You are on page 1of 1

THE WORK SHALL BE EXECUTED IN THE BEST MOST THROUGH MANNER UNDER THE SUSPENSION OF

A REGISTERED ELECTRICAL ENGINEER AND TO THE SATISFACTION OF THE OWNER, ARCHITECT AND
ENGINEER.

THE WORK SHALL BE DONE IN ACCORDANCE WITH THE RULES AND REGULATION OF THE LATEST EDITION
OF THE PHILIPPINE ELECTRICAL CODE (PEC) OF THE LOCAL AUTHORITIES CONCERNED AND THE
REQUIREMENT OF THE LOCAL POWER UTILITY COMPANY, EXCEPT WHEN THESE SHALL CONFLICT WITH
THIS SUCH CODE ETC.

SMALLEST SIZE OF WIRE AND CONDUIT SHALL BE 1.6MM Ø (# 14 AWG) TW WIRE, WIRE SHALL BE
INSULATED FOR 600 VOLTS AND MANUFACTURED BY PHELPS DODGE OR EQUIVALENT. CONDUIT SHALL
BE PVC COILLABLE MOLDFLEX OR EQUIVALENT APPROVED BY THE DESIGNER.
EXCEPT FOR THE POWER SERVICE ENTRANCE. SIZE OF WIRES ARE AS INDICATED IN THE PLANS.

ALL MATERIALS TO BE USED SHALL BE BRAND NEW AND WITH THE APPROVED TYPE FOR THE
PURPOSE AND LOCATION WITH PROPER FITTINGS AND SUPPORT. ELECTRICAL RUN SHALL BE DONE ON
THE NEAREST DISTANCE POSSIBLE, PROVIDE JUNCTION OR PULL BOXES OF PROPER SIZE ALTHOUGH
NOT INDICATED IN THE PLANS

WALL SWITCHES AND POWER RECEPTACLES FOR GENERAL USE SHALL BE 2 WIRE, 250 V. 15 A/10 A
RESPECTIVELY, EXCEPT FOR THE SPECIAL OUTLETS FOR RANGE, HEATER & ACU, WIRE SHALL BE 5.5MM
THW WIRE 1-1.6MM NEUTRAL WIRE. ALL DEVICES MANUFACTURED BY NATIONAL WITH MODERN
PLATE OR APPROVED EQUIVALENT.

MOUNTING HEIGHTS OF DEVICES SHALL BE AS FOLLOWS:

PANEL = 1820MM ABOVE FFL TO BOTTOM OF PANEL BOARD


BOARD 200MM FROM WALL TO OUTER EDGE OF THE DEVICE

WALL = 1400MM ABOVE FFL TO CENTER OF DEVICES AND 4 INCH DISTANCE


SWITCHES FROM CORNER OR DOOR JAMB TO CENTER OF DEVICE

CONVINIENCE =INDICATED ON PLAN, SEE MOUNTING HEIGHT


OUTLET

METER = 1800 MM ABOVE FFL TO CENTER OF METER SOCKET


SOCKET

SERVICE = 4-5 MTR. ALONG & ACROSS PUBLIC ROAD & DRIVEWAYS, SUBJECT
DROP FOR CITY MUNICIPALITY AND POWER UTILITIES APPROVAL.