You are on page 1of 2

Appendix B - 60002 Genelba - Wind loads on outlet duct 11-4-2018

Wind loads according ASCE 7-05

Wind X
L= 1.9 m
B= 8.1 m
L/B= 0.2 -
(acc. App. A)
Section Height qz / qh cp Wind pressure Wind pressure
[m] [N/m2] [N/m2] [Mpa]
1 10.1 1770.5 0.8 1416.4 0.0014

2 16.5 1962.5 0.8 1570.0 0.0016

3 26.75 2172.1 0.8 1737.7 0.0017

-1 26.75 2172.1 -0.5 -1086.1 -0.0011

-2 26.75 2172.1 -0.5 -1086.1 -0.0011

-3 26.75 2172.1 -0.5 -1086.1 -0.0011

top/bottom 26.75 2172.1 -1.2 -2541.4 -0.0025

Wind Y
L= 8.1 m
B= 1.9 m
L/B= 4.3 -
(acc. App. A)
Section Height qz / qh cp Wind pressure Wind pressure
[m] [N/m2] [N/m2] [Mpa]
1 10.1 1770.5 0.8 1416.4 0.0014

2 16.5 1962.5 0.8 1570.0 0.0016

3 26.75 2172.1 0.8 1737.7 0.0017

-1 26.75 2172.1 -0.2 -434.4 -0.0004

-2 26.75 2172.1 -0.2 -434.4 -0.0004

-3 26.75 2172.1 -0.2 -434.4 -0.0004

top/bottom 26.75 2172.1 -1.2 -2541.4 -0.0025

1-2
Appendix B - 60002 Genelba - Wind loads on outlet duct 11-4-2018

2-2