Professional Documents
Culture Documents
WA - Checking + Testing Electrical Installation Wo PDF
WA - Checking + Testing Electrical Installation Wo PDF
AND TESTING
ELECTRICAL
INSTALLING
WORK
Office of Energy
CHECKING AND TESTING ELECTRICAL INSTALLING WORK
Preface
It is a requirement of the Electricity (Licensing) Regulations 1991 that all
electrical installing work carried out in Western Australia complies with the
relevant standards, including Australian/New Zealand Standard AS/NZS
3000:2000 (known as the Wiring Rules) and the WA Electrical Requirements.
This booklet has been produced as a guide to meet the checking and testing
requirements for electrical installing work, as specified in the Wiring Rules. Whilst
the details are focussed on domestic electrical installations, the principles apply
to all electrical installing work.
The testing methods in this booklet are not exclusive. Other test methods may be
used provided that they meet the minimum requirement of the Wiring Rules.
Table of Contents
Checking, Testing and Certification of Electrical Installing Work 1
1. Visual Inspection 5
4. Polarity/Functional Test 10
Test Equipment 10
Test Procedure 10
7. Verification of RCD 12
Test Equipment 13
Further Information 16
Notes 17
CHECKING AND TESTING ELECTRICAL INSTALLING WORK
4
CHECKING AND TESTING ELECTRICAL INSTALLING WORK
1. When the electrical installing work has been completed, a licensed electrician
(which may be the contractor or an employee) is required to carry out checks
and tests of the installation, to ensure the electrical work meets the
requirements of the Wiring Rules. The checking and testing should be carried
out in accordance with a formalised checking and testing procedure.
2. Once these checks and tests have been completed, the electrician confirms
on the relevant section of the Notice of Completion or Notice of Completion-
Minor Work, that the checking and testing has been carried out.
3. For electrical installing work that requires the supply authority to attend
(eg. for electricity supply connection or alteration to the supply service
apparatus), the electrician then completes an Installation Test Certificate and
fixes it inside the meter enclosure of the installation.
4. Then, in the usual manner, the electrical contractor (or nominee) completes
the Notice of Completion, thereby certifying the work, and submits the Notice
to the supply authority.
Notes
1
CHECKING AND TESTING ELECTRICAL INSTALLING WORK
The electrician is requested to record the following key installation test results
and the underground consumerÕs mains cable route on a self adhesive label
which is also to be placed inside the meter enclosure:
¥ either the earth continuity or fault-loop impedance values for each sub circuit;
and
The information will benefit subsequent electrical work and inspection, as well as
assist in preventing electric shocks and accidents.
2
CHECKING AND TESTING ELECTRICAL INSTALLING WORK
INSTALLATION TEST
CERTIFICATE
Installation Address: _________________________
This work has been carried out for and on behalf of:
Electrical contractor’s name and licence No.
3
CHECKING AND TESTING ELECTRICAL INSTALLING WORK
¥ the electrical work has been carried out in accordance with the Electricity
(Licensing) Regulations 1991; and
¥ the installation has been checked and tested and is safe for connection to
the electricity supply.
To achieve this, the following minimum checks and tests should be carried out by
the electrician:
1. Visual Inspection - should be carried out whilst referring to a plan (to ensure
a systematic check to pick up any omissions and to verify that the work
complies with the requirements of the applicable standards).
2. Earth Resistance and Continuity Tests - this test is to include the main
earthing conductor, protective earth conductor and bonding conductor.
5. Correct circuit connections - this test checks earthing conductors do not carry
current during normal operation and no short circuit exists.
6. Fault Loop Impedance - measures the fault loop impedance of each circuit to
verify the protective device will operate.
4
CHECKING AND TESTING ELECTRICAL INSTALLING WORK
1. Visual Inspection
A visual inspection is carried out to ensure that all work has been correctly
completed, by checking that:
¥ all cables and equipment have been correctly installed and terminated, and
¥ the installation complies with the relevant parts of the Wiring Rules and the
WA Electrical Requirements.
The resistance from any point of the electrical installation required to be earthed,
to the point where the main earthing conductor is connected to the neutral
conductor (MEN connection) of the supply system, shall be low enough to permit
the passage of current necessary to operate the circuit protective devices. To
confirm this value (which is dependent upon the type and rating of the protective
device and the fault-loop impedance of the associated conductors) requires the
following test to be performed:
5
CHECKING AND TESTING ELECTRICAL INSTALLING WORK
Test 1: Obtain the resistance value of the protective earthing conductor using a
quality ohm meter (see next page for procedure) and compare this value
with the maximum allowable resistance as tabulated in Table 1, page 18
of this booklet.
Test 2: Obtain the fault-loop impedance of each sub circuit using a quality fault-
loop impedance meter (refer to manufacturerÕs instructions and page 15
of this booklet for procedure). Compare the measured fault-loop
impedance value with the maximum value provided at Appendix B,
Table B4.1 of the Wiring Rules.
Notes:
1 If an RCD operates during the test, the test result is considered
satisfactory.
2 If the value measured is GREATER than the allowable maximum then
the following steps must be performed:
Test 2.1 Check the MEN connection, active, neutral and earth
conductor/equipment connections are all solidly made.
Repeat the fault-loop impedance test 2, above.
If the fault-loop impedance values exceed the requirements
of Table B4.1, then perform Test 2.2
Test 2.2 Perform the earth continuity measurement, Test 1 and
confirm results.
Repeat the fault-loop impedance Test 2, above. If the fault-loop
impedance values do not satisfy the requirements of Table B4.1
then you must contact the supply authority advising them of the
discrepancy.
The resistance from the earthing electrode to the point where the main earthing
conductor is connected to the neutral conductor of the supply system shall not
exceed 0.5 ohms.
Test Equipment
¥ A multimeter set to ohms.
6
CHECKING AND TESTING ELECTRICAL INSTALLING WORK
Test Procedure
Preparation:
3. Connect a standard length test lead to the other terminal of the ohm meter
(short lead).
5. Disconnect the water pipe equipotential bonding conductor and the water
heater earthing conductor (if applicable).
Care must be taken that there are no parallel earth paths when
conducting this test, ie. the earthing system must not be connected to
either the water or gas pipes.
6. Disconnect the MEN link from the main neutral link and connect it to the long
lead (ie. long lead now connected to the earth bar).
¥ Connect the short lead to the earth electrode and measure the earth
resistance of the main earthing conductor.
¥ The resistance shall not exceed 0.5 ohms for the main earthing conductor.
¥ Using the long lead and zeroed multimeter, measure, for each circuit, the
earth conductor resistance from the circuit extremity to the switchboard.
¥ Confirm the measured values are LESS THAN those values as provided at
Table 1, page 18 of this booklet for each sub circuit.
¥ This test is applicable to all circuits, including socket outlet circuits, lighting
circuits and fixed equipment (eg. water heater supply) circuits.
7
CHECKING AND TESTING ELECTRICAL INSTALLING WORK
This does not preclude the use of appliances incorporating heating elements
provided that, when tested with all elements in circuit, the insulation resistance
between live parts and the earthing terminal or earthing contact of the appliance
is not less than 0.01 Megohm (10,000 ohms).
Note: Whilst the minimum reading is 1 Megohm, the ideal reading is infinity.
This indicates a sound installation.
Test Equipment
Where the supply voltage does not exceed 250 volts between conductors and
earth, a 500 volt insulation tester should be used to perform this test.
Test Procedure
1. Ensure that all protective devices are in circuit and that all switches are on. If
there are two way lighting circuits in the installation, tests must be carried out
with the two way switches in all positions, so all circuit conductors are tested.
3. Connect one lead of the insulation tester to the main earthing bar (MEN Link
disconnected) and the other lead to the actives and neutrals connected
together. Do not test between actives and neutrals.
8
CHECKING AND TESTING ELECTRICAL INSTALLING WORK
b) Attach an Òout of serviceÓ tag to the circuit protection device, advising that
the circuit has been disconnected due to low insulation resistance.
c) Check that the earth conductor has been reconnected at the MEN point.
Ensure that all circuits and the MEN connection are re-connected when the
testing is complete.
9
CHECKING AND TESTING ELECTRICAL INSTALLING WORK
4. Polarity Test
Polarity tests are carried out to ensure the correct connection of active, neutral
and earth conductors to electrical equipment and to ensure that switches are not
installed in neutral conductors. Clause 6.3.3.4 ÒPolarityÓ of the Wiring Rules
specifies the testing requirements for this mandatory test.
Test Equipment
To carry out these tests, a continuity tester such as a multimeter (set to ohms)
should be used.
Test Procedure
To ensure that the installation circuits/equipment will function as intended, it is
necessary that the following tests be performed:
¥ Isolate the active conductors by turning the main switch OFF and tagging.
¥ Confirm active conductor switching by using an ohm meter with the long lead
connected to the active conductor at the switchboard and the short lead
connected to the switch terminals (one at a time) in the following manner:
i) Switch ON Å 0 ½ for both terminals
ii) Switch OFF Å 0 ½ for one terminal and ÔinfinityÕ for the other terminal
¥ With the MEN link in place, confirm the polarity of socket outlets using a 10½
resistor and an ohm meter. Connect the 10½ resistor between the circuit
active conductor and the neutral bar then at each socket outlet connect one
lead of the multimeter to the earth terminal and the second lead to the active
terminal. Test the resistance value for:
i) socket outlet switch OFF = ÔinfinityÕ
ii) socket outlet switch ON = 10½.
10
CHECKING AND TESTING ELECTRICAL INSTALLING WORK
3. for the circuit continuity test to prove each circuit for electrical continuity and
that all switches operate in the active conductors.
Test Equipment
To perform the fault-loop impedance test, a fault-loop impedance meter is
required.
Test Procedure
¥ Energise all circuits
¥ The measured value must be less than the maximum values as tabulated at
Table B4.1 of the Wiring Rules
¥ If an RCD operates during the test, the test result can be considered
satisfactory.
11
CHECKING AND TESTING ELECTRICAL INSTALLING WORK
Warning: Operation of the integral test device does not provide a means of
checking:
The tests described in this booklet must also be carried out on alterations and
additions to ensure the electrical installing work is safe to remain connected to
the electrical installation.
The majority of tests described in this booklet are designed to be carried out
without power being connected. When performing these tests, make sure that
electricity supplies are disconnected where necessary and that the appropriate
isolation and tagging has been carried out.
12
CHECKING AND TESTING ELECTRICAL INSTALLING WORK
Test Equipment
Before performing any tests, ensure that the test equipment is correctly set, is
functional and is in good condition, particularly the test leads.
Some types of test equipment (eg. multimeters) are fitted with fuse
protection. Ensure that at all times only the correct type and rated fuse is
used. This is for your protection.
13
CHECKING AND TESTING ELECTRICAL INSTALLING WORK
Table 1
Maximum resistance values of final sub circuit protective earthing conductors.
Circuit - breakers
Protective Fuses
Type B Type C Type D
Device Earthing Disconnection times
Rating Conductor
Size 0.4sec 0.4sec
A mm 2 Maximum final subcircuit earth conductor
resistance ½
6 1 3.08 1.65 1.00 3.69
10 1.5 1.85 1.00 0.60 2.06
16 2.5 1.16 0.62 0.38 0.99
20 2.5 0.93 0.50 0.30 0.68
25 2.5 1.07 0.57 0.34 0.76
32 2.5 0.72 0.38 0.23 0.51
40 2.5 0.66 0.35 0.21 0.44
50 4 0.54 0.29 0.17 0.34
63 4 0.44 0.23 0.14 0.26
14
CHECKING AND TESTING ELECTRICAL INSTALLING WORK
Table 2
Comparison of voltage drop and fault-loop impedance to determine circuit
maximum distance.
This table details the single phase voltage drop for a combination of conductor
size, maximum demand current and distance. It also displays the maximum
circuit length for a Type ÔCÕ circuit breaker (as normally used in most installations)
to ensure the operation of the circuit breaker during a earth fault. You will notice
that compliance for voltage drop is the predominant requirement compared to the
fault-loop distance for the given circuit breaker type.
Maximum Distance
Distance
Conductor Protective Maximum m
Size Device Demand 20m 30m 40m 60m 80m For For Type C
Rating Voltage Drop Voltage Circuit
Drop #2 Breaker #3
mm2 A A #1 V (11.5V = maximum)
10 10.3 - - - - 22* 55
1.0 10
5 5.2 7.7 10.3 - - 45* 55
10 6.6 9.9 - - - 35* 82
1.5 10
5 3.3 5.5 6.6 9.9 - 70* 82
16 5.8 8.6 - - - 40* 85
2.5 16
8 2.9 4.3 5.8 8.6 - 80* 85
25 5.6 8.4 11.2 - - 41* 67
4.0 25
12.5 2.8 4.2 5.6 8.4 10.2 82 67*
* Denotes limiting parameter
Notes:
#1: Maximum demand determined using (a) full load, and (b) half the rating of
the protective device assuming distributed load. Refer to Wiring Rules
Clause 3.6.2
15
CHECKING AND TESTING ELECTRICAL INSTALLING WORK
Further Information
For further information on testing electrical installing work, please contact the
Electrical Inspector at the relevant supply authority, as listed in the manual ÒWA
Electrical RequirementsÓ.
OFFICE OF ENERGY
20 Southport Street
WEST LEEDERVILLE WA 6007
Email: licensing@energy.wa.gov.au
Website: www.energy.wa.gov.au
16
Issued by