Maintenance / Testing and Commissioning
Measurement of insulation resistance (IR) — 2
Home / Technical Articles / Measurement of insulation resistance (IR) — 2
Fluke insulation resistance tester up to 10kV
Continued from frat part: Measurement of insulation resistance (IR) — Part 1Insulation Resistance (IR) Values — Index
. IR Values For Electrical Apparatus & Systems
IR Value for Transformer
be ger
|. IR Value for Electric motor
1. IR Values For Electrical Apparatus & Systems
(PEARL Standard / NETA MTS-1997 Table 10.1)
Megger | Min.JR
Size | Value
50 Volts 500 Volts | 25 MO
(00 Volts 4,000 | 100 Mo
Volts
BK 2,500 {1,000 Ma
Volts
BK 2,500 {2,000 MO
Volts
5 KV 2,500 {5,000 M0
Volts
ps5 KV 5,000 | 20,000
Volts ma
B5 KV 15,000 | 100,000
Volts ma
he Kv 15,000 | 100,000
Volts ma
fo KV 15,000 | 100,000
Volts ma
‘One Meg ohm Rule for IR Value for Equipment
Based upon equipment rating:
< 1K V = 1 MQ minimum
>AKV = 1 MQ MIKV
As per IE Rules-1956At a pressure of 1000 V applied between each live conductor and garth for @ period of ane minute the
insulgtion resistance of HV installations shall be at least 1 Mega ohm or as specified by the Bureau of Indian
Standards.
Medium and Low Voltage Installations- At a pressure of 500 V applied batween each live conductor and earth
for a period of one minute, the insulation resistance of medium and low voltage installations shall be al least 1
Mega ohm or as specified by the Bureau of Indian Standards] from time to time.
As per CBIP specifications the acceptable values sre 2 Mega ohms per KV
2. IR Value for Transformer Indext.
Insulation resistance tests are made to determine insulation resistance from individual windings to ground or
between individual windings. Insulation resistance fests are commonly measured directly in megahms or may
be calculated from measurements of applied voltage and leakage current.
The recommended practice in measuring insulation resistance is to always ground the tank (and the core).
Short circuit each winding of the transformer at the bushing terminals. Resistance measurements are then
made between each winding and all other windings grounded.
IR Testing (HV-Earth) IR Testing (HV-LV_)
Insulation resistance testing: HV — Earth and HV — LV
‘Transformer windings are never left floating for insulation resistance measurements. Solidly grounded winding
must have the ground removed in order to measure the insulation resistance of the winding grounded. If the
ground cannot be removed, as in the case of some windings with solidly grounded neutrals, the insulation
resistance of the winding cannot be measured. Treat if as part of the grounded section of the circuit.
We need ta test winding to winding and winding to ground ( E ).For three phase transformers, We need to
test winding ( L1,L2,L3 ) with substitute Earthing for Delta transformer or winding ( L1,L2,L3 ) with earthing (
E ) and neutral (N ) for wye transformers.