERNING
SUSTAINED SHORT CIRCUIT REFER TO SHORT CIRCUIT DECREMENT CURVES (page 7)

CONTROL SYSTEM SELF EXCITED


A.V.R. AS440
VOLTAGE REGULATION ± 1.0 % With 4% ENGINE GOVERNING
SUSTAINED SHORT CIRCUIT SERIES 4 CONTROL DOES NOT SUSTAIN A SHORT CIRCUIT CURRENT

INSULATION SYSTEM CLASS H


PROTECTION IP23
RATED POWER FACTOR 0.8
STATOR WINDING DOUBLE LAYER LAP
WINDING PITCH TWO THIRDS
WINDING LEADS 12
STATOR WDG. RESISTANCE 0.0065 Ohms PER PHASE AT 22°C SERIES STAR CONNECTED
ROTOR WDG. RESISTANCE 1.55 Ohms at 22°C
EXCITER STATOR RESISTANCE 17 Ohms at 22°C
EXCITER ROTOR RESISTANCE 0.092 Ohms PER PHASE AT 22°C
R.F.I. SUPPRESSION BS EN 61000-6-2 & BS EN 61000-6-4,VDE 0875G, VDE 0875N. refer to factory for others
WAVEFORM DISTORTION NO LOAD < 1.5% NON-DISTORTING BALANCED LINEAR LOAD < 5.0%
MAXIMUM OVERSPEED 2250 Rev/Min
BEARING DRIVE END BALL. 6220 (ISO)
BEARING NON-DRIVE END BALL. 6314 (ISO)
1 BEARING 2 BEARING
WEIGHT COMP. GENERATOR 1263 kg 1275 kg
WEIGHT WOUND STATOR 584 kg 584 kg
WEIGHT WOUND ROTOR 502 kg 473 kg
WR² INERTIA 6.8928 kgm2 6.6149 kgm2
SHIPPING WEIGHTS in a crate 1355 kg 1395 kg
PACKING CRATE SIZE 166 x 87 x 124(cm) 166 x 87 x 124(cm)
50 Hz 60 Hz
TELEPHONE INTERFERENCE THF<2% TIF<50
COOLING AIR 1.035 m³/sec 2202 cfm 1.312 m³/sec 2780 cfm
VOLTAGE SERIES STAR 380/220 400/231 415/240 440/254 416/240 440/254 460/266 480/277
VOLTAGE PARALLEL STAR 190/110 200/115 208/120 220/127 208/120 220/127 230/133 240/138
VOLTAGE SERIES DELTA 220/110 230/115 240/120 254/127 240/120 254/127 266/133 277/138
kVA BASE RATING FOR REACTANCE
455 500 455 450 525 550 581 594
VALUES
Xd DIR. AXIS SYNCHRONOUS 3.30 3.28 2.77 2.44 3.94 3.69 3.57 3.35
X'd DIR. AXIS TRANSIENT 0.18 0.18 0.15 0.13 0.18 0.17 0.16 0.15
X''d DIR. AXIS SUBTRANSIENT 0.13 0.13 0.11 0.10 0.13 0.12 0.12 0.11
Xq QUAD. AXIS REACTANCE 2.69 2.67 2.25 1.98 3.12 2.92 2.82 2.65
X''q QUAD. AXIS SUBTRANSIENT 0.27 0.26 0.22 0.20 0.34 0.32 0.31 0.29
XL LEAKAGE REACTANCE 0.07 0.07 0.06 0.05 0.08 0.07 0.07 0.07
X2 NEGATIVE SEQUENCE 0.19 0.19 0.16 0.14 0.23 0.22 0.21 0.20
X0 ZERO SEQUENCE 0.11 0.11 0.09 0.08 0.11 0.10 0.10 0.09
REACTANCES ARE SATURATED VALUES ARE PER UNIT AT RATING AND VOLTAGE INDICATED
T'd TRANSIENT TIME CONST. 0.08s
T''d SUB-TRANSTIME CONST. 0.012s
T'do O.C. FIELD TIME CONST. 2s
Ta ARMATURE TIME CONST. 0.017s
SHORT CIRCUIT RATIO 1/Xd

3
50 HCI534C/544C
Winding 311
Hz THREE PHASE EFFICIENCY CURVES

4
60 HCI534C/544C
Winding 311
Hz THREE PHASE EFFICIENCY CURVES

5
HCI534C/544C
Winding 311

Locked Rotor Motor Starting Curve

50
Hz
MX SX
346V 380V 400V 415V 440V 346V 380V 400V 415V 440V
30 30

25 25

20 20
P E R C E N T T R A N S IE N T V O L T A G E D IP .

P E R C E N T T R A N S IE N T V O L T A G E D IP .
15 15

10 10

5 5

0 0
0 200 400 600 800 1000 1200 1400 1600 0 200 400 600 800 1000 1200
LOCKED ROTOR kVA LOCKED ROTOR kVA

60
Hz
MX SX
380V 416V 440V 460V 480V 380V 416V 440V 460V 480V
30 30

25 25

20 20
P E R C E N T T R A N S IE N T V O L T A G E D IP .

P E R C E N T T R A N S IE N T V O L T A G E D IP .

15 15

10 10

5 5

0 0
0 200 400 600 800 1000 1200 1400 1600 0 200 400 600 800 1000 1200 1400
LOCKED ROTOR kVA LOCKED ROTOR kVA

6
HCI534C/544C

Three-phase Short Circuit Decrement Curve. No-load Excitation at Rated Speed


Based on star (wye) connection.
50 100000

Hz
SYMMETRICAL

ASYMMETRICAL
10000
CURRENT (Amps)

1000

100
0.001 0.01 0.1 1 10
TIME (secs)

Sustained Short Circuit = 2,050 Amps

60 100000

Hz SYMMETRICAL

ASYMMETRICAL

10000
CURRENT (Amps)

1000

100
0.001 0.01 0.1 1 10
TIME (secs)

Sustained Short Circuit = 2,350 Amps


Note 1 Note 2
The following multiplication factors should be The following multiplication factor should be used to convert the
used to adjust the values from curve between values calculated in accordance with NOTE 1 to those applicable to
time 0.001 seconds and the minimum current the various types of short circuit :
point in respect of nominal operating voltage :
50Hz 60Hz 3-phase 2-phase L-L 1-phase L-N
Voltage Factor Voltage Factor Instantaneous x 1.00 x 0.87 x 1.30
380v X 1.00 416v X 1.00 Minimum x 1.00 x 1.80 x 3.20
400v X 1.03 440v X 1.06 Sustained x 1.00 x 1.50 x 2.50
415v X 1.05 460v X 1.12 Max. sustained duration 10 sec. 5 sec. 2 sec.
440v X 1.07 480v X 1.20 All other times are unchanged
The sustained current value is constant irrespective of
voltage level
Note 3
Curves are drawn for Star (Wye) connected machines. For other
connections the following multipliers should be applied to current
values as shown :
Parallel Star = Curve current value X 2
Series Delta = Curve current value X 1.732
7
HCI534C/544C
Winding 311 0.8 Power Factor

RATINGS
Class - Temp Rise Cont. F - 105/40°C Cont. H - 125/40°C Standby - 150/40°C Standby - 163/27°C

Series Star (V) 380 400 415 440 380 400 415 440 380 400 415 440 380 400 415 440
50 Parallel Star (V) 190 200 208 220 190 200 208 220 190 200 208 220 190 200 208 220
Hz
Series Delta (V) 220 230 240 254 220 230 240 254 220 230 240 254 220 230 240 254

kVA 400 445 400 400 455 500 455 450 478 512 478 478 500 520 500 495

kW 320 356 320 320 364 400 364 360 382 410 382 382 400 416 400 396

Efficiency (%) 94.5 94.3 94.8 94.9 94.0 93.8 94.4 94.6 93.8 93.7 94.2 94.4 93.5 93.6 94.0 94.3

kW Input 339 378 338 337 387 426 386 381 408 437 406 405 428 444 425 420

Series Star (V) 416 440 460 480 416 440 460 480 416 440 460 480 416 440 460 480
60
Parallel Star (V) 208 220 230 240 208 220 230 240 208 220 230 240 208 220 230 240
Hz
Delta (V) 240 254 266 277 240 254 266 277 240 254 266 277 240 254 266 277

kVA 481 500 531 538 525 550 581 594 550 581 613 625 569 600 631 644

kW 385 400 425 430 420 440 465 475 440 465 490 500 455 480 505 515

Efficiency (%) 94.3 94.4 94.4 94.5 94.0 94.1 94.1 94.2 93.8 93.9 93.9 94.0 93.6 93.7 93.7 93.9

kW Input 408 424 450 455 447 468 494 504 469 495 522 532 486 512 539 549

DIMENSIONS

Barnack Road • Stamford • Lincolnshire • PE9 2NB


Tel: 00 44 (0)1780 484000 • Fax: 00 44 (0)1780 484100

© 2007 TD_HCI5C.GB_08.07_04_GB
PowerCommand®
2.2 control system

Control system description Features


• 128 x 128 pixels graphic LED backlight LCD.
®
The PowerCommand control system is a
microprocessor-based generator set monitoring, • Multiple language support.
metering and control system designed to meet the
• AmpSentry™ Protective Relay - True alternator
demands of today’s engine driven generator sets. The
overcurrent protection.
integration of all control functions into a single control
system provides enhanced reliability and performance, • Real time clock for fault and event time stamping.
compared to conventional generator set control systems. • Exerciser clock and time of day start/stop.
These control systems have been designed and tested to • Digital voltage regulation. Three phase full wave FET
meet the harsh environment in which gensets are type regulator compatible with either shunt or PMG
typically applied. systems.
• Generator set monitoring and protection.
• 12 and 24 VDC battery operation.

®
Modbus interface for interconnecting to customer
equipment.
• Warranty and service. Backed by a comprehensive
warranty and worldwide distributor service network.
• Certifications - Suitable for use on generator sets that
are designed, manufactured, tested and certified to
relevant UL, NFPA, ISO, IEC, Mil Std., CE and CSA
standards.

©2010 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins
Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of Cummins Power Generation. Other company,
product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
S-1568c (5/10) Page 1 of 7
• Real time clock for fault and event time stamping.
PowerCommand digital • Exerciser clock and time of day start/stop.
generator set control • Advanced serviceability - using InPower™, a PC-
based software service tool.
PCC 2300 • Environmental protection - The control system is
designed for reliable operation in harsh environments.
The main control board is a fully encapsulated module
that is protected from the elements.
• Modbus interface for interconnecting to customer
equipment.
• Configurable inputs and outputs - Four discrete inputs
and four dry contact relay outputs.
• Warranty and service - Backed by a comprehensive
warranty and worldwide distributor service network.
• Certifications - Suitable for use on generator sets that
Description are designed, manufactured, tested and certified to
relevant UL, NFPA, ISO, IEC, Mil Std., CE and CSA
The PowerCommand generator set control is suitable for standards.
use on a wide range of generator sets in non-paralleling
applications. The PowerCommand control is compatible Base control functions
with shunt or PMG excitation style. It is suitable for use
with reconnectable or non-reconnectable generators, and HMI capability
it can be configured for any frequency, voltage and power Operator adjustments - The HMI includes provisions for
connection from 120-600 VAC line-to-line. many set up and adjustment functions.
Power for this control system is derived from the Generator set hardware data - Access to the control and
generator set starting batteries. The control functions software part number, generator set rating in KVA and
over a voltage range from 8 VDC to 30 VDC. generator set model number is provided from the HMI or
InPower.
Features Data logs - Includes engine run time, controller on time,
number of start attempts, total kilowatt hours, and load
• 12 and 24 VDC battery operation. profile. (Control logs data indicating the operating hours
• Digital voltage regulation - Three phase full wave FET at percent of rated kW load, in 5% increments. The data
type regulator compatible with either shunt or PMG is presented on the operation panel based on total
systems. Sensing is three phase. operating hours on the generator.)
• Full authority engine communications (where Fault history - Provides a record of the most recent fault
applicable) - Provides communication and control with conditions with control date and time stamp. Up to 32
the Engine Control Module (ECM). events are stored in the control non-volatile memory.
• AmpSentry protection - for true alternator overcurrent Alternator data
protection.
- Voltage (single or three phase line-to-line and line-to-
• Common harnessing - with higher feature Cummins
neutral)
Power Generation controls. Allows for easy field
- Current (single or three phase)
upgrades. - kW, KVAR, power factor, KVA (three phase and total)
• Generator set monitoring - Monitors status of all critical - Frequency
engine and alternator functions.
Engine data
• Digital genset metering (AC and DC).
• Genset battery monitoring system to sense and warn - Starting battery voltage
against a weak battery condition. - Engine speed
• Configurable for single or three phase AC metering. - Engine temperature
• Engine starting - Includes relay drivers for starter, fuel - Engine oil pressure
shut off (FSO), glow plug/spark ignition power and - Engine oil temperature
- Intake manifold temperature
switch B+ applications.
- Comprehensive Full Authority Engine (FAE) data
• Generator set protection – Protects engine and
(where applicable)
alternator.

Our energy working for you.™


www.cumminspower.com
©2010 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins
Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of Cummins Power Generation. Other
company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
S-1568c (5/10) Page 2 of 7
Service adjustments - The HMI includes provisions for Cycle cranking - Is configurable for the number of
adjustment and calibration of generator set control starting cycles (1 to 7) and duration of crank and rest
functions. Adjustments are protected by a password. periods. Control includes starter protection algorithms
to prevent the operator from specifying a starting
Functions include:
sequence that might be damaging.
- Engine speed governor adjustments
- Voltage regulation adjustments Time delay start and stop (cooldown) - Configurable for
- Cycle cranking time delay of 0-300 seconds prior to starting after
- Configurable fault set up receiving a remote start signal and for time delay of 0-
- Configurable output set up 600 seconds prior to shut down after signal to stop in
- Meter calibration normal operation modes. Default for both time delay
- Display language and units of measurement periods is 0 seconds.
Engine control Alternator control
SAE-J1939 CAN interface to full authority ECMs (where The control includes an integrated three phase line-to-
applicable). Provides data swapping between genset and line sensing voltage regulation system that is compatible
engine controller for control, metering and diagnostics. with shunt or PMG excitation systems. The voltage
12 VDC/24 VDC battery operations - PowerCommand will regulation system is a three phase full wave rectified and
operate either on 12 VDC or 24 VDC batteries. has an FET output for good motor starting capability.
Major system features include:
Temperature dependent governing dynamics (with
Digital output voltage regulation - Capable of regulating
electronic governing) - modifies the engine governing
output voltage to within +/-1.0% for any loads between
control parameters as a function of engine temperature.
no load and full load. Voltage drift will not exceed +/-
This allows the engine to be more responsive when warm
1.5% for a 40 ºC (104 ºF) change in temperature in an
and more stable when operating at lower temperature
eight hour period. On engine starting or sudden load
levels.
acceptance, voltage is controlled to a maximum of 5%
Isochronous governing - (where applicable) Capable of overshoot over nominal level. The automatic voltage
controlling engine speed within +/-0.25% for any steady regulator feature can be disabled to allow the use of an
state load from no load to full load. Frequency drift will external voltage regulator.
not exceed +/-0.5% for a 33 °C (60 °F) change in ambient
Droop voltage regulation - Control can be adjusted to
temperature over an 8 hour period.
droop from 0-10% from no load to full load.
Droop electronic speed governing - Control can be
Torque-matched V/Hz overload control - The voltage
adjusted to droop from 0 to 10% from no load to full load.
roll-off set point and rate of decay (i.e. the slope of the
Remote start mode - It accepts a ground signal from V/Hz curve) is adjustable in the control.
remote devices to automatically start the generator set
Fault current regulation - PowerCommand will regulate
and immediately accelerate to rated speed and voltage.
the output current on any phase to a maximum of three
The remote start signal will also wake up the control from
times rated current under fault conditions for both single
sleep mode. The control can incorporate a time delay
phase and three phase faults. In conjunction with a
start and stop.
permanent magnet generator, it will provide three times
Remote and local emergency stop - The control accepts rated current on all phases for motor starting and short
a ground signal from a local (genset mounted) or remote circuit coordination purpose.
(facility mounted) emergency stop switch to cause the
generator set to immediately shut down. The generator
set is prevented from running or cranking with the switch Protective functions
engaged. If in sleep mode, activation of either On operation of a protective function the control will
emergency stop switch will wakeup the control. indicate a fault by illuminating the appropriate status LED
Sleep mode - The control includes a configurable low on the HMI, as well as display the fault code and fault
current draw state to minimize starting battery current description on the LCD. The nature of the fault and time
draw when the genset is not operating. The control can of occurrence are logged in the control. The service
also be configured to go into a low current state while in manual and InPower service tool provide service keys
auto for prime applications or applications without a and procedures based on the service codes provided.
battery charger. Protective functions include:

Engine starting - The control system supports automatic Battle short mode
engine starting. Primary and backup start disconnects When enabled and the battle short switch is active, the
are achieved by one of two methods: magnetic pickup or control will allow some shutdown faults to be bypassed.
main alternator output frequency. The control also If a bypassed shutdown fault occurs, the fault code and
supports configurable glow plug control when applicable.

Our energy working for you.™


www.cumminspower.com
©2010 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins
Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of Cummins Power Generation. Other
company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
S-1568c (5/10) Page 3 of 7
description will still be annunciated, but the genset will so that downstream protective devices have the
not shutdown. This will be followed by a fail to shutdown maximum current available to quickly clear fault
fault. Emergency stop shutdowns and others that are conditions without subjecting the alternator to potentially
critical for proper operation are not bypassed. Please catastrophic failure conditions. See document R1053 for
refer to the Control Application Guide or Manual for list of a full size time over current curve.
these faults.
Derate
The Derate function reduces output power of the genset
in response to a fault condition. If a derate command
occurs while operating on an isolated bus, the control will
issue commands to reduce the load on the genset via
contact closures or Modbus.
Configurable alarm and status inputs
The control accepts up to four alarm or status inputs
(configurable contact closed to ground or open) to
indicate a configurable (customer-specified) condition.
The control is programmable for warning, shutdown or
status indication and for labeling the input.

Emergency stop
Annunciated whenever either emergency stop signal is
received from external switch.
Full authority electronic engine protection
Engine fault detection is handled inside the engine ECM.
Fault information is communicated via the SAE-J1939
data link for annunciation in the HMI. High AC voltage shutdown (59) - Output voltage on any
phase exceeds preset values. Time to trip is inversely
General engine protection proportional to amount above threshold. Values
Low and high battery voltage warning - Indicates status adjustable from 105-125% of nominal voltage, with time
of battery charging system (failure) by continuously delay adjustable from 0.1-10 seconds. Default value is
monitoring battery voltage. 110% for 10 seconds.
Low AC voltage shutdown (27) - Voltage on any phase
Weak battery warning - The control system will test the has dropped below a preset value. Adjustable over a
battery each time the generator set is signaled to start range of 50-95% of reference voltage, time delay 2-20
and indicate a warning if the battery indicates impending seconds. Default value is 85% for 10 seconds. Function
failure. tracks reference voltage. Control does not nuisance trip
Fail to start (overcrank) shutdown - The control system when voltage varies due to the control directing voltage
will indicate a fault if the generator set fails to start by the to drop, such as during a V/Hz roll-off during
completion of the engine crack sequence. synchronizing.
Fail to crank shutdown - Control has signaled starter to Under frequency shutdown (81 u) - Generator set output
crank engine but engine does not rotate. frequency cannot be maintained. Settings are adjustable
from 2-10 Hz below reference governor set point, for a 5-
Cranking lockout - The control will not allow the starter to 20 second time delay. Default: 6 Hz, 10 seconds.
attempt to engage or to crank the engine when the Under frequency protection is disabled when excitation
engine is rotating. is switched off, such as when engine is operating in idle
speed mode.
Alternator protection
Over frequency shutdown/warning (81o) - Generator set
AmpSentry Protective relay - A comprehensive
is operating at a potentially damaging frequency level.
monitoring and control system integral to the
Settings are adjustable from 2-10 Hz above nominal
PowerCommand Control System that guards the
governor set point for a 1-20 second time delay. Default:
electrical integrity of the alternator and power system by
6 Hz, 20 seconds, disabled.
providing protection against a wide array of fault
conditions in the generator set or in the load. It also
provides single and three phase fault current regulation

Our energy working for you.™


www.cumminspower.com
©2010 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins
Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of Cummins Power Generation. Other
company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
S-1568c (5/10) Page 4 of 7
Overcurrent warning/shutdown - Thresholds and time shutdown fault as well as ready to load, not in auto,
delays are configurable. Implementation of the thermal common alarm, common warning and common
damage curve with instantaneous trip level calculated shutdown.
based on current transformer ratio and application power - Ready to load (generator set running) signal: Operates
rating. when the generator set has reached 90% of rated
speed and voltage and latches until generator set is
Loss of sensing voltage shutdown - Shutdown of
switched to off or idle mode.
generator set will occur on loss of voltage sensing inputs
Communications connections include:
to the control.
Field overload shutdown - Monitors field voltage to - PC tool interface: This RS-485 communication port
shutdown generator set when a field overload condition allows the control to communicate with a personal
occurs. computer running InPower software.
- Modbus RS-485 port: Allows the control to
Over load (kW) warning - Provides a warning indication communicate with external devices such as PLCs
when engine is operating at a load level over a set point. using Modbus protocol.
Adjustment range: 80-140% of application rated kW, 0-
120 second delay. Defaults: 105%, 60 seconds. Note - An RS-232 or USB to RS-485 converter is
required for communication between PC and control.
Reverse power shutdown (32) - Adjustment range:
5-20% of standby kW rating, delay 1-15 seconds. - Networking: This RS-485 communication port allows
Default: 10%, 3 seconds. connection from the control to the other Cummins
Power Generation products.
Reverse Var shutdown - Shutdown level is adjustable: 15-
50% of rated Var output, delay 10-60 seconds. Default:
20%, 10 seconds.
Mechanical drawings
Short circuit protection - Output current on any phase is
more than 175% of rating and approaching the thermal
damage point of the alternator. Control includes
algorithms to protect alternator from repeated over
current conditions over a short period of time.

Field control interface


Input signals to the PowerCommand control
include:
- Coolant level (where applicable)
- Fuel level (where applicable)
- Remote emergency stop
- Remote fault reset
- Remote start
- Battleshort
- Rupture basin
- Start type signal
- Configurable inputs - Control includes (4) input signals
from customer discrete devices that are configurable
for warning, shutdown or status indication, as well as
message displayed
Output signals from the PowerCommand control
include:
- Load dump signal: Operates when the generator set is
in an overload condition.
- Delayed off signal: Time delay based output which will
continue to remain active after the control has removed
the run command. Adjustment range: 0 - 120
seconds. Default: 0 seconds.
- Configurable relay outputs: Control includes (4) relay
output contacts (3 A, 30VDC). These outputs can be
configured to activate on any control warning or

Our energy working for you.™


www.cumminspower.com
©2010 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins
Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of Cummins Power Generation. Other
company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
S-1568c (5/10) Page 5 of 7
• Certifications: Suitable for use on generator sets that
PowerCommand human are designed, manufactured, tested and certified to
machine interface relevant UL, NFPA, ISO, IEC, Mil Std., CE and CSA
standards.
HMI220 LCD languages supported: English, Spanish, French,
German, Italian, Greek, Dutch, Portuguese, Finnish,
Norwegian, Danish, Russian and Chinese Characters.
Communications connections include:
- PC tool interface - This RS-485 communication port
allows the HMI to communicate with a personal
computer running InPower.
- This RS-485 communication port allows the HMI to
communicate with the main control board.

Description Mechanical drawing


This control system includes an intuitive operator
interface panel that allows for complete genset control as
well as system metering, fault annunciation, configuration
and diagnostics. The interface includes five generator set
status LED lamps with both internationally accepted
symbols and English text to comply with customers
needs. The interface also includes an LED backlit LCD
display with tactile feel soft-switches for easy operation
and screen navigation. It is configurable for units of
measurement and has adjustable screen contrast and
brightness.
The run/off/auto switch function is integrated into the
interface panel. Software
All data on the control can be viewed by scrolling through InPower (beyond 6.0 version) is a PC-based software
screens with the navigation keys. The control displays service tool that is designed to directly communicate to
the current active fault and a time-ordered history of the PowerCommand generator sets and transfer switches, to
five previous faults. facilitate service and monitoring of these products.

Features: Environment
• LED indicating lamps The control is designed for proper operation without
- genset running recalibration in ambient temperatures from -40 ºC to
- remote start +70º C (-40 ºF to 158 ºF) and for storage from -55 ºC to
- not in auto +80 ºC (-67 ºF to 176 ºF). Control will operate with
- shutdown humidity up to 95%, non-condensing.
- warning The HMI is designed for proper operation in ambient
- auto temperatures from -20 ºC to +70 ºC (-4 ºF to 158 ºF) and
- manual and stop for storage from -30 ºC to +80 ºC (-22 ºF to 176 ºF).
• 128 x 128 pixels graphic LED backlight LCD.
The control board is fully encapsulated to provide
• Two tactile feel membrane switches for LCD defined superior resistance to dust and moisture. Display panel
operation. The functions of these switches are defined has a single membrane surface, which is impervious to
dynamically on the LCD. effects of dust, moisture, oil and exhaust fumes. This
• Seven tactile feel membrane switches dedicated screen panel uses a sealed membrane to provide long reliable
navigation buttons for up, down, left, right, ok, home service life in harsh environments.
and cancel.
The control system is specifically designed and tested for
• Six tactile feel membrane switches dedicated to control resistance to RFI/EMI and to resist effects of vibration to
for auto, stop, manual, manual start, fault reset and provide a long reliable life when mounted on a generator
lamp test/panel lamps. set. The control includes transient voltage surge
• Two tactile feel membrane switches dedicated to suppression to provide compliance to referenced
control of circuit breaker (where applicable). standards.
• Allows for complete genset control setup.

Our energy working for you.™
www.cumminspower.com
©2010 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins
Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of Cummins Power Generation. Other
company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
S-1568c (5/10) Page 6 of 7
Certifications
PowerCommand meets or exceeds the requirements of
the following codes and standards:
- NFPA 110 for level 1 and 2 systems.
- ISO 8528-4: 1993 compliance, controls and
switchgear.
- CE marking: The control system is suitable for use on
generator sets to be CE-marked.
- EN 50081-1,2 residential/light industrial emissions or
industrial emissions.
- EN 50082-1,2 residential/light industrial or industrial
susceptibility.
- ISO 7637-2, level 2; DC supply surge voltage test.
- Mil Std 202C, Method 101 and ASTM B117: Salt fog
test.
- UL 508 recognized or Listed and suitable for use on UL
2200 Listed generator sets.
- CSA C282-M1999 compliance
- CSA 22.2 No. 14 M91 industrial controls.
- PowerCommand control systems and generator sets
are designed and manufactured in ISO 9001 certified
facilities.

Warranty
All components and subsystems are covered by an
express limited one year warranty. Other optional and
extended factory warranties and local distributor
maintenance agreements are available.

See your distributor for more information

Cummins Power Generation


Americas Europe, CIS, Middle East and Africa Asia Pacific
rd
1400 73 Avenue N.E. Manston Park Columbus Ave. 10 Toh Guan Road #07-01
Minneapolis, MN 55432 USA Manston Ramsgate TT International Tradepark
Phone: 763 574 5000 Kent CT 12 5BF United Kingdom Singapore 608838
Fax: 763 574 5298 Phone 44 1843 255000 Phone 65 6417 2388
Fax 44 1843 255902 Fax 65 6417 2399

Warning: Back feed to a utility system can cause electrocution and/or property damage. Do not connect to any building’s electrical system
except through an approved device or after building main switch is open.
Our energy working for you.™
www.cumminspower.com
©2010 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins
Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of Cummins Power Generation. Other
company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
S-1568c (5/10) Page 7 of 7