TEST REPORT
REPORT NO.: 2015EEDA0100
PAGE
4 OF 12
Thi Test Report rofore only o camples cubmiied by the applicant to SIRIM GAS International Sdn, Bh
SIRIM QAS International Sdn. Bhd. This test report shall not be roproduced, except In full and shall not be used for
advertising purposes by any means or forms without wrttan approval from Managing Director, SIRIM QAS International
San, Bhd. Ploase refer overleaf for Conditions Relating To The Uso of Test Report.
snd tested by
Applicant PRODUCT CERTIFICATION SECTION
SIRIM QAS INTERNATIONAL SDN. BHD.
(wp : Nurrulhuda bt Mahmud, FIRE)
Manufacturer MEGAPOWER MANUFACTURING (M) SDN. BHD
LOT 1888 KAWASAN PERINDUSTRIAN BUKIT 8ELIMBING
43300, BALAKONG, SELANGOR DARUL EHSAN
Product RIGID PVC CONDUIT FOR ELECTRICAL INSTALLATION
Reference Standard) : BS EN 61386-21:2004 + A11: 2010
Method of test
Legrand H20W, Legrand H25W
Description of Brand Name : Legrand
Model / Type
Size 20 mm, 25 mm
Classification : 4421
Date received 25 MAC 2015
Job No. JD151420063 (PM027701)
Overall test result: COMPLIED
Issue date 31 MAC 2015
(MOHAMAD ASNANBIN AHNS
Testing Executive
AS
212 Al/ SP yoved Signatory;
‘ZAMAI BIN MUSTAFFA)
Head
Blectrical & Electronic | Section
Testing Services DepartmentREPORT NO.: 2015EEDA0100 PAGE :20F 12
“This Test Rept veers only Yo samples submitted by the appieant te SIRINT GAS Tniomatonal Sah, Bhd. and tested by SIRIMT ONS
Intemational Sen. Bho. This test repo shal not be fepredced, except in Tul and shall rot be wee for adverteng purposes by any
‘means of forms wihoutwiten approval from Maneging Director, SIRIMI QAS Intemational Sn Bhd
SUMMARY OF TESTS:
This is a type test report as requested by the applicant.
2. This report must to be read in conjunction with report no. 2014EEDA0177.
3. The samples submitted for testing has been checked in accordance to BS EN 61386-
21:2004 + A11: 2010.
4. Unless otherwise specified, tests were conducted at ambient temperature of 25 + 5 ° C.
5. The abbreviation used in this test report denotes as follows;
PASS:
NA: Not Applicable with the requirement
FAIL: Did Not Comply with the requirement
‘omplied with the requirement
SUMMARY OF RESULTIS:
1. The submitted test samples as described in this test report complied with the requirements of
BS EN 61386-21:2004 + A11: 2010.
ADDITIONAL INFORMATION:
1. Tested by: Hasbar Rafeg Bin Abd Rahim
2. Checked by: Mohamad Asnan bin Ahmad
3. Date of test sample(s) received;
a) 1" submission: 21 JUL 2014
— ba 1REPORT NO.: 2015EEDA0100 PAGE: 9 OF 12
“Ths Test Report veers only To samples submited by the applicant to SIRiNi GAS Intemational San, Bhd. and Tested by SIRI GAS
Intemational Sn. Ghd. This test roport shal not be reproduced. except in ful and shal rot be used for advertsing purboses by any
‘means or forme without wetten approval rom Mneging Director, SIRIMA QAS Intemational San, Bhd
Clause Requirement Remark Results
The measured resistance shall be more than 5 NA
Mo
12 Thermal properties Pass
724 Non metallic and composited material shall be Pass
resistance to heat
The hear load as declared by the compression Pass
classification (mfg. to dectare)
122 ‘Three samples each 100 mm long placed in Pass
apparatus.
Shall be kept in a heating cabinet for 4 hrs ( the Pass’
‘temperature as in table 2 (BS standard))
Then loaded with mass (table 8 in BS standard) |4.0 kg Pass
for 24 hrs.
After 24 hours the setup is cooled to ambient Pass
temp.
The weight are removed and an appropriate Pass
‘gauge is passed through the conduit on its own
‘weight in vertical position
12.3 The gauge shall easily pass through the conduit. Pass
13 Fire hazard Pass
13.1 Reaction to fire NA
13.1.3 [Spread of fire Fas
13.1.3.1 Non flame propagating conduit shall be tested; NA
Glow wire test (IEC 60695-2-11) NA
Temperature of glow wire (750°C) NA
No visible flame or sustained glowing. NA
13.1.3.2 Checked by applying a 1KW flame (IEC 60695- Pass
11-2)
Three samples are tested with each of length Pass
|675 mm placed in a metal enclosure.
[A steel rod of (sizes from 2 mm to 16 mm) based Pass
on diameter of the conduit is inserted through the
sample.
The steel rod is mounted rigi Bend Pass
vertically. Z ernatio x
The burner is supported Pass