Feeder Protection and Control REF630: Product Guide
Feeder Protection and Control REF630: Product Guide
Contents
Disclaimer
The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any
errors that may appear in this document.
© Copyright 2015 ABB.
All rights reserved.
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
2 ABB
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3 Issued: 2015-03-31
Revision: G
2. Application
REF630 provides main protection for overhead lines and
cable feeders of distribution networks. The IED fits both
ABB 3
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
REF630
Preconf. n
Io ANSI IEC
27 3U<
Uo 51BF/51NBF 3I>/Io>BF
3U 51N-1/51N-2 Io>/Io>>
3I 59 3U>
67-1 3I>→
Bus A
Bus B
3U 3U
Uo Uo
3I 3I 3I 3I
Io Io Io Io
21FL FLOC 47O-/59 U2>/3U> 47O-/59 U2>/3U> 21FL FLOC 21FL FLOC 21FL FLOC
46 I2> 47U+/27 U1</3U< 47U+/27 U1</3U< 46 I2> 46 I2> 46 I2>
46PD I2/I1> 59G Uo> 59G Uo> 46PD I2/I1> 46PD I2/I1> 46PD I2/I1>
49F 3Ith>F 81O/81U/81R f</f>/ df/dt 81O/81U/81R f</f>/ df/dt 49F 3Ith>F 49F 3Ith>F 49F 3Ith>F
50N/51N 3Io>>> 50N/51N 3Io>>> 50N/51N 3Io>>> 50N/51N 3Io>>>
50P/51P 3I>>> 50P/51P 3I>>> 50P/51P 3I>>> 50P/51P 3I>>>
51BF/51NBF 3I>/Io>BF 51BF/51NBF 3I>/Io>BF 51BF/51NBF 3I>/Io>BF 51BF/51NBF 3I>/Io>BF
51N-1/51N-2 Io>/Io>> 51N-1/51N-2 Io>/Io>> 51N-1/51N-2 Io>/Io>> 51N-1/51N-2 Io>/Io>>
51P-1/51P-2 3I>/3I>> 51P-1/51P-2 3I>/3I>> 51P-1/51P-2 3I>/3I>> 51P-1/51P-2 3I>/3I>>
60 FUSEF 60 FUSEF 60 FUSEF 60 FUSEF
67N-1 Io>→ 67N-1 Io>→ 67N-1 Io>→ 67N-1 Io>→
68 3I2f> 68 3I2f> 68 3I2f> 68 3I2f>
79 O→I 79 O→I
GUID-2D5D5EDF-BA34-4545-8116-7D4BAB6EFC27 V1 EN
Figure 1. Application example with double busbar switchgear arrangement with one incoming feeder and several outgoing feeders for
overhead line and cable feeders in preconfiguration n
4 ABB
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
REF630
Preconf. n
Io ANSI IEC
47O-/59 U2>/3U>
47U+/27 U1</3U<
Uo
51BF/51NBF 3I>/Io>BF
3U 59G Uo>
3I
67-1/67-2 3I>→/3I>>→
81O f>
81LSH UFLS/R
Bus A
Bus B
3I 3I 3I 3I
Io 3U Uo Io 3U Uo Io 3U Uo Io 3U Uo
GUID-E52499B7-DF0A-46D4-B120-97203A34F91A V1 EN
Figure 2. Application example in double busbar, also so called back 2 back, switchgear arrangement with dedicated voltage measurement
in each feeder
ABB 5
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
REF620
Preconf. C
ANSI IEC
27 3U<
51BF/51NBF 3I>/Io>BF
Io 51N-1/51N-2 Io>/Io>>
67-1 3I>→
59 3U>
81O/81U/81R f</f>/ df/dt
Uo
3U
3I
Bus A
Bus B
2U
2U
3I 3I 3I 3I 3I
Io 3U Uo Io 3U Uo Io 3U Uo Io 3U Uo
21, 21P, 21N Z< 21, 21P, 21N Z< 21, 21P, 21N Z< 21, 21P, 21N Z< 25 SYNC
27/59 3U</3U> 27/59 3U</3U> 27/59 3U</3U> 27/59 3U</3U> 47O-/59 U2>/3U>
46 I2> 46 I2> 46 I2> 46 I2> 47U+/27 U1</3U<
46PD I2/I1> 46PD I2/I1> 46PD I2/I1> 46PD I2/I1> 50P/51P 3I>>>
49F 3Ith>F 49F 3Ith>F 49F 3Ith>F 49F 3Ith>F 51BF/51NBF 3I>/Io>BF
50N/51N 3Io>>> 50N/51N 3Io>>> 50N/51N 3Io>>> 50N/51N 3Io>>> 51P-1/51P-2 3I>/3I>>
50P/51P 3I>>> 50P/51P 3I>>> 50P/51P 3I>>> 50P/51P 3I>>>
51BF/51NBF 3I>/Io>BF 51BF/51NBF 3I>/Io>BF 51BF/51NBF 3I>/Io>BF 51BF/51NBF 3I>/Io>BF
51N-1/51N-2 Io>/Io>> 51N-1/51N-2 Io>/Io>> 51N-1/51N-2 Io>/Io>> 51N-1/51N-2 Io>/Io>>
51P-1/51P-2 3I>/3I>> 51P-1/51P-2 3I>/3I>> 51P-1/51P-2 3I>/3I>> 51P-1/51P-2 3I>/3I>>
59G Uo> 59G Uo> 59G Uo> 59G Uo>
60 FUSEF 60 FUSEF 60 FUSEF 60 FUSEF
67N-1/67N-2 Io>→/Io>>→ 67N-1/67N-2 Io>→/Io>>→ 67N-1/67N-2 Io>→/Io>>→ 67N-1/67N-2 Io>→/Io>>→
68 3I2f> 68 3I2f> 68 3I2f> 68 3I2f>
79 O→I 79 O→I 79 O→I 79 O→I
SOFT SOFT SOFT SOFT SOFT SOFT SOFT SOFT
GUID-05EAB48E-56BE-4C20-98D5-24A5643A175B V1 EN
Figure 3. Application example in double busbar arrangement, most typical, for gas insulated switchgear with 3 position disconnector and
voltage measurement in each feeder
The bus sectionalizer with also independent voltage sections. Preconfiguration C with its distance protection is
measurement on both busbars allows switchgear operation preconfigured for ring and meshed type feeders.
while maintenance works are required on one of the busbar
6 ABB
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
REF630 REF630
Preconf. n Preconf. n
Io ANSI IEC Io ANSI IEC
25 SYNC 25 SYNC
3U 47O-/59 U2>/3U> 3U 47O-/59 U2>/3U>
Uo 47U+/27 U1</3U< Uo 47U+/27 U1</3U<
50P/51P 3I>>> 50P/51P 3I>>>
3I 3I
51BF/51NBF 3I>/Io>BF 51BF/51NBF 3I>/Io>BF
51P-1/51P-2 3I>/3I>> 51P-1/51P-2 3I>/3I>>
59G Uo> 59G Uo>
67-1 3I>→ 67-1 3I>→
3I 3I 3I 3I
3U Uo 3U Uo
Io Io Io
GUID-D1305B07-E9C9-4353-A69F-253D93273E7D V1 EN
Figure 4. Application example with single busbar switchgear arranged into two bus sections separated with bus coupler
High impedance earthed network with preconfigurations N synchrocheck functionality is used to prevent unsynchronized
and directional overcurrent and directional earth-fault connection of two separate networks into each other.
functions are used. In incoming feeders and bus coupler the
ABB 7
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
8 ABB
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
UL1UL2UL3
Uo
2× AND
3I OR
I2> I2/I1> 3Ith>F 3I>>>
46 46PD 49F 50P/51P *) Fixed or detached LHMI is available.
1× 1× 2×
3I>/Io>BF 3I> 3I>>
CONDITION MONITORING COMMUNICATION
51BF/51NBF 51P-1 51P-2
AND SUPERVISION
Protocols: 1 0 1 0 0 0 1 1 0 0 1 1 0 0
2× 1× 1× 1× 1× IEC 61850-8-1 1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
3I>→ 3I>>→ 3I2f> FUSEF CBCM E IEC 60870-5-103 1 1 0 0 1 1 1 0 1 1 0 1 0
67-1 67-2 68 60 CBCM E DNP3 1 0 1 1 0 1 1 0 1 1 0 1 0 0
1 0 1 0 0 0 1 1 0 0 1 1 0 0 1 0 1
1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
Interfaces: 1 1 0 0 1 1 1 0 1 1 0 1 0
UL1UL2UL3 1× 1× 3×
Ethernet: TX (RJ45),
1 0FX1(LC)
1 0 1 1 0 1 1 0 1 0 0
MCS 3I OPTS TCS
Serial: Serial glass fiber (ST),
MCS 3I OPTM TCM
Serial plastic fiber
(snap-in connector)
Io 2× 1×
Io>> Io>→ Io>→ Io>→IEF U<>
51N-2 67N-1 67N-2 67NIEF U<>
Uo
CONTROL AND INDICATION 1) MEASUREMENT
3×
Z< FLOC Yo>→ Object Ctrl 2) - I, U, Io, Uo, P, Q, E, pf, f
21, 21P, 21N 21FL 21YN - Symmetrical components
CB 2 - Limit value supervision
3× 3× DC
3U< Po>→ 8
Q>→, 3U< ES Analog interface types B
27 32N 32Q, 27
1)
Check availability of binary inputs/outputs Current transformer 51)
from technical documentation
3× 2× 2× 2× 2)
Control and indication function for Voltage transformer 4
P> U2> U1> U1< primary object
1)
One of available current transformer
32R/32O 47O- 47O+ 47U+ inputs is sensitive (0.1 / 0.5 A)
3× 1× 1×
Io>>> Io> Io>HA 3U> O→I SYNC PQM3I PQM3Upe
50N/51N 51N-1 51NHA 59 79 25 PQM3I PQM3Vpg
3× 6× 5×
Uo> Io>→Y UFLS/R f> PQM3Upp
59G 67YN 81LSH 81O PQM3Vpp
5× 5× 16× 2×
df/dt> f< MAP SOTF PQMUBU PQMU
81R 81U MAP SOTF PQMUBV PQMV
REMARKS
Optional 2× No. of instances
function enabled by default
GUID-973EE09F-BEFA-40C3-AAEE-FB97B84EAA52 V1 EN
ABB 9
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
UL1UL2UL3
Uo
2× AND
3I OR
I2> I2/I1> 3Ith>F 3I>>>
46 46PD 49F 50P/51P *) Fixed or detached LHMI is available.
1× 1× 2×
3I>/Io>BF 3I> 3I>>
CONDITION MONITORING COMMUNICATION
51BF/51NBF 51P-1 51P-2
AND SUPERVISION
Protocols: 1 0 1 0 0 0 1 1 0 0 1 1 0 0
1× 1× 1× 1× IEC 61850-8-1 1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
3I2f> FUSEF CBCM E IEC 60870-5-103 1 1 0 0 1 1 1 0 1 1 0 1 0
68 60 CBCM E DNP3 1 0 1 1 0 1 1 0 1 1 0 1 0 0
1 0 1 0 0 0 1 1 0 0 1 1 0 0 1 0 1 0 0
1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
Interfaces: 1 1 0 0 1 1 1 0 1 1 0 1 0
UL1UL2UL3 1× 1× 3×
Ethernet: TX (RJ45),
1 0FX1(LC)
1 0 1 1 0 1 1 0 1 0 0
MCS 3I OPTS TCS
Serial: Serial glass fiber (ST),
MCS 3I OPTM TCM
Serial plastic fiber
(snap-in connector)
Io 1× 2×
Io>>> Io> Io>> Io>→ U<>
50N/51N 51N-1 51N-2 67N-1 U<>
Uo
CONTROL AND INDICATION 1) MEASUREMENT
3×
Z< FLOC Yo>→ Object Ctrl 2) - I, U, Io, Uo, P, Q, E, pf, f
21, 21P, 21N 21FL 21YN - Symmetrical components
CB 2 - Limit value supervision
3× 3× DC
8
3U< Po>→ Q>→, 3U< ES Analog interface types B
27 32N 32Q, 27 1)
Check availability of binary inputs/outputs Current transformer 51)
from technical documentation
3× 2× 2× 2× 2)
Control and indication function for Voltage transformer 4
P> U2> U1> U1< primary object
1)
One of available current transformer
32R/32O 47O- 47O+ 47U+ inputs is sensitive (0.1 / 0.5 A)
3× 3× 2× 1× 1×
Io>HA 3U> Uo> 3I>→ O→I SYNC PQM3I PQM3Upe
51NHA 59 59G 67-1 79 25 PQM3I PQM3Vpg
6× 5× 5× 5×
UFLS/R f> df/dt> f< PQMUBU PQMU
81LSH 81O 81R 81U PQMUBV PQMV
16× 2×
MAP SOTF
MAP SOTF
REMARKS
Optional 2× No. of instances
function enabled by default
GUID-041037E1-4C3F-4F83-BFFB-995BA916B55B V1 EN
10 ABB
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
UL1UL2UL3
Uo
3I 2× AND
Z< I2> I2/I1> OR
21, 21P, 21N 46 46PD *) Fixed or detached LHMI is available.
1× 1×
3Ith>F 3I>>> 3I>/Io>BF
CONDITION MONITORING COMMUNICATION
49F 50P/51P 51BF/51NBF
AND SUPERVISION
Protocols: 1 0 1 0 0 0 1 1 0 0 1 1 0 0
2× 1× 1× 1× 1× IEC 61850-8-1 1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
3I> 3I>> 3I2f> FUSEF CBCM E IEC 60870-5-103 1 1 0 0 1 1 1 0 1 1 0 1 0
51P-1 51P-2 68 60 CBCM E DNP3 1 0 1 1 0 1 1 0 1 1 0 1 0 0
1 0 1 0 0 0 1 1 0 0 1 1 0 0 1 0 1
1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
Interfaces: 1 1 0 0 1 1 1 0 1 1 0 1 0
UL1UL2UL3 1× 1× 3×
Ethernet: TX (RJ45),
1 0FX1(LC)
1 0 1 1 0 1 1 0 1 0 0
MCS 3I OPTS TCS
Serial: Serial glass fiber (ST),
MCS 3I OPTM TCM
Serial plastic fiber
(snap-in connector)
3×
Io
Io>> Io>→ Io>→ U<>
51N-2 67N-1 67N-2 U<>
Uo
CONTROL AND INDICATION 1) MEASUREMENT
3× 3× 1× 1×
FLOC Yo>→ Po>→ O→I SYNC PQM3I PQM3Upe
21FL 21YN 32N 79 25 PQM3I PQM3Vpg
3× 2×
Q>→, 3U< P> U2> PQM3Upp
32Q, 27 32R/32O 47O- PQM3Vpp
2× 2×
U1> U1< Io>>> Io> PQMUBU PQMU
47O+ 47U+ 50N/51N 51N-1 PQMUBV PQMV
2×
Io>HA 3I>→ 3I>>→ Io>→IEF
51NHA 67-1 67-2 67NIEF
REMARKS
6× 5× 5× Optional 2× No. of instances
Io>→Y UFLS/R f> df/dt> function enabled by default
67YN 81LSH 81O 81R
GUID-A5805D15-8663-4995-B76C-A21248C18FBF V1 EN
ABB 11
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
2× 1× 1× AND
3I OR
I2> 3I>>> 3I>/Io>BF
46 50P/51P 51BF/51NBF *) Fixed or detached LHMI is available.
2×
3I> 3I>> 3I2f>
CONDITION MONITORING COMMUNICATION
51P-1 51P-2 68
AND SUPERVISION
Protocols: 1 0 1 0 0 0 1 1 0 0 1 1 0 0
2× 1× 1× IEC 61850-8-1 1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
Io FUSEF CBCM E IEC 60870-5-103 1 1 0 0 1 1 1 0 1 1 0 1 0
60 CBCM E DNP3 1 0 1 1 0 1 1 0 1 1 0 1 0 0
1 0 1 0 0 0 1 1 0 0 1 1 0 0 1 0 1 0 0
1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
Interfaces: 1 1 0 0 1 1 1 0 1 1 0 1 0
2× 3×
Ethernet: TX (RJ45),
1 0FX1(LC)
1 0 1 1 0 1 1 0 1 0 0
Io>>> Io> Io>> MCS 3I OPTS TCS
Serial: Serial glass fiber (ST),
50N/51N 51N-1 51N-2 MCS 3I OPTM TCM
Serial plastic fiber
(snap-in connector)
U<>
U<>
3×
Z< FLOC Yo>→
21, 21P, 21N 21FL 21YN
CONTROL AND INDICATION 1) MEASUREMENT
3× 3×
3U< Po>→ Q>→, 3U< Object Ctrl 2) - I, U, Io, Uo, P, Q, E, pf, f
27 32N 32Q, 27 - Symmetrical components
CB 2 - Limit value supervision
3× 2× 2× DC
8
P> I2/I1> U2> U1> ES Analog interface types B
32R/32O 46PD 47O- 47O+ 1)
Check availability of binary inputs/outputs Current transformer 51)
from technical documentation
2× 3× 2)
Control and indication function for Voltage transformer 4
U1< 3Ith>F Io>HA 3U> primary object 1)
One of available current transformer
47U+ 49F 51NHA 59 inputs is sensitive (0.1 / 0.5 A)
3× 2× 3× 2×
Uo> 3I>→ 3I>>→ Io>→ O→I SYNC PQM3I PQM3Upe
59G 67-1 67-2 67N-1 79 25 PQM3I PQM3Vpg
6×
Io>→ Io>→IEF Io>→Y UFLS/R PQM3Upp
67N-2 67NIEF 67YN 81LSH PQM3Vpp
5× 5× 5× 16×
f> df/dt> f< MAP PQMUBU PQMU
81O 81R 81U MAP PQMUBV PQMV
2×
SOTF
SOTF REMARKS
GUID-46E0483B-5329-418D-944B-5F75F073A12E V1 EN
12 ABB
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
UL1UL2UL3
Uo
3× 3× 2× AND
3I
Po>→ Q>→, 3U< P> I2> OR
32N 32Q, 27 32R/32O 46 *) Fixed or detached LHMI is available.
2× 2× 2×
I2/I1> U2> U1> U1< 3Ith>F
CONDITION MONITORING COMMUNICATION
46PD 47O- 47O+ 47U+ 49F
AND SUPERVISION
Protocols: 1 0 1 0 0 0 1 1 0 0 1 1 0 0
2× 2× 2× IEC 61850-8-1 1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
Io>>> 3I>>> 3I>/Io>BF Io> FUSEF CBCM E IEC 60870-5-103 1 1 0 0 1 1 1 0 1 1 0 1 0
1 0 1 1 0 1 1 0 1 1 0 1 0 0
50N/51N 50P/51P 51BF/51NBF 51N-1 60 CBCM E DNP3 1 0 1 0 0 0 1 1 0 0 1 1 0 0 1 0
U12 1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
Interfaces: 1 1 0 0 1 1 1 0 1 1 0 1 0
2× 3× 2× 3×
Ethernet: TX (RJ45),1 0 1(LC)
FX 1 0 1 1 0 1 1 0 1 0 0
Io>> Io>HA 3I> 3I>> 3U> MCS 3I OPTS TCS
Serial: Serial glass fiber (ST),
51N-2 51NHA 51P-1 51P-2 59 MCS 3I OPTM TCM
Serial plastic fiber
(snap-in connector)
3× 2× 3×
Uo> 3I>→ 3I>>→ Io>→ Io>→ U<>
Io 59G 67-1 67-2 67N-1 67N-2 U<>
6× 5×
Io>→IEF Io>→Y 3I2f> UFLS/R f>
67NIEF 67YN 68 81LSH 81O CONTROL AND INDICATION 1) MEASUREMENT
2×
O→I SYNC PQM3I PQM3Upe
79 25 PQM3I PQM3Vpg
PQM3Upp
PQM3Vpp
PQMUBU PQMU
PQMUBV PQMV
REMARKS
Optional 3× Total nr. of
function instances
GUID-6BE6503A-F28B-43F9-8195-385F14F3A45D V1 EN
Description Preconfiguration
ABB 13
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
Description A B C D n
Protection
Distance protection - - 1 - 1
Fault locator - - - - 1
Autoreclosing 1 1 1 - 2
Overfrequency protection - - - - 5
Underfrequency protection - - - - 5
Load shedding - - - - 6
14 ABB
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
Tripping logic 1 1 1 1 2
Protection-related functions
Control
Bay control 1 1 1 1 1
Interlocking interface 4 4 4 1 10
Circuit breaker 1 1 1 1 2
Disconnector 3 3 3 - 8
Synchrocheck - - - - 1
Event counter - - - - 1
Trip-circuit supervision 3 3 3 3 3
Energy monitoring - - - - 1
Power quality
Voltage variation - - - - 1
Voltage unbalance - - - - 1
Current harmonics - - - - 1
ABB 15
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
Measurement
Binary receive - - - - 10
Interlock receive - - - - 59
Integer receive - - - - 32
16 ABB
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
independent stages. Apart from the conventional earth-fault and logic circuits for establishing bay control and interlocking
protection, the IED offers wattmetric, admittance-based and functions for circuit breakers and motor operated switch-
harmonics-based earth-fault protection. disconnectors. The IED supports both single and double
busbar substation busbar layouts. The number of controllable
The included transient/intermittent earth-fault protection is primary apparatuses depends on the number of available
based on detection of earth-fault transients related to inputs and outputs in the selected configuration. Besides
continuous or intermittent faults. Intermittent earth-fault is a conventional hardwired signaling also GOOSE messaging
special type of earth-fault encountered in compensated according to IEC 61850-8-1 can be used for signal
networks with underground cables. In solidly earthed or interchange between IEDs to obtain required interlockings.
compensated networks the transient earth-fault protection
function detects earth-faults with low fault resistance. Further, the IED incorporates a synchro-check function to
ensure that the voltage, phase angle and frequency on either
Multi-frequency admittance-based earth-fault protection side of an open circuit breaker satisfy the conditions for safe
provides selective directional earth-fault protection for high- interconnection of two networks.
impedance earthed networks. The operation is based on multi-
frequency neutral admittance measurement utilizing
fundamental frequency and harmonic components in Uo and 6. Fault location
Io. A special filtering algorithm enables dependable and REF630 features an impedance-measuring fault location
secure fault direction also during intermittent/restriking earth function suitable for locating short-circuits in radial
faults. It provides a very good combination of reliability and distribution systems. Earth faults can be located in effectively
sensitivity of protection with a single function for low ohmic and low-resistance earthed networks. Under circumstances
and higher ohmic earth faults and for transient and where the fault current magnitude is at least of the same
intermittent/restriking earth faults. order of magnitude or higher than the load current, earth
faults can also be located in isolated neutral distribution
The residual overvoltage protection, with three independent networks. The fault location function identifies the type of the
stages, is used for earth-fault protection of the substation bus fault and then calculates the distance to the fault point. An
and the incoming feeder, and for backup protection of the estimate of the fault resistance value is also calculated. The
outgoing feeders. estimate provides information about the possible fault cause
and the accuracy of the estimated distance to the fault point.
The IED offers distance protection including both circular
(mho) and quadrilateral (quad) zone characteristics, three
independent zones with separate reach settings for phase-to- 7. Measurement
phase and phase-to-earth measuring elements and two The IED continuously measures the phase currents, positive
zones for controlling autoreclosing of circuit breakers. and negative sequence currents and the residual current. The
Further, the IED offers automatic switch-onto-fault logic with IED also measures phase-to earth or phase-to-phase
voltage and current based detection options. voltages, positive and negative sequence voltages and the
residual voltage. In addition, the IED monitors active, reactive
The IED offers voltage protection functions including three- and apparent power, the power factor, power demand value
phase undervoltage and overvoltage protection with three over a user-selectable pre-set time frame as well as
independent stages each, both with phase-to-phase or phase- cumulative active and reactive energy of both directions. Line
to-earth measurement. The IED also offers overfrequency, frequency, the calculated temperature of the feeder, and the
underfrequency and rate-of-change of frequency protection phase unbalance value based on the ratio between the
to be used in load shedding and network restoration negative sequence and positive sequence current are also
applications. calculated. Cumulative and averaging calculations utilize the
non-volatile memory available in the IED.
The reactive power undervoltage protection (QU) can be used
at grid connection point of distributed power generation units. The values measured are accessed locally via the front-panel
user interface of the IED or remotely via the communication
In addition, the IED offers three-pole multi-shot autoreclose interface of the IED. The values are also accessed locally or
functions for overhead line feeders. remotely using the web-browser based user interface.
The IED incorporates breaker failure protection for circuit
breaker re-tripping or backup tripping for the upstream 8. Disturbance recorder
breaker. The IED is provided with a disturbance recorder featuring up
to 40 analog and 64 binary signal channels. The analog
channels can be set to record the waveform of the currents
5. Control
and voltage measured. The analog channels can be set to
The IED incorporates local and remote control functions. The
trigger the recording when the measured value falls below or
IED offers a number of freely assignable binary inputs/outputs
exceeds the set values. The binary signal channels can be set
ABB 17
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
to start a recording on the rising or the falling edge of the • Negative-sequence voltage magnitude
binary signal. The binary channels are set to record external • Zero-sequence voltage magnitude
or internal IED signals, for example the start or operate • Ratio of negative-sequence to positive-sequence voltage
signals of the protection functions, or external blocking or magnitude
control signals. Binary IED signals such as a protection start • Ratio of zero-sequence to positive-sequence voltage
or trip signal, or an external IED control signal over a binary magnitude
input can be set to trigger the recording. In addition, the • Ratio of maximum phase voltage magnitude deviation
disturbance recorder settings include pre- and post triggering from the mean voltage magnitude to the mean of phase
times. voltage magnitude
18 ABB
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
The monitoring functions provide operational circuit breaker 18. Inputs and outputs
history data, which can be used for scheduling preventive Depending on the hardware configuration selected, the IED is
circuit-breaker maintenance. equipped with three phase-current inputs and one or two
residual-current inputs for earth-fault protection. The IED
always includes one residual voltage input for directional earth-
13. Trip-circuit supervision
fault protection or residual voltage protection. Further, the IED
The trip-circuit supervision continuously monitors the
includes three phase-voltage inputs for overvoltage,
availability and operability of the trip circuit. It provides open-
undervoltage and directional overcurrent protection and other
circuit monitoring both when the circuit breaker is in its
voltage based protection functions. Depending on the
closed and in its open position. It also detects loss of circuit-
hardware configuration, the IED also includes a dedicated
breaker control voltage.
voltage input for synchrocheck.
14. Self-supervision The phase-current inputs are rated 1/5 A. The IED is
The IED’s built-in self-supervision system continuously equipped with one or two alternative residual-current inputs,
monitors the state of the IED hardware and the operation of that is 1/5 A or 0.1/0.5 A. The 0.1/0.5 A input is normally
the IED software. Any fault or malfunction detected is used used in applications requiring sensitive earth-fault protection
for alerting the operator. and featuring a core-balance current transformer.
Self-supervision events are saved into an internal event list The three phase-voltage inputs, for either phase-to-phase
which can be accessed locally via the user interface on the voltages or phase-to-earth voltages, and the residual-voltage
IED front panel. The event list can also be accessed using the input cover the rated voltages 100 V, 110 V, 115 V and 120
Web-browser based user interface or PCM600. V. The rated values of the current and voltage inputs are
selected in the IED software.
15. Fuse failure supervision In addition, the binary input thresholds are selected by
The fuse failure supervision detects failures between the adjusting the IED’s parameter settings. The threshold voltage
voltage measurement circuit and the IED. The failures are can be set separately for each binary input.
detected either by the negative sequence-based algorithm or
by the delta voltage and delta current algorithm. Upon the The optional RTD/mA module facilitates the measurement of
detection of a failure, the fuse failure supervision function up to eight analog signals via the RTD/mA inputs and
activates an alarm and blocks voltage-dependent protection provides four mA outputs. With RTD sensors the RTD/mA
functions from unintended operation. inputs can for instance be used for temperature measurement
stator windings, thus extending the functionality of the
thermal overload protection and preventing premature aging
16. Current circuit supervision of the windings. Furthermore, the RTD/mA inputs can be
Current circuit supervision is used for detecting faults in the used for measuring the ambient air or cooling media
current transformer secondary circuits. On detecting of a fault temperature, or bearing temperatures. The RTD/mA inputs
the current circuit supervision function can also activate an can be used for supervision of analog mA signals provided by
alarm LED and block certain protection functions to avoid external transducers. The RTD/mA inputs can be alternatively
unintended operation. The current circuit supervision function used also as resistance input or as an input for voltage
calculates the sum of the phase currents and compares the transducer. The RTD/mA module enables the use of the
sum with the measured single reference current from a core multipurpose analog protection functions. These protection
balance current transformer or from another set of phase functions can be used for tripping and alarm purposes based
current transformers. on RTD/mA measuring data, or analog values communicated
via GOOSE messaging. The mA outputs can be used for
17. Access control transferring freely selectable measured or calculated analog
To protect the IED from unauthorized access and to maintain values to devices provided with mA input capabilities.
information integrity, the IED is provided with an
The enhanced scalability of the 6U variant IEDs are intended
authentication system including user management. Using the
for optimized medium voltage metal-clad switchgear
IED User Management tool in the Protection and Control IED
applications where additional binary inputs and outputs are
Manager PCM600, an individual password is assigned to
often required.
each user by the administrator. Further, the user name is
associated to one or more of the four available user groups: All binary input and output contacts are freely configurable
System Operator, Protection Engineer, Design Engineer and using the signal matrix of the application configuration
User Administrator. The user group association for each function in PCM600.
individual user enables the use of the IED according to the
profile of the user group.
ABB 19
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
AA 4 - 5 - -
AB 4 1 4 - -
AC 3 1 5 - -
BA 4 - 5 8 4
BB 4 1 4 8 4
BC 3 1 5 8 4
Default AA 14 9
Default AA 14 9
19. Communication 61850 standard. Further, the IED supports the sending and
The IED supports the IEC 61850 substation automation receiving of analog values using GOOSE messaging. Analog
standard including horizontal GOOSE communication as well GOOSE messaging enables fast transfer of analog
as the well-established DNP3 (TCP/IP) and IEC 60870-5-103 measurement values over the station bus, thus facilitating for
protocols. All operational information and controls are example sharing of RTD input values, such as surrounding
available through these protocols. temperature values, to other IED applications. Analog GOOSE
messages can also be used in load shedding applications.
Disturbance files are accessed using the IEC 61850 or IEC The IED interoperates with other IEC 61850 compliant IEDs,
60870-5-103 protocols. Disturbance files are also available to tools and systems and simultaneously reports events to five
any Ethernet based application in the standard COMTRADE different clients on the IEC 61850 station bus. For a system
format. The IED can send binary signals to other IEDs (so using DNP3 over TCP/IP, events can be sent to four different
called horizontal communication) using the IEC 61850-8-1 masters. For systems using IEC 60870-5-103 IED can be
GOOSE (Generic Object Oriented Substation Event) profile. connected to one master in a station bus with star-topology.
Binary GOOSE messaging can, for example, be employed for
protection and interlocking-based protection schemes. The All communication connectors, except for the front port
IED meets the GOOSE performance requirements for tripping connector, are placed on integrated communication modules.
applications in distribution substations, as defined by the IEC The IED is connected to Ethernet-based communication
20 ABB
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
systems via the RJ-45 connector (10/100BASE-TX) or the • SNTP (simple network time protocol)
fibre-optic multimode LC connector (100BASE-FX). • DNP3
IEC 61850 ● ●
DNP3 ● ●
IEC 60870-5-103 ● ●
● = Supported
1) Please refer to the Selection and ordering data chapter for more information
ABB 21
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
Table 7. Dimensions
Description Value
Width 220 mm
Depth 249.5 mm
1) Without LHMI
Uauxnominal 100, 110, 120, 220, 240 V AC, 50 and 60 Hz 48, 60, 110, 125 V DC
Ripple in the DC auxiliary voltage Max 15% of the DC value (at frequency of 100 Hz)
Power supply input must be protected by an For example, type S282 UC-K.
external miniature circuit breaker The rated maximum load of aux voltage which is given as 35 watts. Depending on the voltage
used, select a suitable MCB based on the respective current. Type S282 UC-K has a rated
current of 0.75 A at 400 V AC.
22 ABB
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
Description Value
• Continuously 4A 20 A
• For 10 s 25 A 100 A
Voltage inputs Rated voltage, Un 100 V AC/ 110 V AC/ 115 V AC/ 120 V AC
Voltage withstand:
• Continuous 425 V AC
• For 10 s 450 V AC
1) Residual current
2) Phase currents or residual current
Description Value
ABB 23
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
Description Value
RTD inputs Supported RTD sensor 100 Ω platinum TCR 0.00385 (DIN 43760)
Operation accuracy ±0.1% ±20 ppm per °C of full-scale Ambient temperature -40°C...
70°C
Operation accuracy ±0.1% ±40 ppm per °C of full-scale Ambient temperature -40°C...
70°C
24 ABB
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
Description Value
Breaking capacity when the control-circuit time constant L/R<40 ms, at ≤0.5 A/≤0.1 A/≤0.04 A
U < 48/110/220 V DC
Description Value
Breaking capacity when the control-circuit time constant L/R<40 ms, at ≤1 A/≤0.3 A/≤0.1 A
U< 48/110/220 V DC
Description Value
Breaking capacity when the control-circuit time constant L/R<40 ms, at ≤1 A/≤0.3 A/≤0.1 A
U < 48/110/220 V DC
Description Value
Isolation level 4 kV
ABB 25
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
Screw terminal, pin row header IRIG-B Shielded twisted pair cable
Recommended: CAT 5, Belden RS-485 (9841- 9844) or Alpha Wire
(Alpha 6222-6230)
660 mm 1 mm Snap-in 10 m
Description Value
Front side IP 40
Description Value
Description Value
Altitude up to 2000 m
26 ABB
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
ABB 27
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
100 kHz and 1 MHz burst disturbance test IEC 61000-4-18, level 3
IEC 60255-22-1
• Contact discharge 8 kV
• Air discharge 15 kV
• Conducted, common mode 10 V (rms), f=150 kHz...80 MHz IEC 61000-4-6 , level 3
IEC 60255-22-6
• All ports 4 kV
• Communication 1 kV line-to-earth
• 2s 100 A/m
Power frequency immunity test Binary inputs only IEC 60255-22-7, class A
IEC 61000-4-16
28 ABB
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
• Radiated RF-emission
• Resistance <0.1Ω, 4 A, 60 s
ABB 29
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
Description Reference
LV directive 2006/95/EC
Description Reference
Description
30 ABB
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
Protection functions
Characteristic Value
PHHPTOC:
IFault = 2 × set Start value Typically 19 ms (±5 ms)
PHLPTOC:
IFault = 2 × set Start value Typically 23 ms (±15 ms)
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3)
1) Set Operate delay time = 0.02 s, Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0 × I n , f n = 50 Hz, fault current in one
phase with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Includes the delay of the heavy-duty output contact
ABB 31
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
32 ABB
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
Characteristic Value
DPHLPDOC Current:
±1.5% of the set value or ±0.002 × In
Voltage:
±1.5% of the set value or ±0.002 × Un
Phase angle:
±2°
DPHHPDOC Current:
±1.5% of the set value or ±0.002 × In (at currents in the range of 0.1…
10 × In)
±5.0% of the set value (at currents in the range of 10…40 × In)
Voltage:
±1.5% of the set value or ±0.002 × Un
Phase angle:
±2°
Start time1)2) IFault = 2.0 × set Start value Typically 24 ms (±15 ms)
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms3)
1) Measurement mode = default (depends of stage), current before fault = 0.0 × I n, f n = 50 Hz, fault current in one phase with nominal frequency injected from random phase angle, results
based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 × I n, Start value multiples in range of 1.5...20
ABB 33
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
Characteristic Value
Current:
±1.5% of the set value or ±0.003 × In
Voltage:
±1.0% of the set value or ±0.003 × Un
Impedance:
±2.0% of the set value or ±0.01 Ω static accuracy
Phase angle: ±2°
34 ABB
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
ABB 35
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
36 ABB
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
Characteristic Value
Characteristic Value
Characteristic Value
ABB 37
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3)
1) Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0 × I n, f n = 50 Hz, earth-fault current with nominal frequency injected
from random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 × I n , Start value multiples in range of 1.5...20
38 ABB
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
Characteristic Value
DEFLPDEF Current:
±1.5% of the set value or ±0.002 × In
Voltage
±1.5% of the set value or ±0.002 × Un
Phase angle: ±2°
DEFHPDEF Current:
±1.5% of the set value or ±0.002 × In
(at currents in the range of 0.1…10 × In)
±5.0% of the set value
(at currents in the range of 10…40 × In)
Voltage:
±1.5% of the set value or ±0.002 × Un
Phase angle: ±2°
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3)
1) Set Operate delay time = 0.06 s, Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0 × I n , f n = 50 Hz, earth-fault current
with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 × I n, Start value multiples in range of 1.5 to 20
ABB 39
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in IDMT mode 3) ±5.0% of the set value or ±20 ms
1) Fundamental frequency current = 1.0 × I n. Harmonics current before fault = 0.0 × I n , harmonics fault current 2.0 × Start value . Results based on statistical distribution of 1000
measurement.
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 × I n , Start value multiples in range of 2...20
40 ABB
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
Characteristic Value
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
1) Io varied during the test. Uo = 1.0 × U n = phase to earth voltage during earth-fault in compensated or unearthed network.
2) Includes the delay of the signal output contact. Results based on statistical distribution of 1000 measurements.
ABB 41
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
Characteristic Value
1) Includes the delay of the signal output contact. Results based on statistical distribution of 1000 measurements.
42 ABB
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the set value or ±20 ms
1) Io varied during the test. Uo = 1.0 × U n = phase to earth voltage during earth-fault in compensated or un-earthed network. The residual power value before fault = 0.0 pu, f n = 50 Hz,
results based on statistical distribution of 1000 measurements.
2) Includes the delay of the signal output contact.
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
ABB 43
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
Characteristic Value
Start time 1)2) IFault = 2 × set Start value Typically 23 ms (±15 ms)
IFault = 10 × set Start value Typically 16 ms (±15 ms)
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3)
1) Operate curve type = IEC definite time, negative sequence current before fault = 0.0, f n = 50 Hz
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 × I n , Start value multiples in range of 1.5 to 20
Characteristic Value
1) Overload current > 1.2 × Operate level temperature, Current reference > 0.50 pu
44 ABB
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
Table 59. Three-phase thermal overload protection for feeder (T1PTTR) main settings
Characteristic Value
Current measurement:
±1.5% of the set value or ±0.002 × In
Ratio I2f/I1f measurement:
±5.0% of the set value
ABB 45
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
Characteristic Value
Start time1)2) UFault = 2.0 × set Start value Typically 17 ms (±15 ms)
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms3)
1) Start value = 1.0 × Un, Voltage before fault = 0.9 × U n, f n = 50 Hz, overvoltage in one phase-to-phase with nominal frequency injected from random phase angle
2) Includes the delay of the signal output contact
3) Maximum Start value = 1.20 × U n, Start value multiples in range of 1.10...2.00
Characteristic Value
Start time1)2) UFault = 0.9 × set Start value Typically 24 ms (±15 ms)
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms3)
1) Start value = 1.0 × Un, Voltage before fault = 1.1 × U n, f n = 50 Hz, undervoltage in one phase-to-phase with nominal frequency injected from random phase angle
2) Includes the delay of the signal output contact
3) Minimum Start value = 0.50 × U n, Start value multiples in range of 0.90...0.20
46 ABB
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
1) Positive-sequence voltage before fault = 0.0 × U n, f n = 50 Hz, positive-sequence overvoltage of nominal frequency injected from random phase angle
2) Includes the delay of the signal output contact
Characteristic Value
Start time1)2) UFault = 0.9 × set Start value Typically 28 ms (±15 ms)
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
1) Positive-sequence voltage before fault = 1.1 × U n, f n = 50 Hz, positive-sequence undervoltage of nominal frequency injected from random phase angle
2) Includes the delay of the signal output contact
ABB 47
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
1) Negative-sequence voltage before fault = 0.0 × U n, f n = 50 Hz, negative-sequence overvoltage of nominal frequency injected from random phase angle
2) Includes the delay of the signal output contact
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
1) Residual voltage before fault = 0.0 × U n, f n = 50 Hz, residual voltage with nominal frequency injected from random phase angle
2) Includes the delay of the signal output contact
48 ABB
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
1) Start value = 0.05 × Sn, Reactive power before fault = 0.8 × Start value . Reactive power overshoot 2 times. Results based on statistical distribution of 1000 measurement.
Table 75. Directional reactive power undervoltage protection (DQPTUV) main settings
Characteristic Value
Start time1)2) Start value = 0.05 Hz/s Typically 110 ms (±15 ms)
df/dtFAULT = ±1.0 Hz/s
Operate time accuracy in definite time mode ±1.0% of the set value or ±30 ms
ABB 49
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
Characteristic Value
±0.003 Hz
Operate time accuracy in definite time mode ±1.0% of the set value or ±30 ms
Characteristic Value
±0.003 Hz
Operate time accuracy in definite time mode ±1.0% of the set value or ±30 ms
50 ABB
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
Characteristic Value
±0.003 Hz
Operate time accuracy in definite time mode ±1.0% of the set value or ±30 ms
Characteristic Value
ABB 51
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
Characteristic Value
Characteristic Value
52 ABB
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
ABB 53
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
Protection-related functions
Characteristic Value
Characteristic Value
Table 94. Communication logic for residual overcurrent (RESCPSCH) main settings
Characteristic Value
54 ABB
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
Characteristic Value
Table 98. Current reversal and WEI logic (CRWPSCH) main settings
Table 99. Current reversal and WEI logic for residual overcurrent (RCRWPSCH)
Characteristic Value
ABB 55
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
Table 100. Current reversal and WEI logic for residual overcurrent (RCRWPSCH) main settings
56 ABB
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
Control functions
Characteristic Value
ABB 57
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
Characteristic Value
Table 103. Runtime counter for machines and devices (MDSOPT) main settings
Characteristic Value
Characteristic Value
Operate time1) • NPS function UFault = 1.1 × set Neg Seq voltage Typically 35 ms (±15 ms)
Lev Typically 25 ms (±15 ms)
UFault = 5.0 × set Neg Seq voltage
Lev
• Delta function ΔU = 1.1 × set Voltage change rate Typically 35 ms (±15 ms)
ΔU = 2.0 × set Voltage change rate Typically 28 ms (±15 ms)
1) Includes the delay of the signal output contact, f n = 50 Hz, fault voltage with nominal frequency injected from random phase angle
Characteristic Value
58 ABB
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
Characteristic Value
Characteristic Value
Characteristic Value
ABB 59
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
Characteristic Value
Operation VPPMHAI On -
Off
60 ABB
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
Operation VPHMHAI On -
Off
ABB 61
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
Measurement functions
Characteristic Value
±0.5% or ±0.002 × In
(at currents in the range of 0.01...4.00 × In)
Characteristic Value
±0.5% or ±0.002 × Un
(at voltages in the range of 0.01...1.15 × Un)
Characteristic Value
±0.5% or ±0.002 × Un
(at voltages in the range of 0.01...1.15 × Un)
Characteristic Value
±0.5% or ±0.002 × In
(at currents in the range of 0.01...4.00 × In)
Characteristic Value
±0.5% or ±0.002 × Un
62 ABB
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
Characteristic Value
Characteristic Value
±1.0% or ±0.002 × In
at currents in the range of 0.01...4.00 × In
Characteristic Value
±1.0% or ±0.002 × Un
At voltages in range of 0.01…1.15 × Un
ABB 63
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
21. Front panel user interface with LED indicators. The 15 programmable alarm LEDs can
The 630 series IEDs can be ordered with a detached front- indicate a total of 45 alarms. The local HMI offers full front-
panel user interface (HMI). An integrated HMI is available for panel user-interface functionality with menu navigation, menu
4U high housing. The local HMI includes a large graphical views and operational data. In addition, the local HMI can,
monochrome LCD with a resolution of 320 x 240 pixels (width using PCM600, be configured to show a single-line diagram
x height). The amount of characters and rows fitting the view (SLD). The SLD view displays the status of the primary
depends on the character size as the characters' width and apparatus such as circuit breakers and disconnectors,
height may vary. selected measurement values and busbar arrangements.
GUID-5CFD3446-A92F-4A5F-B60D-90025DCFDC61 V2 EN
Mounting methods:
• Flush mounting
• Semi-flush mounting
• Overhead/ceiling mounting
64 ABB
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
270
252,5
366
13
101,6
180
ø6,8
GUID-945D3C86-A432-4C1F-927A-A208E0C1F5F6 V2 EN
GUID-AF1BEC0B-A9DC-4E9B-9C89-98F28B1C81DB V1 EN
Figure 11. Flush mounting
Figure 12. Semi-flush mounting
,5 22 0
25
25 8,
177
13
265,9
4
22
GUID-A368C5C3-D4A9-40B7-BD0E-181A6BB7ECA6 V1 EN
Figure 14. 6U half 19" unit wall mounted with two mounting
brackets and detached LHMI
ABB 65
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
23. Selection and ordering data The order code consists of a string of letters and digits
generated from the hardware and software modules of the
The IED type and serial number label identifies the protection IED. Use the ordering key information in tables to generate
and control IED. The label placed is on the side of the IED the order code when ordering protection and control IEDs.
case. The IED labels include a set of smaller size labels, one
label for each module in the IED. The module labels state the
type and serial number of each module.
SBFAABABBBAZAZNBXD
# Description
1 IED
630 series, 4U half 19” housing S
630 series, 6U half 19” housing T
630 series, 4U half 19” housing & connector set U
630 series, 6U half 19” housing & connector set V
2 Standard
IEC B
3 Main application
Feeder protection and control F
GUID-3D6E8ED5-075A-4229-82C7-80A7D126FEC2 V5 EN
66 ABB
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
The preconfiguration determines the analog input and binary I/O options. SBFAABABBBAZAZNBXD
The example below shows standard configuration “A” with chosen options.
# Description
4-8 Functional application, preconfigurations:
A = Preconfiguration A for open/closed ring feeder
B = Preconfiguration B for radial overhead/mixed line feeder
C = Preconfiguration C for ring/meshed feeder1)
D = Preconfiguration D for bus sectionalizer
N = None
Pre- Available analog input options Available binary input/
conf. output options
AB = 23 BI + 18 BO
AC = 32 BI + 27 BO
A AB = 4I (I0 1/5 A) + 1I (I0 0.1/0.5 A) + 4U
AD2) = 41 BI + 36 BO
AE2) = 50 BI + 45 BO
AB = 23 BI + 18 BO
AC = 32 BI + 27 BO
B AB = 4I (I0 1/5 A) + 1I (I0 0.1/0.5 A) + 4U
AD2) = 41 BI + 36 BO
AE2) = 50 BI + 45 BO
AB = 23 BI + 18 BO
AC = 32 BI + 27 BO
C1) AB = 4I (I0 1/5 A) + 1I (I0 0.1/0.5 A) + 4U
AD2) = 41 BI + 36 BO
AE2) = 50 BI + 45 BO
AB = 23 BI + 18 BO
AC = 32 BI + 27 BO
D AB = 4I (I0 1/5 A) + 1I (I0 0.1/0.5 A) + 4U
AD2) = 41 BI + 36 BO
AE2) = 50 BI + 45 BO
AA = 4I (I0 1/5 A) + 5U
AB = 4I (I0 1/5 A) + 1I (I0 0.1/0.5 A) + 4U
AA = 14 BI + 9 BO
AC = 3I + 1I (I0 0.1/0.5 A) + 5U
AB = 23 BI + 18 BO
BA = 4I (I0 1/5 A) + 5U +
N 8mA/RTD in + 4mA out AC3) = 32 BI + 27 BO
1) Preconfiguration C requires that the distance protection option is chosen for digit #14 or digit #15
2) Binary input/output options AD and AE require 6U half 19” IED housing (digit #1 = T or V)
3) Binary input/output option AC is not available for 4U high variant (digit #1 = S or U) with RTD card options
(digit #5-6 = BA, BB or BC)
4) Binary input/output option AE is not available for 6U high variant (digit #1 = T or V) with RTD card options
(digit #5-6 = BA, BB or BC)
GUID-D8AAE9B9-CABD-41D3-BBC1-F9377202A589 V5 EN
ABB 67
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
SBFAABABBBAZAZNBXD
# Description
9 Communication modules (Serial)
Serial glass fibre (ST connector) A
Serial plastic fibre (Snap-in connector) B
10 Communication modules (Ethernet)
Ethernet 100Base-FX (LC connector) A
Ethernet 100Base-TX (RJ-45 connector) B
11 Communication (Protocol)
IEC 61850 protocol A
IEC 61850 and DNP3 TCP/IP protocols B
IEC 61850 and IEC 60870-103 protocols C
GUID-28800219-99DA-45EB-919C-C7CBE7B7C69D V5 EN
68 ABB
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
SBFAABABBBAZAZNBXD
# Description
12 Language
Language package Z
13 Front panel
Integrated LHM1) A
Detached LHMI + 1 m cable B
Detached LHMI + 2 m cable C
Detached LHMI + 3 m cable D
Detached LHMI + 4 m cable E
Detached LHMI + 5 m cable F
No LHMI2) N
14 Option 13)
Fault locator and synchro-check A
Fault locator and distance protection 4)
B
Fault locator and power quality 5) C
Synchro-check and distance protection 4) D
Synchro-check and power quality5) E
Distance protection and power quality 4,5)
F
All options Z
None N
15 Option 23)
Fault locator A
Synchro-check B
Distance protection4) D
Power quality5) E
None N
16 Power supply
Power supply 48-125 VDC A
Power supply 110-250 VDC, 100-240 VAC B
17 Reserved
Undefined X
18 Version
Version 1.3 D
ABB 69
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
Example code: S B F A A B A B B B A Z A Z N B X D
Digit (#) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
Code
GUID-05BC330A-4237-4597-B5B0-9FD1B4414DC0 V5 EN
24. Accessories
Flush mounting kit for one 4U half 19” housing IED 1KHL400040R0001
Semi-flush mounting kit for one 4U half 19” housing IED 1KHL400444R0001
Wall-mounting kit (cabling towards the mounting wall) for one 4U half 19” housing IED 1KHL400067R0001
Wall-mounting kit (cabling to the front) for one 4U half 19” housing IED 1KHL400449R0001
19" rack mounting kit for one 4U half 19” housing IED 1KHL400236R0001
19" rack mounting kit for two 4U half 19” housing IEDs 1KHL400237R0001
Overhead/ceiling mounting kit (with cable space) for one 4U half 19” housing IED 1KHL400450R0001
Wall-mounting kit for direct rear wall mounting (with cabling to the front) of one 6U half 19" housing IED 1KHL400452R0001
Wall-mounting kit (with cabling towards the mounting wall) for one 6U half 19" housing IED 1KHL400200R0001
Overhead/ceiling mounting kit (with cable space) for one 6U half 19" housing IED 1KHL400464R0001
19" rack mounting kit for one RTXP8 test switch (the test switch is not included in the delivery) 1KHL400465R0001
19" rack mounting kit for one RTXP18 test switch (the test switch is not included in the delivery) 1KHL400467R0001
19" rack mounting kit for one RTXP24 test switch (the test switch is not included in the delivery) 1KHL400469R0001
Connector set for one 4U housing IED including analog input variant 4I + 5U or 5I + 4U 2RCA021735
Connector set for one 6U housing IED including analog input variant 4I + 5U or 5I + 4U 2RCA021736
Connector set for one 4U housing IED including analog input variant 7I + 3U 2RCA023041
Connector set for one 6U housing IED including analog input variant 7I + 3U 2RCA023042
Connector set for one 4U housing IED including analog input variant 8I + 2U 2RCA023039
Connector set for one 6U housing IED including analog input variant 8I + 2U 2RCA023040
70 ABB
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
26. Tools browser (IE 7.0 or later). For security reasons, the web-
The IED is delivered either with or without an optional factory browser based user interface is disabled by default. The
made preconfiguration. The default parameter setting values interface can be enabled with the PCM600 tool or from the
can be changed from the front-panel user interface, the web- front panel user interface. The functionality of the interface is
browser based user interface (WebHMI) or the PCM600 tool by default limited to read-only, but can be configured to
in combination with the IED specific connectivity package. enable read and write access by means of PCM600 or the
local HMI.
PCM600 offers extensive IED configuration functions such as
IED application configuration, signal configuration, DNP3 The IED connectivity package is a collection of software and
communication configuration and IEC 61850 communication specific IED information, which enable system products and
configuration including horizontal communication, GOOSE. tools to connect and interact with the IED. The connectivity
packages reduce the risk of errors in system integration,
When the web-browser based user interface is used, the IED minimizing device configuration and set-up times.
can be accessed either locally or remotely using a web
ABB 71
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
Parameter setting ● ●
Disturbance handling ● ●
Signal monitoring ● ●
Event viewer ● ●
Hardware configuration - ●
Signal matrix - ●
Communication management - ●
User management - ●
Creating/handling projects - ●
IED Compare - ●
27. Supported ABB solutions among the distinctive features of the protection system
ABB’s 630 series protection and control IEDs together with approach enabled by the implementation of the IEC 61850
the Grid Automation controller COM600 constitute a genuine substation automation standard.
IEC 61850 solution for reliable power distribution in utility and
industrial power systems. To facilitate and streamline the At the substation level COM600 utilizes the logic processor
system engineering ABB’s IEDs are supplied with and data content of the bay level IEDs to offer enhanced
Connectivity Packages containing a compilation of software substation level functionality. COM600 features a Web-
and IED-specific information including single-line diagram browser based HMI providing a customizable graphical
templates, manuals, a full IED data model including event and display for visualizing single line mimic diagrams for
parameter lists. By utilizing the Connectivity Packages the switchgear bay solutions. To enhance personnel safety, the
IEDs can be readily configured via the PCM600 Protection WebHMI also enables remote access to substation devices
and Control IED Manager and integrated with the Grid and processes. Furthermore, COM600 can be used as a local
Automation controller COM600 or the MicroSCADA Pro data warehouse for technical documentation of the substation
network control and management system. and for network data collected by the IEDs. The collected
network data facilitates extensive reporting and analyzing of
The 630 series IEDs offer support for the IEC 61850 standard network fault situations using the data historian and event
also including horizontal GOOSE messaging. Compared with handling features of COM600.
traditional hard-wired inter-device signaling, peer-to-peer
communication over a switched Ethernet LAN offers an COM600 also features gateway functionality providing
advanced and versatile platform for power system protection. seamless connectivity between the substation IEDs and
Fast software-based communication, continuous supervision network-level control and management systems such as
of the integrity of the protection and communication system, MicroSCADA Pro and System 800xA.
and inherent flexibility for reconfiguration and upgrades are
72 ABB
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
Product Version
ABB 73
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
GUID-88CD16F3-27E5-4657-BDAF-46D27B4970D8 V1 EN
74 ABB
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
GUID-5E27DD50-FD15-4824-BDFB-DD52E29730EA V2 EN
Unit BI/BO
4U X319 + X3161)
X324 + X321
6U X324 + X3211)
X329 + X326
X334 + X331
X339 + X336
ABB 75
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
GUID-CB7B1CF8-A0E4-42F5-998C-701641515127 V1 EN
29. References
The www.abb.com/substationautomation portal offers you
information about the distribution automation product and
service range.
76 ABB
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
Protection
Three-phase directional overcurrent protection, low stage DPHLPDOC 3I> -> 67-1
Three-phase directional overcurrent protection, high stage DPHHPDOC 3I>> -> 67-2
ABB 77
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
Protection-related functions
Current reversal and WEI logic for residual overcurrent RCRWPSCH CLCRWN 85NCRW
Control
Power quality
78 ABB
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
Measurement
ABB 79
Feeder Protection and Control 1MRS756976 G
REF630
Product version: 1.3
80 ABB
81
Contact us
www.abb.com/substationautomation