F0089

© 2011 Tyco Safety Products, All Rights Reserved.


How to Manage Points Using
Install Mode from
the 4100ES FACP
4100ES
(Adobe Reader 9 or later is required to correctly view
this document Click here to download the free viewer )
Follow these steps and click the corresponding movie to view the
procedure for using Install Mode to manage points at a 4100ES FACP.
Note: This Tutorial is Part 1 of 2. Please refer to F0090 “How to Remove Cards from Install Mode” for the conclusion of this procedure.

1. From the 4100ES Front Panel, use the Trouble Ack button to review active troubles on the system.
2. Login at the default Access Level 3 (see Tutorial F0088 if necessary for this procedure).
3. Navigate to the “Diagnostics Functions” screen, and then the “View/Change Install Mode List?” screen.
4. Add the NO ANSWER devices to the Install Mode List.
5. Add MISSING/FAILED Cards to the Install Mode List.
6. Remove ALL NORMAL Points from the Install Mode List.
7. Verify the proper devices are in the Install Mode List.
8. Continue on to F0090 to complete the procedure.

For additional information, reference TSPI Tutorials related to 4100ES Install Mode F0087 through F0091. To give us feedback, click here.

International Trade Controls and Restrictions


This material may contain information or technology the export or re-export of which is restricted by U.S. laws and regulations. By viewing this material, the recipient agrees to the following: (i) the recipient's use of the
contents of this material shall comply with all applicable laws, rules and regulations, including, without limitation, U.S. international trade laws and regulations, and (ii) the recipient may not transfer or otherwise export or
re-export any information or technology contained in this material except in full compliance with the export controls administered by the U.S. and other countries and any applicable import and use restrictions.