TEST PROCEDURE FOR P442 TEST EQUIPMENT : OMICRON [NOTO : IN PSL [PROGRAMMABLE SCHEME LOGIC] Assign any trip Input signal TO faultrecord trigger output signal } SOTF: TOR: GOTO DISTANCE SCHEMES IN MAIN MENU GOTO SOTF/TOR MODE ENABLE SOTF ALL ZONES. [i.e make to 1] MAKE OTHER SETTINGS DISABLE [Le. make @ ONLY J SET SOTF DELAY = 105 [MIN= 10S ; MAX =3.6 Ks] GOTO STATE SEQUENCER IN OMICRON 1* stage APPLY NOMINAL V & 1 [Le. 63.5v & 1A ]FOR3 PH UPTO 1 SEC. 2" stage APPLY 0 V &0A FOR ALL 3 PHI UPTO 11 see 3" stage APPLY 0 V & 12 A FOR ALL 3 PH UPTO 1 SEC. RELAY WILL TRIP IN SOT#/TOR TRIP, GOTO DISTANCE SCHEMES IN MAIN MENU GOTO SOTF/TOR MODE ENABLE TOR ALL ZONES. | i.e. make 0 to 1] MAKE OTHER SETTINGS DISABLE [Le. make @ ONLY ] DEFAULT TOR DELAY = 200 ms GOTO STATE SEQUENCER IN OMICRON 1™ stage APPLY NOMINAL V & I [Le. 63.5 v & 14] FOR3 PH UPTO 1 SEC. 2™ stage APPLY 0 V & 0 A FOR ALL 3 PH UPTO 300 msec 3" stage APPLY 0 V & 1.2 A FOR ALL3 PH UPTO 1 SEC. © RELAY WILLTRP IN SOTE/TOR TRIP. CARRIER AIDED TRIP: . . © GOTO DISTANCE SCHEMES IN MAIN MENU © GOTO STANDARD MODE o SBLECT P.U.PZ2 {NOTO; IN PSL [PROGRAMMABLE SCHEME LOGIC] Assign any OPTO Input signal TO distance channel reciev output signal ] © ENERGISE THE CORRESPONDING OPTO & APPLY AZ2 FAULT co RELAY WILL TRIP IN TI! time & distance Aided Trip Z2 Signal appear IN FAULRECORD. © FOR OTHER ZONES RELAY WILL TRIP IN CORRESPONDING ZONE TIME DELAY THOUGH THE CARRIER IS RECIVED, WEEK INFEED: o GOTO DISTANCE SCHEMES IN MAIN MENU o GOTO STANDARD MODE o SELECT P.U.P 22 o GOTO WI: Mode Status & Assign Trip & Echo o GOTO WI: Single Pole & Assign Enabled. o SET WI: Thres = 45 V [NOTO : IN PSL [PROGRAMMABLE SCHEME LOGIC] Assign any OPTO Input signal TO distance channel reciev output signal & Assign Distance Signal Send Input signal TO Any Output Signal output signal] o ENERGISE THE CORRESPONDING OPTO & APPLY LESS THAN 43 V. o RELAY WILL TRIP IN WEEK INFEED TRIP & Signal Send O/P Relay should Operate 9. If The Voltage 18 NOT LESS THAN 45V RELAY WON'T TRIP & ECHO back the Carrier [ie. Distance Signal will Send ] VT FUSE FAIL ; © GOTO SUPERVISION IN THE MAIN MENU o SET VTS TIME DELAY = 1 SEC o SET VTS 12 & Ie Inh = 50.00 Ma [ NOTE : THE ABOVE SETTING IS FOR 1 PH, 2 PH VT FUSE FAIL) © GOTO STATE SEQUENCER IN OMICRON © 1* stage APPLY NOMINAL V&l [Le 63.5v&1A]FOR3 PH UPTO 15SEC, o of stage APPLY 0 V FOR FOR ANY IPH OR 2 PH FOR 2 SEC WITHOUT CHANGE IN NOMINAL 3 PH CURRENT. © VT FALL INDICATION WILL APPEAR IN THE FAULT RECORD. DISTANCE PROTECTION WILL GET BLOCKED DURING REAL FUSEFAIL, © DURING 2“ STAGE, IF THE NEGATIVE SEQUENCE CURRENT & ZERO SEQUENCE CURRENT IS MORE THAN $0.0 mA RELAY WILL TAKE IT AS A FAULT & GIVE THE TRIP ah’ NO VT FAIL INDICATION. WILL APPEAR. ef wD wo © GOTO SUPERVISION IN THE MAIN MENU AGAIN oT 0 SETDETRCT 3P ENABLED ae A get” » SET Threshold 3P = 30 V v a) ° ay vw 0 SET DELTAI> 100.0 Ma “y SM we © GOTO STATE SEQUENCER IN OMICRON & o i stage APPLY NOMINAL V & I [Le. 63.5v&1A]FOR3 PH UPTO 1 SEC. oi ge stage APPLY 0 V FOR FOR ALL 3PH FOR 2 SEC WITHOUT CHANGE IN NOMINAL 3 PH CURRENT, ° VT FAIL INDICATION WILL APPEAR IN THE FAULT RECORD. Lease peuinal . Nonuinall O6+5v by o get eek

You might also like