You are on page 1of 5

Lightning Performance of 275 kV Transmission

Lines
R. Bhattarai1, R. Rashedin, S. Venkatesan, A. Haddad, H. Griffiths, N. Harid
High Voltage Energy Systems Group, School of Engineering, Cardiff University, United Kingdom
1
BhattaraiR@Cardiff.ac.uk

Abstract—This paper presents a comparative lightning front time of the lightning impulse. The overvoltage
performance study conducted on a 275 kV double circuit magnitude and impulse shape on the struck phase conductor
shielded transmission line using two software programs, TFlash
and Sigma-Slp. The line performance was investigated by using is computed for both the shielding failure and backflashover
both a single stroke and a statistical performance analysis and cases.
considering cases of shielding failure and backflashover. A To improve the lightning performance of the line, the
sensitivity analysis was carried out to determine the relationship application of metal oxide surge arrester was studied using
between the flashover rate and the parameters influencing it. To different arrester configurations and locations. The computed
improve the lightning performance of the line, metal oxide surge
arresters were introduced using different phase and line results indicate that arresters installed on the top phase of
locations. Optimised arrester arrangements are proposed. each circuit give the most significant improvement in
lightning performance when combined with low tower
Index Terms—Lightning Overvoltages, Statistical Analysis,
Electrogeometric modelling, Sensitivity Analysis, Surge Arrester footing resistance. Optimised locations of surge arresters
were then derived for practical applications.

I. INTRODUCTION II. SIMULATED LINE DATA


Lightning is a major cause of overhead line faults. A 35km long, 275kV double circuit line with 300m span
Between 5% to 10% of the lightning-caused faults are thought length was selected in this study. The height of the steel-
to result in permanent damage to power system equipment lattice towers of the line is assumed to be 36.88m. The surge
[1]. Therefore, the analysis of lightning performance is impedance of the tower was calculated to be 173.1Ω using (1)
fundamental when designing new lines and for uprating [2, 5].
existing lines to higher voltages.
Lightning is a natural phenomenon with random behaviour, ⎡ ⎛ ravg ⎞⎤
Z T = 60 ln cot ⎢0.5 tan −1 ⎜⎜ ⎟⎥
⎟ (1)
and hence a complete study of the lightning performance of ⎢⎣ ⎝ h1 + h2 ⎠⎥⎦
an overhead line should also include a statistical approach [2].
Computer software packages have been developed for the where, ravg is the weighted average tower radius given by (2).
evaluation of lightning performance of overhead lines. In this r1 h2 + r2 (h1 + h2 ) + r3 h1
ravg = (2)
study, two widely-available programs, viz. TFlash and Sigma- (h1 + h2 )
Slp have been used in a comparative study of the lightning
performance of a generic 275 kV double circuit line. where,
Both software packages make use of the travelling wave r1, r2 and r3 are the radii at the top, midsection and base of the
tower respectively, and
method for the computation of electromagnetic transients
h1 and h2 are the tower heights from base to midsection and
along the line [3, 4]. TFlash employs a Stroke Incidence
midsection to the tower top respectively.
Table (SIT) together with an Electrogeometric Model (EGM)
The line is assumed to be located on flat terrain with a
or the EPRI stroke attraction model while Sigma-Slp uses a
ground flat density of 0.5 flashes per kilometre square per
Monte Carlo statistical method in combination with the EGM
year (fl/km2/yr). It is also assumed that there is no nearby
to determine strike points on the line. Both programs are
object present to cause an induced voltage flashover on the
capable of modelling the application of line surge arresters.
line.
In this paper, single and statistical stroke analyses were
The phase conductors were twin 175mm2 ‘Lynx’ type
made with different amplitudes of the injected stroke current
ACSR conductors with a bundle spacing of 30.48cm and a
in order to estimate the flashover performance of the studied
single Lynx ACSR conductor was used for earthwire. The
transmission line. In this investigation, both shielding failure
individual conductors have a 19.53mm diameter. The phase
and backflashover were considered. Detailed sensitivity
and earth conductors were assumed to have a 7.05m and
analysis studies were carried out to determine the relationship
6.66m mid-span sag respectively. The Tower structure and
between the flashover rate and the parameters influencing it;
conductor geometry are shown in Fig. 1.
such as tower footing resistance, ground flash density and

Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE MINAS GERAIS. Downloaded on March 4, 2009 at 11:15 from IEEE Xplore. Restrictions apply.
III. LINE MODELLING TECHNIQUES
The details of the transmission line modelling in the
software are as follows:
The line consists of 116 spans with each span represented
as a multiphase untransposed distributed parameter line
section. To avoid reflections on the line, a sufficiently long
section is added to each side of the studied line. At line ends,
Sigma-Slp connects coupling matrices while TFlash adds
matching impedances in order to avoid reflections. Each
simulated span section is further divided into shorter sections
to enable stroke simulation at a number of points along the
span.
In TFlash, the tower is modelled as a simple transmission
line with constant surge impedance, and terminated with a
footing resistance. In Sigma-Slp, the tower is modelled by a
propagation element model represented by the tower surge
impedance and its propagation length. The propagation
length is equal to the height of the tower.
A non-linear footing resistance, as derived by Weck [2] and
given in (3), is used in both programs
R0
RT = (3)
I
1+
Ig

Eg ρ
With; Ig = (4)
2 π R02
where, R0 is the low-current tower footing resistance, ρ is the
Fig. 1. 275 kV double circuit shielded transmission line tower showing
its conductor coordinates. Values in parenthesis are midspan heights. soil resistivity, I is the stroke current through the tower
footing and, E0 the soil ionisation threshold [400kV/m].
The line insulator strings are composed of 16 individual In TFlash, the Disruptive Effect (DE) method [6] is used as
glass insulator discs having 170mm spacing and each disc has the default insulator flashover model whereas Sigma-Slp, uses
a creepage distance of 540mm which is equivalent to a total a leader progression method. The DE method defines the
string length of 3.31m (including the length of the fittings at disruptive index by
top and bottom of the string). The calculated critical B

flashover voltage (CFO) of the insulator string is 1646kV. DE = ∫ [V (t ) − A] dt (5)


To study the lightning performance of the line with surge where, V(t) is instantaneous value of the impulse voltage, and
arresters, metal oxide arresters with a nominal discharge A and B are constants; A represents the minimum voltage
current of 10kA, a Maximum Continuous Operating Voltage below which breakdown cannot occur and B is a coefficient
(MCOV) of 220kV and an energy capability of 7.8kJ/kV were indicating that the breakdown process is not linear. When the
used. The voltage-current characteristic of the arrester used disruptive index, DE, reaches a critical value, breakdown
in this work is shown in Fig. 2. would occur.
800 The leader progression method [2] is represented by
750 ⎡ u (t ) ⎤ 0.0015 u d(t )
Vl = 170 d ⎢ − E0 ⎥ e (6)
⎣ d − ll
Discharge Voltage (kV)

700 ⎦
where, Vl is the leader velocity, d the gap distance, ll the
650
leader length, u(t) the applied voltage and, E0 the voltage
600 gradient (520kV/m).
The power frequency voltage may influence the insulator
550
flashover. This influence is taken into account by calculating
500
the voltage across the insulators through a 3600 phase cycle,
0 10 20 30 40 and the flashover rate is determined using its average.
Arre ster Cur rent (k A) The effect of corona coupling in the line is considered in
Fig. 2. Surge arrester voltage-curve.
TFlash while it is ignored in Sigma-Slp.

Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE MINAS GERAIS. Downloaded on March 4, 2009 at 11:15 from IEEE Xplore. Restrictions apply.
The EGM is used to determine the strike point on the line. 6000
TFlash

In this investigation, more than 20000 stokes are used for the 5000 Sigma-Slp

electromagnetic simulations. The conductor and earth 4000

Overvoltage (kV)
striking distance used in the software are given by [2, 7] 3000

2000
0.65
R c = 10 I (7) 1000

R e = [3.6 + 1.7 ln(43 − h)] I 0.65


for h < 40 m (8) 0

-1000

R e = 5.5 I 0.65 for h > 40 m (9) -2000


0 2 4 6 8 10
where, Rc is the striking distance to a line conductor, Re is the Time (µs)

striking distance to earth, I is the lightning impulse current


(a) Shielding failure flashover
magnitude and, h is the height of the tower.
6000
TFlash
5000 Sigma-Slp
IV. SINGLE STROKE ANALYSIS
4000

Overvoltage (kV)
For the single stroke studies, the overvoltage magnitude
3000
and impulse shape on the phase conductor during shielding
2000
failure and backflashover are computed. A 32kA, 2/75
impulse current is applied to phase conductor A1 at the tower 1000

position to simulate a shielding failure flashover on the line. 0

A low current tower footing resistance of 10Ω and 200 Ωm -1000


0 5 10 15 20 25 30 35 40 45 50
soil resistivity were assumed. Fig. 3a shows typical impulse
Time (µs)
voltage on the phase conductor. As can be seen in the figure,
similar voltage impulse magnitudes were obtained with the (b) Backflashover
two models. However, close examination of the results
Fig. 3. Overvoltage magnitude and shape on phase conductor A1
reveals that the TFlash model predicts a slightly higher computed using TFlash & Sigma-Slp.
overvoltage magnitude and a faster initial rise time compared
with the Sigma-Slp model. For the backflashover studies, a possible, 32 stroke current beans and a current range from
200kA lightning impulse was injected on to the shield wire at 2.5kA to 160kA were selected.
a tower position. A low current tower footing resistance of In the TFlash model, the selected lightning current impulse
80Ω and a soil resistivity of 1600Ωm were adopted, which shape was used for the entire statistical calculation without
allow backflashover to be initiated. Fig. 3b shows a typical any variation. Again, for close matching of the two models,
impulse shape of overvoltage computed on the phase simulations were carried out with a 2/75 lightning impulse.
conductor during backflashover. Here again, we can observe
A. Sensitivity Analysis
that the results obtained with TFlash model indicate slightly
Sensitivity analysis studies were carried out to determine
higher magnitudes of overvoltage and faster rise times
the relationship between the flashover rate and the parameters
compared with the Sigma-Slp model.
influencing it, such as tower footing resistance, ground flash
density (GFD) and front time of the lightning impulse.
V. STATISTICAL ANALYSIS
(i) Effect of footing resistance
Statistical flashover analysis of the studied line is carried It was found that the shielding failure flashover rate
out to assess the risk of flashover considering the random (SFFR) is not affected by footing resistance and a constant
behaviour of lightning. The flashover rate (number of flashes SFFR of 0.7 and 0.63 fl/100km/yr was obtained in TFlash and
per 100km per year) is used as the basic parameter in the Sigma-Slp respectively. Fig. 4a illustrates the effect of
sensitivity analysis, and the performance of the line is footing resistance on the backflashover rate. As can be seen
analysed with different arrester configurations. in the figure, the backflashover rate (BFR) evaluated by
The programs used in this investigation (Sigma-Slp and Sigma-Slp, for a given value of footing resistance is higher
TFlash) use slightly different approaches for simulating than that computed by TFlash.
random behaviour of lightning. In Sigma-Slp, random
(ii) Effect of ground flash density (GFD)
lightning strokes are generated with magnitudes between 1.2
The effect of GFD on SFFR is shown in Fig. 4b. As can be
and 161.1kA and with rise times in the range between 1.2 and
seen, the SFFR calculated using the Sigma-Slp model is
4.38 µs. A fixed half time of 75 µs is assumed. The impulse
lower than the SFFR computed using the TFlash model.
shape varies randomly, with a sample size of 2000. In
The difference may be attributed to the different stroke
TFlash, however, the stroke current range can be selected
statistics patterns of the two models. In the TFlash model,
from 1kA to 300kA, and the range is divided up to 512
45% to 50% of the current bins are in the low-current range
current ‘bins’. In order to match the two models, as closely as

Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE MINAS GERAIS. Downloaded on March 4, 2009 at 11:15 from IEEE Xplore. Restrictions apply.
which is more likely to result in shielding failures. On the B. Flashover Performance of the Line with Surge Arresters
other hand, in the Sigma-Slp model, only 10% to 15% of the The objective of this study was to estimate the
total number of strokes are likely to hit the phase conductor as improvement in flashover rate by implementing surge
a result of shielding failure. Therefore, the majority of arresters on the line. Different arrester configurations and
strokes in the Sigma-Slp simulations hit the shield wire or the locations were analysed and compared to assess
tower top resulting in higher backflashover rates. improvements in lightning performance of the line. In these
studies, low current tower footing resistance value was varied
(iii) Effect of impulse shape
from 10Ω to 80Ω keeping the ratio of soil resistivity to
The computed effect of lightning impulse shape on the line
footing resistance constant (ρ/R0 = 20). An initial study was
flashover rate is shown in Fig. 4c. Only results from the
carried out with arresters positioned at every tower and on
TFlash model were shown since it is possible to vary the
every phase conductor. This resulted in a zero flashover rate,
impulse front time in this case. From Fig. 4c, it can be seen
but, practically the configuration would be too expensive.
that, for fast front times (< 2µs), the BFR increases as the
It is well known [8] that, in the low current range, the
front time decreases. The simulations show that SFFR is not
lightning strikes hit only the top phase conductors of the two
influenced by variations in the front time; a constant value of
circuits during shielding failure. This suggests that the
0.7 fl/100km/yr is obtained.
majority of shielding failures for this tower design would
TF las h
occur on the top phases. Table I shows typical results of an
0. 4 S ig m a-S lp electrogeometric model (EGM) study obtained with Sigma-
0 .3 5
0. 3
Slp and Fig. 5 shows an example of graphical display of
lightning strokes hitting the line for different current
BFR (fl/100km/yr)

0 .2 5
0. 2 magnitudes, which were obtained with TFlash. Based on
0 .1 5 these studies, four practical different arrester configurations
0. 1 were studied, and are shown in Table II. In the table, the
0 .0 5 black spots on the phases represent the application of an
0
arrester on that phase.
-0 .0 5
0 10 20 30 40 50 60 70 80 90
As can be seen in the table, the Sigma-Slp modelling shows
L o w C u rr e n t F o o tin g R e sista n ce (o h m ) that the application of arresters substantially improves the
flashover rate. By placing arresters on the top phases only, a
(a) Flashover rate vs. low current footing resistance
zero SFFR is obtained. However, this arrangement only
(GFD = 0.5 fl/km2/yr, ρ/R0 = 20)
TF la s h
suppresses backflashover under low footing resistance
1. 6
S igm a -S lp conditions. On the other hand, with arresters installed on the
1. 4
bottom phases only, a zero backflashover rate is obtained at
1. 2
expense of shielding failure. When arresters are installed on
SFFR (fl/100km/yr)

1
the top and bottom phases, both shielding and backflashover
0. 8
failure can be suppressed. Therefore, to improve the
0. 6
lightning performance, it is recommended to install arresters
0. 4
only in the top phases at towers with low footing resistance
0. 2
and in the top and bottom phases at towers with high footing
0
0 0 .2 0. 4 0 .6 0. 8 1 1. 2
resistance.
G F D (fl /k m 2 / yr ) TABLE I
EGM REPORT IN SIGMA-SLP
(b) Flashover rate vs. GFD (R0 = 10 Ω, ρ = 200 Ωm)
To Phase A2
To phase A1

To phase B1

To phase C1

To phase C2

To phase B2
current (kA)
Med. stroke

Total stroke

0 .7
To shield
To tower
To earth
GFD

wire

0 .6

0 .5
BFR (fl/100km/yr)

0 .4

0 .3
20000

14054

4840
31.5

331

280

298
0.5

0 .2

0 .1

-0 .1
0 .5 1 1 .5 2 2 .5 3 3. 5 4
F r o n t T im e (µ s)

(c) Flashover rate vs. lightning impulse front time in TFlash


(GFD = 0.5 fl/km2/yr, R0 = 10 Ω, ρ = 200 Ωm)

Fig. 4. Sensitivity analysis Fig. 5. Stroke view at different current magnitude in TFlash

Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE MINAS GERAIS. Downloaded on March 4, 2009 at 11:15 from IEEE Xplore. Restrictions apply.
Table III shows the results obtained with the TFlash model, 40 0.01 0 0 0 0
which agree with the previous findings. The SFFR obtained 50 0.04 0 0 0 0
60 0.09 0.02 0 0 0
in this case is slightly higher while the BFR lower.
70 0.15 0.03 0 0 0
80 0.25 0.05 0.02 0 0
TABLE II Total Flashover Rate (fl/100km/yr)
FLASHOVER RATE (SIGMA-SLP MODEL) 10 0.70 0 0.70 0.70 0
DIFFERENT ARRESTER CONFIGURATIONS 20 0.70 0 0.70 0.70 0
Footing 30 0.70 0 0.70 0.70 0
Resistan 40 0.71 0 0.70 0.70 0
ce 50 0.74 0 0.70 0.70 0
(Ω) 60 0.79 0.02 0.70 0.70 0
Shielding Failure Flashover Rate (fl/100km/yr) 70 0.85 0.03 0.70 0.70 0
10 0.63 0 0.63 0.63 0 80 0.95 0.05 0.72 0.70 0
20 0.63 0 0.63 0.63 0 • mark indicates surge arrester in the phase
30 0.63 0 0.63 0.63 0
40 0.63 0 0.63 0.63 0
50 0.63 0 0.63 0.63 0
60 0.63 0 0.63 0.63 0 VI. CONCLUSION
70 0.63 0 0.63 0.63 0
80 0.63 0 0.63 0.63 0
Two similar models of transmission line were studied using
Backflashover Rate (fl/100km/yr) Sigma-Slp and TFlash software packages. Satisfactory
10 0 0 0 0 0 agreement is given by the two models.
20 0 0 0 0 0 It was shown that the lightning performance of overhead
30 0 0 0 0 0 transmission lines can be improved by applying surge
40 0.03 0 0 0 0 arresters. Arresters on the top phases improve shielding
50 0.08 0.01 0 0 0 failure flashover rate, and when applied to the bottom phases
60 0.14 0.03 0.01 0 0 they allow improvement of backflashover rate. Adequate
70 0.26 0.07 0.02 0 0 selection of the arrester configuration in the line can
80 0.35 0.11 0.03 0 0
significantly improve lightning performance and may reduce
Total Flashover Rate (fl/100km/yr)
10 0.63 0 0.63 0.63 0
the financial burden.
20 0.63 0 0.63 0.63 0
30 0.63 0 0.63 0.63 0
40 0.67 0 0.63 0.63 0
50 0.72 0.01 0.63 0.63 0 REFERENCES
60 0.78 0.03 0.65 0.63 0 [1] T. Short, "Application of the IEEE Guide for Improving the Lightning
70 0.90 0.07 0.66 0.63 0 Performance of Electric Power Overhead Distribution Lines (Std. 1410-
80 0.99 0.11 0.67 0.63 0 1997)," in IEEE T&D Conference, 1999.
• mark indicates surge arrester in the phase [2] CIGRE Working Group 33-01, "Guide to Procedures for Estimating the
Lightning Performance of Transmission Lines," CIGRE Brochure 63,
1991.
TABLE III [3] T. E. McDermott and V. J. Longo, "Advanced computational methods
FLASHOVER RATE (TFLASH MODEL) in lightning performance the EPRI Lightning Protection Design
DIFFERENT ARRESTER CONFIGURATIONS Workstation," Power Engineering Society Winter Meeting, 2000. IEEE,
2000.
Footing
[4] Y. A. Wahab, Z. Z. Abidin, and S. Sadovic, "Line surge arrester
Resistan
application on the quadruple circuit transmission line," Power Tech
ce
Conference Proceedings, 2003 IEEE Bologna, 2003.
(Ω)
[5] W. A. Chisholm, Y. L. Chow, and K. D. Srivastava, "Travel Time of
Shielding Failure Flashover Rate (fl/100km/yr) Transmission Towers," IEEE Transactions on Power Apparatus and
10 0.70 0 0.70 0.70 0 Systems, vol. PAS-104, pp. 2922-2928, 1985.
20 0.70 0 0.70 0.70 0 [6] U. Savadamuthu, K. Udayakumar, and V. Jayashankar, "Modified
30 0.70 0 0.70 0.70 0 disruptive effect method as a measure of insulation strength for non-
40 0.70 0 0.70 0.70 0 standard lightning waveforms," Power Delivery, IEEE Transactions on,
50 0.70 0 0.70 0.70 0 vol. 17, pp. 510-515, 2002.
[7] "IEEE guide for improving the lightning performance of transmission
60 0.70 0 0.70 0.70 0
lines," IEEE Std 1243-1997, 1997.
70 0.70 0 0.70 0.70 0 [8] S. Sadovic, R. Joulie, S. Tartier, and E. Brocard, "Use of line surge
80 0.70 0 0.70 0.70 0 arresters for the improvement of the lightning performance of 63 kV
Backflashover Rate (fl/100km/yr) and 90 kV shielded and unshielded transmission lines," Power
10 0 0 0 0 0 Delivery, IEEE Transactions on, vol. 12, pp. 1232-1240, 1997.
20 0 0 0 0 0
30 0 0 0 0 0

Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE MINAS GERAIS. Downloaded on March 4, 2009 at 11:15 from IEEE Xplore. Restrictions apply.

You might also like