Expansion Tank Calculation for Chilled Water Primary &
Secondary Network _ET-GR-01
[(B)-1]-3a a7
G2
y=V, X
Ao A)
Vr= Volume of Expansion Tank (Gallons)
Vs= Volume of Water in Piping System (Gallons)
‘Vs = 261300 gallon
{as per attached schedule for quantity survey of network)
supply Water Temperature
Ambient Temperature (Design Weather Data)
he
(From design schedule $11013-010-10-01-MH-603-REV 1 date 19/5/2011)
"cea F
Ty 46°C = 114.98°F
(From design schedule 1-MH-FC-04-00-03-005 REV 0 date 2/5/2011)
T=
TCR) aT =73.98 °F
v1 = SpVispecific volume) of H:O at Ti = 0.01602 (ft?/1b)
vs= SpV(specific volume) of HeO at Ts= 0.01620 (ft?/1b) (From attached sehedue)
c= Linear Coefficient of Expansion
asia, =6.5 x 10°
MyContinue Expansion Tank Calculation for Chilled Water
Primary & Secondary Network ET-GR-01
Pa = Atmospheric Pressure (14.7 Psia)
= System Fill Pressure/Minimum System Pressure (Psia)
Ps = System Operating Pressure/Maximum Operating Pressure (Psia)
lead of secondary chw pump = 500 kpa =72.5 psia
Operating pressure of secondary chw pump = 1600kpa = 232 psia
{From design schedule $11013-010-TD-01-MH-603-REV 1 date 19/5/2011)
[(ooie2t.)- 1]+3 6.5x10-9)(73.98)
GE a)
V, = 261300 X
V; = 18352 gallon
V, /5 = 3670 gallon
V; For each with safety factor 10 % = 4037 gallon
=15281 liter
uy‘CENTRAL CHILLED WATER PLANT AT AIYAD
(CHILLED WATER NETWORK TAKE-OFF
‘SECONDARY CHILLED WATER CIRCUTT ONLY,
ToraLvowun (ms) | 128.054