Expansion Tank Calculation for Chilled Water Primary & Secondary Network _ET-GR-01 [(B)-1]-3a a7 G2 y=V, X Ao A) Vr= Volume of Expansion Tank (Gallons) Vs= Volume of Water in Piping System (Gallons) ‘Vs = 261300 gallon {as per attached schedule for quantity survey of network) supply Water Temperature Ambient Temperature (Design Weather Data) he (From design schedule $11013-010-10-01-MH-603-REV 1 date 19/5/2011) "cea F Ty 46°C = 114.98°F (From design schedule 1-MH-FC-04-00-03-005 REV 0 date 2/5/2011) T= TCR) aT =73.98 °F v1 = SpVispecific volume) of H:O at Ti = 0.01602 (ft?/1b) vs= SpV(specific volume) of HeO at Ts= 0.01620 (ft?/1b) (From attached sehedue) c= Linear Coefficient of Expansion asia, =6.5 x 10° My Continue Expansion Tank Calculation for Chilled Water Primary & Secondary Network ET-GR-01 Pa = Atmospheric Pressure (14.7 Psia) = System Fill Pressure/Minimum System Pressure (Psia) Ps = System Operating Pressure/Maximum Operating Pressure (Psia) lead of secondary chw pump = 500 kpa =72.5 psia Operating pressure of secondary chw pump = 1600kpa = 232 psia {From design schedule $11013-010-TD-01-MH-603-REV 1 date 19/5/2011) [(ooie2t.)- 1]+3 6.5x10-9)(73.98) GE a) V, = 261300 X V; = 18352 gallon V, /5 = 3670 gallon V; For each with safety factor 10 % = 4037 gallon =15281 liter uy ‘CENTRAL CHILLED WATER PLANT AT AIYAD (CHILLED WATER NETWORK TAKE-OFF ‘SECONDARY CHILLED WATER CIRCUTT ONLY, ToraLvowun (ms) | 128.054 WM