Grounded Wye Primory Wire)

Neutrol
NOTE: The High-Voltoge
neutrol of the tronsformer
bonk must be connected to
the primory neutrol.

Surge Arrester
Fused Cutout NOTE:'Wild Leq '
' 208 V. To
Ground.

Primory ond Secondory


be \\
neutrols must De
neutrats
interconnected. \

NOTE:'Wild Leo
, 208 V. To Pole
Ground. Ground

Use seven
terminol
4 Wire Open Delto meter.
Secondory 12A/240 V.

VOLTAGE POTENTIALS-SECONDARY

PHASES I VOLTAGE
o-b |I 240 VOLTS
b-c 24O VOLTS
APPLICATION Used to supply lorqe sinqle-phose, 12O/24O voll o-c I 24O VOLTS
loods with smoll omount'bf thre-e phoSe loods. Also used o-N I 12O VOLTS
when only two phoses of primory ore ovoiloble or during b-N I 't20 voLTS
emergencies when one unit of o four-wire, wye-delto bonk c-N I 208 VOLTS
is disobled.
See drowing 'G2.1' or "VG2.1'for construction detoils. 2.I O. ANGUI.AR DISPLACEMENT
One-bushing or two-bushing tronsformers moy be used.
Usuolly tronsformers of different KVA sizes ore used.
BANK RATING: This bonk hos only 86.6% of the rotino of
ffi fiiffiAkino uo the three-bhose bonk ond onlv-57.7% oJ
the
the three-ohose'rotinq of o clo3ed delto-delto bonk of three
tronsformers. Thus, i[ is relotively inefficient where
... ,fi"
three-phose loods predominote. (lAaitive Polority-See TRANSFORMER SPECIFICATIOI

TRANSFORMER/METER CONNECTTON GUTDE


THREE_PHASE, OPEN_WYE _ OPEN DELTA
FOR 12O/24O VOLT POWER LOADS

APRIL 2OO5

RUS G2.1G