Landmark Lofts Ltd Calculation Page Ref: Date: Calcs By:

13 Ensign House Page 12 02 Nov 2012 WC


Admirals Way
Canary Wharf Project:
London E14 9XQ 10 Wolsey Drive, Kingston, KT2 5DN

Description: SFB2

Dead Load= 0.55 kn/m^2 x 3.00 = 0.83 kn/m


(Flat Roof) 2

Live Load= 0.75 kn/m^2 x 3.00 = 1.13 kn/m


(Flat Roof) 2

Dead Load= 0.50 kn/m^2 x 4.40 = 1.10 kn/m (Partial Udl)


(Floor Load) 2

Live Load= 1.50 kn/m^2 x 4.40 = 3.30 kn/m (Partial Udl)


(Floor load) 2

Design Udl= ( 1.4 x ( 0.83 + 1.10 + 0.4 )) + ( 1.6 x ( 1.13 + 3.30 ))

Design Udl= 10.34 kn/m Span of beam= 5.70 m

Maximum Bending Moment = 42.4 kn.m (See Superbeam calcs)

Try a 152 x 152 x 37 UC

Moment Capacity = 84.90 kn.m > 42.40 kn.m Ok in Bending

Deflection

Δ = 5.w.l^4 Span of beam= 5.70 m


384.E.I

w=unfactored imposed load only

From Super beam Calcs Unfactored Live load deflection = 58.7 x 10^8 / EI

Δ = 58.70 x 10^8 = 12.96 mm


205000 x 2210
Table 5 BS5950
Allowable deflection = span = 5700 = 15.83 mm
360 360