You are on page 1of 12

Constante KG para distintos factores de potencia

Calibre R equiv. Factor de potencia


XL [Ω/Km]
(AWG) [Ω/Km] 0.8 0.85 0.9 0.95
14 10.2 0.19 8.019778699 8.73907408 9.30359734 9.574176
12 6.6 0.177 52.93053941 57.6778889 61.4037424 63.1895616
10 3.9 0.164 206.4291037 224.943767 239.474595 246.43929
8 2.56 0.171 528.4585055 575.856043 613.054964 630.884583
6 1.61 0.167 850.8181939 927.12823 987.018493 1015.72418
4 1.02 0.157 867.8345578 945.670794 1006.75886 1036.03866
3 0.82 0.154 711.6243374 775.450051 825.542267 849.551703
2 0.62 0.148 441.2070892 480.779032 511.836206 526.722056
1 0.49 0.151 216.1914737 235.581726 250.799741 258.093807
1/0 0.39 0.144 84.31467474 91.876873 97.8118989 100.656585
2/0 0.33 0.141 27.82384266 30.3193681 32.2779266 33.216673
3/0 0.253 0.138 7.039432194 7.67080012 8.16631544 8.40381827
4/0 0.203 0.135 1.429004735 1.55717243 1.65776203 1.70597511
250 0.171 0.135 0.24435981 0.26627648 0.28347731 0.29172174
300 0.144 0.135 0.035187813 0.03834381 0.04082073 0.04200793
350 0.125 0.131 0.004398477 0.00479298 0.00510259 0.00525099
400 0.108 0.131 0.000475035 0.00051764 0.00055108 0.00056711
500 0.089 0.128 4.227816E-05 4.607E-05 4.9046E-05 5.0473E-05
600 0.075 0.128 3.170862E-06 3.4553E-06 3.6785E-06 3.7854E-06
750 0.062 0.125 1.965934E-07 2.1423E-07 2.2806E-07 2.347E-07
1000 0.049 0.121 9.633078E-09 1.0497E-08 1.1175E-08 1.15E-08
Grados 36.869 31.788 25.841 18.194

Radianes -0.7380068 0.3635478 0.6505123 -0.6096


Capacidad de corriente permisible en conductores aislados para 0 a 2000 V nominales al aire libre
y temperatura ambiente de 30 °C. (TABLA 310-16 NTC 2050)

Temperatura Nominal Del Conductor


60 ºC 75 ºC 90 ºC 60 ºC 75 ºC 90 ºC
Tipos Tipos Tipos Tipos Tipos Tipos
TBS SA SIS
Sección TBS SA SIS
FEP FEPB MI Calibre
THHN THHW
Tranversal FEPW RH RHH RHW-2
RH RHW THW-2
RHW THHW THHN THHW
THHW THW THWN-2 RHH
S TW UF THW THWN THW-2 TW UF
THWN XHHW RHW-2 USE-2
XHHW USE THWN-2 USE-
USE XHH XHHW
ZW 2 XHH XHHW
XHHW-2 ZW-
XHHW-2 ZW-
2
2

mm2 COBRE ALUMINIO RECUBIERTO CON COBREAWG ó kcmil


0.82 18 18
1.31 24 16
2.08 25 30 35 14
3.3 30 35 40 25 30 35 12
5.25 40 50 55 35 40 40 10
8.36 60 70 80 45 55 60 8
13.29 80 95 105 60 75 80 6
21.14 105 125 140 80 100 110 4
26.66 120 145 165 95 115 130 3
33.62 140 170 190 110 135 150 2
42.2 165 195 220 130 155 175 1
53.5 195 230 260 150 180 205 1/0
67.44 225 265 300 175 210 235 2/0
85.02 260 310 350 200 240 275 3/0
107.21 300 360 405 135 280 315 4/0
126.67 340 405 455 265 315 355 250
152.01 375 445 505 290 350 395 300
177.34 420 505 570 330 395 445 350
202.68 455 545 615 355 425 480 400
253.35 515 620 700 405 485 545 500
304.02 575 690 780 455 540 615 600
354.69 630 755 855 500 595 675 700
380.02 655 785 855 515 620 700 750
405.36 680 815 920 535 645 725 800
456.03 730 870 985 580 700 785 900
506.7 780 935 1055 625 750 845 1000
633.38 890 1065 1200 710 855 960 1250
760.05 980 1175 1325 795 950 1075 1500
886.73 1070 1280 1445 875 1050 1185 1750
1013.04 1155 1385 1560 960 1150 1335 2000
FACTORES DE CORRECCIÓN POR TEMPERATURA AMBIENTE

Temperatur Temperatura
Para temperaturas ambientes distintas de 30 ºC, multiplicar las
a Ambiente Ambiente en
anteriores corrientes por el correspondiente factor de los siguientes
en ºC ºC

21-25 1.08 1.05 1.04 1.08 1.05 1.04 21-25


26-30 1 1 1 1 1 1 26-30
31-35 0.91 0.94 0.96 0.91 0.94 0.96 31-35
36-40 0.82 0.88 0.91 0.82 0.88 0.91 36-40
41-45 0.71 0.82 0.87 0.71 0.82 0.87 41-45
46-50 0.58 0.75 0.82 0.58 0.75 0.82 46-50
51-55 0.41 0.67 0.76 0.41 0.67 0.76 51-55
56-60 0.58 0.71 0.58 0.71 56-60
61-70 0.33 0.58 0.33 0.58 61-70
71-80 0.41 0.41 71-80
Capacidad de corriente permisible en conductores aislados para 0 a 2000 V nominales de 60 ºC a
90 ºC no más de tres conductores portadores de corriente en una canalización, cable o tierra
( directamente enterrados) y temperatura ambiente de 30 ºC (TABLA 310-17 NTC 2050)

Temperatura Nominal Del Conductor


60 ºC 75 ºC 90 ºC 60 ºC 75 ºC 90 ºC
Tipos Tipos Tipos Tipos Tipos Tipos

TBS SA SIS
Sección FEP FEPB
Tranversa MI RHH TBS SA SIS Calibre
FEPW RH RHW-2 THHN THHW
l RHW THHW THHN THHW
RH RHW
THW-2 THWN-2
THHW THW
S TW UF THW THWN THW-2 TW UF RHH RHW-2
THWN XHHW
XHHW USE THWN-2 USE-2 XHH
USE
ZW USE-2 XHH XHHW XHHW-2
XHHW ZW-2
XHHW-2 ZW-
2

mm2 COBRE ALUMINIO RECUBIERTO CON COBRE AWG ó kcmil


0.82 14 18
1.31 18 16
2.08 20 20 25 14
3.3 25 25 30 20 20 25 12
5.25 30 35 40 25 30 35 10
8.36 40 50 55 30 40 45 8
13.29 55 65 75 40 50 60 6
21.14 70 85 95 55 65 75 4
26.66 85 100 110 65 75 85 3
33.62 95 115 130 75 90 100 2
42.2 110 130 150 85 100 115 1
53.5 125 150 170 100 120 135 1/0
67.44 145 175 195 115 135 150 2/0
85.02 165 200 225 130 155 175 3/0
107.21 195 230 260 150 180 205 4/0
126.67 215 255 290 170 205 230 250
152.01 240 285 320 190 230 255 300
177.34 260 310 350 210 250 280 350
202.68 280 335 380 225 270 305 400
253.35 320 380 430 260 310 350 500
304.02 355 420 475 285 340 385 600
354.69 385 460 520 310 375 420 700
380.02 400 475 535 320 385 435 750
405.36 410 490 555 330 395 450 800
456.03 435 520 585 355 425 480 900
506.7 455 545 615 375 445 500 1000
633.38 495 590 665 405 485 545 1250
760.05 520 625 705 435 520 585 1500
886.73 545 650 735 455 545 615 1750
1013.04 560 665 750 470 560 630 2000
FACTORES DE CORRECCIÓN POR TEMPERATURA AMBIENTE
Temperat
Temperatura
ura Para temperaturas ambientes distintas de 30 ºC, multiplicar las
Ambiente en
Ambiente anteriores corrientes por el correspondiente factor de los siguientes
ºC
en ºC
21-25 1.08 1.05 1.04 1.08 1.05 1.04 21-25
26-30 1 1 1 1 1 1 26-30
31-35 0.91 0.94 0.96 0.91 0.94 0.96 31-35
36-40 0.82 0.88 0.91 0.82 0.88 0.91 36-40
41-45 0.71 0.82 0.87 0.71 0.82 0.87 41-45
46-50 0.58 0.75 0.82 0.58 0.75 0.82 46-50
51-55 0.41 0.67 0.76 0.41 0.67 0.76 51-55
56-60 0.58 0.71 0.58 0.71 56-60
61-70 0.33 0.58 0.33 0.58 61-70
71-80 0.41 0.41 71-80
Capacidad de corriente permisible de tres conductores sencillos aislados de 0 a 2000 V, de 150 ºC a
250 ºC en canalizaciones o cables y temperatura ambiente de 40 ºC (TABLA 310-18 NTC 2050)

Temperatura nominal del conductor


Secciòn 150 ºC 200 ºC 250 ºC 150 ºC
Calibre
transv. TIPOS FEP,
TIPO Z TIPOS PFAH, TFE TIPO Z
FEPB, PFA
ALUMINIO O
Nìquel O Nìquel
ALUMINIO
mm2 COBRE RECUBRIMIENTO DE AWG kcmils
RECUBIERTO DE
COBRE
COBRE
2.08 34 36 39 14
3.3 43 45 54 30 12
5.25 55 60 73 44 10
8.36 76 83 93 57 8
13.29 96 110 117 74 6
21.14 120 125 148 94 4
26.66 143 152 166 109 3
33.62 160 171 191 124 2
42.2 186 197 215 145 1
53.5 215 229 244 169 1/0
67.44 251 260 273 198 2/0
85.02 288 297 308 227 3/0
107.21 332 346 361 260 4/0
126.67 250
152.01 300
177.34 350
202.68 400
253.35 500
304.02 600
354.69 700
380.02 750
405.36 800
506.7 1000
760.05 1500
1013.4 2000

FACTORES DE CORRECCIÒN
Temp. Temp.
Para temperaturas ambientes distintas de 40ºC multiplicar las
Ambiente en Ambiente en
anteriores corrientes por el correspondiente de los siguientes factores
ºC ºC
41-50 0.95 0.97 0.98 0.95 41-50
51-60 0.9 0.94 0.95 0.9 51-60
61-70 0.85 0.9 0.93 0.85 61-70
71-80 0.8 0.87 0.9 0.8 71-80
81-90 0.74 0.83 0.87 0.74 81-90
91-100 0.67 0.79 0.85 0.67 91-100
101-120 0.52 0.71 0.79 0.52 101-120
121-140 0.3 0.61 0.72 0.3 121-140
141-160 0.5 0.65 141-160
161-180 0.35 0.58 161-180
181-200 0.49 181-200
201-225 0.35 201-225
Capasidad de corriente permisible de conductores sencillos aislados de 0 a 2000 V, de 150 ºC a 250 ºC en
canalizaciones o cables y temperatura ambiente de 40 ºC (TABLA 310-19 NTC 2050)

Temperatura nominal del conductor


Secciòn 150 ºC 200 ºC Conductores 250 ºC 150 ºC
transv. TIPOS FEP, desnudos o TIPOS PFAH, TFE
TIPO Z TIPO Z
FEPB, PFA cubiertos

Nìquel O Nìquel
mm2 COBRE RECUBRIMIENTO ALUMINIO O ALUMINIO
DE NIQUEL RECUBIERTO DE
COBRE
2.08 46 54 30 59
3.3 60 68 35 78 47
5.25 80 90 50 107 63
8.36 106 124 70 142 83
13.29 155 165 95 205 112
21.14 190 220 125 278 148
26.66 214 252 150 327 170
33.62 255 293 175 381 198
42.2 293 344 200 440 228
53.5 339 399 235 532 263
67.44 390 467 275 591 305
85.02 451 546 320 708 351
107.21 529 629 370 830 411
126.67 415
152.01 460
177.34 520
202.68 560
253.35 635
304.02 710
354.69 780
380.02 805
405.36 835
865
506.7 895
760.05 1,205
1013.4 1,420

FACTORES DE CORRECCIÒN
Temp. Para temperaturas ambientes distintas de 40ºC multiplicar
Ambiente en las anteriores corrientes por el correspondiente de los Temp. Ambiente en ºC
ºC siguientes factores
41-50 0.95 0.97 0.98 0.95 41-50
51-60 0.9 0.94 0.95 0.9 51-60
61-70 0.85 0.9 0.93 0.85 61-70
71-80 0.8 0.87 0.9 0.8 71-80
81-90 0.74 0.83 0.87 0.74 81-90
91-100 0.67 0.79 0.85 0.67 91-100
101-120 0.52 0.71 0.79 0.52 101-120
121-140 0.3 0.61 0.72 0.3 121-140
141-160 0.5 0.65 141-160
161-180 0.35 0.58 161-180
181-200 0.49 181-200
201-225 0.35 201-225
Tipos y secciòn transversal (calibre) de Los conductores RH, RHH, RHW, THHW, THW, THWN,
THHN, XHHW, USE
Aluminio o aluminio Capacidad de corriente de la acometida o
Cobre
recubierto de cobre. alimentador
mm2 AWG mm2 AWG (A)
21.14 4 33.62 2 100
26.66 3 42.2 1 110
33.62 2 53.5 1/0 125
42.2 1 67.44 2/0 150
53.5 1/0 85.02 3/0 175
67.44 2/0 107.21 4/0 200
85.02 3/0 126.67 250 kcmils 225
107.21 4/0 152.01 300 kcmils 250
126.67 250 kcmils 177.34 350 kcmils 300
177.34 350 kcmils 253.35 500 kcmils 350
202.68 400 kcmils 304.02 600 kcmils 400

Tabla 310-19-8a
Numero de conductores Porcertanje del valor de las tablas, ajustado
portadores de corriente para la temperatura ambiente si fuera necesario
De 4 a 6 80
De 7 a 9 70
De 10 a 20 50
De 21 a 30 45
De 31 a 40 40
41 y mas 35
de 150 ºC a 250 ºC en
NTC 2050)

Calibre

AWG kcmils

14
12
10
8
6
4
3
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
800
900
1000
1500
2000

You might also like