A REGISTERED ELECTRICAL ENGINEER AND TO THE SATISFACTION OF THE OWNER, ARCHITECT AND
ENGINEER.
THE WORK SHALL BE DONE IN ACCORDANCE WITH THE RULES AND REGULATION OF THE LATEST EDITION
OF THE PHILIPPINE ELECTRICAL CODE (PEC) OF THE LOCAL AUTHORITIES CONCERNED AND THE
REQUIREMENT OF THE LOCAL POWER UTILITY COMPANY, EXCEPT WHEN THESE SHALL CONFLICT WITH
THIS SUCH CODE ETC.
SMALLEST SIZE OF WIRE AND CONDUIT SHALL BE 1.6MM Ø (# 14 AWG) TW WIRE, WIRE SHALL BE
INSULATED FOR 600 VOLTS AND MANUFACTURED BY PHELPS DODGE OR EQUIVALENT. CONDUIT SHALL
BE PVC COILLABLE MOLDFLEX OR EQUIVALENT APPROVED BY THE DESIGNER.
EXCEPT FOR THE POWER SERVICE ENTRANCE. SIZE OF WIRES ARE AS INDICATED IN THE PLANS.
ALL MATERIALS TO BE USED SHALL BE BRAND NEW AND WITH THE APPROVED TYPE FOR THE
PURPOSE AND LOCATION WITH PROPER FITTINGS AND SUPPORT. ELECTRICAL RUN SHALL BE DONE ON
THE NEAREST DISTANCE POSSIBLE, PROVIDE JUNCTION OR PULL BOXES OF PROPER SIZE ALTHOUGH
NOT INDICATED IN THE PLANS
WALL SWITCHES AND POWER RECEPTACLES FOR GENERAL USE SHALL BE 2 WIRE, 250 V. 15 A/10 A
RESPECTIVELY, EXCEPT FOR THE SPECIAL OUTLETS FOR RANGE, HEATER & ACU, WIRE SHALL BE 5.5MM
THW WIRE 1-1.6MM NEUTRAL WIRE. ALL DEVICES MANUFACTURED BY NATIONAL WITH MODERN
PLATE OR APPROVED EQUIVALENT.
SERVICE = 4-5 MTR. ALONG & ACROSS PUBLIC ROAD & DRIVEWAYS, SUBJECT
DROP FOR CITY MUNICIPALITY AND POWER UTILITIES APPROVAL.