Insulation resistance (IR) value for electric
motor
=]
IR (Min) = ‘or most windings made
V4 afore about 1970, all field
jindings, and others not
lescribed below:
feo = 100. For most de armature and
1¢ windings built atler about
1970 (form wound coils)
feo) =5 — For most machines with
\dom -wound stator coils
nd form-wound coils rated
alow 1kV
Example-1: For 11KV, Three Phase Motor.
IR Valug =11+1=12 MO but as per IEFE43 It should be 100 MO.
» Exemple-2: For 415V,Three Phase Motor
IR Value =0.415+1=1.41 MQ but as per IEEE43 It should be 5 MO.
» As per IS 732 Min IR Value of Motor=(20XVoltage(p-p/(1000+2XKW)
IR Value of Motor as per NETA ATS 2007. Section 7.15.1Test | Min IR
Voltage | Value
50V s00v DC | 25 MO
}00V (1000V DC | 100MQ
ooov tooov Dc | 100Ma
500V 1000V DC | 500MQ
2500V DC
S000 j2500V DC | 5000MQ
5000V s000V Dc | 20000Ma
p4500V_ 15000V |100000MO
IR Value of Submersible Motor:
A used motor which can be reinstalled 10 MQ
lotor Installed in Well (With Cable)
A used motor which can be reinstalled 0.5 MO.
Index?
5. IR Value for Electrical cable and wiring
For insulation testing, we need to disconnect from panel or equipment and keep them isolated from power
supply. The_wiring and cables need to test for each other ( phase to phase ) with a ground ( E ) cable. The
Insulated Power Cable Engineers Association (IPCEA) provides the formula to determine minimum insulation
resistance values.
R=K x Log 10 (Did)
R = IR Value in MQs per 1000 feet (305 meters) of cable.
K = Insulation material constant.( Varnished Cambric=2460, Thermoplastic Polyethlene=50000,Composite
Polyethylene=30000)
D = Outside diameter of conductor insulation for single conductor wire and cable ( D = d + 2c + 2b diameter
of single conductor cable )
d — Diameter of conductor
¢ — Thickness of conductor insulation
b — Thickness of jacket insulation
HV test on new XLPE cable (As per ETSA Standard)