Application Information

Refrigerant Piping

Maximum Piping Length and Maximum Number of Bends


When the pipe length becomes too long, both the capacity and reliability drop. As the number of bends
increases, system piping resistance to the refrigerant flow increases, thus lowering the cooling capacity,
and as the result the compressor may become defective. Always choose the shortest path and follow the
recommendation as tabulated below:

R(Y)75CXY1 / RC(Y)100BXY1 / RC(Y)125BXY1 / RC150CXY1 /


Outdoor
RC75DXY1 RC100DXY1 RC125DXY1 RC150DXY1
Max. Length, m 35
Max. Elevation, m 20
Max. No. of Bends 10

Additional Charge

• For piping length below 7.5m, kindly charge in refrigerant based on serial number sticker on unit.
• When piping length is more than 7.5m, please use the Table 3 below based on liquid pipe size per meter
length.
Liquid Pipe Size (in) Additional Charge (kg/m)
3/8 0.06
1/2 0.10
5/8 0.16
3/4 0.25
Table 3: Additional Charge

17