Refrigerant Piping
Additional Charge
• For piping length below 7.5m, kindly charge in refrigerant based on serial number sticker on unit.
• When piping length is more than 7.5m, please use the Table 3 below based on liquid pipe size per meter
length.
Liquid Pipe Size (in) Additional Charge (kg/m)
3/8 0.06
1/2 0.10
5/8 0.16
3/4 0.25
Table 3: Additional Charge